KJM MANDÍK
–
Detailed operating instructions
M&C KJMPNO 07/2022
MANDÍK, a.s.,
15
than the non-sensitivity, then a damper failure may be indicated and consequently the
component with that damper or the entire AC unit may shut down.
Temperatures
6.1
This menu contains information about the measured temperatures according to the
settings in the configuration. The location of the temperature sensors in the air handling unit and
air ducts can be seen in Figure 2.
Legend:
T1 –
Outdoor
(ODA)
T4 –
Preheat
–
after 1st heating
T7 –
Room
T2 –
Inlet
T5 –
Reheat
–
before 2nd heating
T8 –
Extract
(ETA)
T3 –
Supply
Recuperation
T6 –
Supply
(SUP)
T9 –
Extract
Recuperation
T10 –
Exhaust
(EHA
)
Fig. 2 - Temperature sensor locations
Following are the descriptions of every temperature sensor, including installation methods
and other related settings:
Room
– if configured, the sensor should be placed in the room that is the target of the air
conditioning so that the measured temperature is not affected by any local influences, such
as radiators, sunlight through a window, etc. If not configured, it can be replaced by a supply