Design  .01  with  mechanical  control  can  be  equipped  by  one  or  two  limit  switches  signalling

position of the damper blade "CLOSED". Limit switch is connected via duct.

Design .11

Design .15

Limit switch

“CLOSED”

Limit switch

“CLOSED”

Limit switch

“CLOSED”

 

Design according to fire resistance

EIS 120

EIS 90

EIS 60

 

Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3.

 

Temperature in the place of installation is permitted to range from - 20°C to + 50°C.

 

Design with mechanical control

 

Design with mechanical control with a thermal protective fuse (inner mechanical control which

actuates  the  shutting  device  within  120  seconds  at  latest  after  the  nominal  start  temperature

72  °C  has  been  reached.  Automatic  initiation  of  the  shutting  device  is  not  activated  if  the

temperature does not exceed 70 °C.

Содержание CFDM

Страница 1: ......

Страница 2: ...ure loss 14 8 Material 15 9 Inspection testing 15 15 10 Logistic terms 15 11 Assembly 15 12 Entry into service and revisions 16 13 Data label 16 14 Quick review 16 17 15 Ordering key 17 These technical specifications state a row of manufactured sizes and models of fire dampers further only dampers CFDM It is valid for production designing ordering delivery assembly and operation ...

Страница 3: ...ccordance with EN 1366 2 Classified acc to EN 13501 3 A1 Fire resistance EIS 120 EIS 90 EIS 60 Internal leakage class 2 acc to EN 1751 external leakage is equal to ducting system Corrosion resistant acc to EN 15650 ES Certificate No 1391 CPR 2016 0082 Declaration of Perfomance No PM CFDM 01 16 1 Working conditions Exact damper function is provided under the following conditions a Maximum air circu...

Страница 4: ...ers are designed for macroclimatic areas with mild climate according to EN 60 721 3 3 Temperature in the place of installation is permitted to range from 20 C to 50 C Design with mechanical control Design with mechanical control with a thermal protective fuse inner mechanical control which actuates the shutting device within 120 seconds at latest after the nominal start temperature 72 C has been r...

Страница 5: ...er blade 3 Shutting spring 4 Thermal fuse 5 Locking planchet 1 Fire damper CFDM 2 Dish valve 3 Duct COM black NO red NC white Nominal voltage current DC 30 V 0 1 A Degree of protection IP 67 Ambient temperature 40 C 85 C 1 2 4 3 5 1 2 3 ...

Страница 6: ...nstallation space volume installation gap To provide needed access space to the control device all other objects must be situated at least 350 mm from the control parts of the damper Inspection hole must be accessible Damper has to be accessible for regular checks and maintenance Fire damper is inserted inside the duct Blade has to be inside of fire separating construction after closing The distan...

Страница 7: ...truction made e g of normal concrete masonry porous concrete with minimum thickness 100 mm or into solid ceiling construction made e g of normal concrete with minimum thickness 110 mm or porous concrete with minimum thickness 125 mm The fire damper can be integrated into a gypsum wall construction with fire classification EI 120 or EI 90 ...

Страница 8: ...th fire resistant coating 15 Wet mortar or gypsum 16 Dry mineral wool boards with fire resistant coating 17 Statement of installations the fire dampers CFDM 25 100 Position 1 Fire damper CFDM 2 Solid wall construction 3 Mortar or gypsum 4 Duct Make installation Opening Install duct in the Opening Fill gap Insert damper in the duct ...

Страница 9: ... materials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT Fire resistant board and fire stop coating can be replaced by another approved fire sealing system for damper installation with equivalent material properties D 60 to 800 max 1650 D 60 to 800 max 2050 Make installation Opening Install duct in the Opening Fill gap and cover duct by fire resistant coating Insert damper in the duct 50 50 ...

Страница 10: ... 3 Mortar or gypsum 4 Duct Installation opening has to be reinforced by profile UW CW Profil is fixed by screws 3 5 mm with corresponding length Distance between screws 200 mm Make installation Opening Install duct in the Opening Fill gap Insert damper in the duct ...

Страница 11: ...il is fixed by screws 3 5 mm with corresponding length Distance between screws 200 mm Make installation Opening Install duct in the Opening Fill gap and cover duct by fire resistant coating Insert damper in the duct Position 1 Fire damper CFDM 2 Gypsum wall construction 3 Fire resistant board 4 Fire stop coating thickness 1 mm 5 Glass fiber felt with aluminium foil width 50 mm thickness 5 mm 6 Duc...

Страница 12: ...on 1 Fire damper CFDM 2 Solid wall construction 3 Mortar or gypsum 4 Duct 25 150 Install duct in the Opening Insert damper in the duct Make installation Opening Fill gap min 110 Concrete min 125 Aerated concrete ...

Страница 13: ...0 max 2050 D 60 to 800 max 1650 Make installation Opening Install duct in the Opening Fill gap and cover duct by fire resistant coating Insert damper in the duct Position 1 Fire damper CFDM 2 Ceiling wall construction 3 Fire resistant board 4 Fire stop coating thickness 1 mm 5 Glass fiber felt with aluminium foil width 50 mm thickness 5 mm 6 Duct Used materials example 3 Hilti CFS CT B 1S 140 50 4...

Страница 14: ... the duct 50 Insert valve housing in the duct and screw to the construction Insert valve in the housing Pressure loss calculation p w 2 p Pa pressure loss w m s air flow speed in nominal damper section kg m air density coefficient of local pressure loss for the nominal damper section see Tab 7 1 1 ...

Страница 15: ... 2 kg m Tab 3 2 1 Sef 0 0206 m Calculation w m s V m h 3600 Sef m w 8 09 m s Tab 7 1 1 0 4167 Calculation p w 2 0 4167 1 2 8 09 2 16 4 Pa Diagram 6 2 1 LWA 52 dB Determination of pressure loss by using diagram 9 2 1 1 2 kg m and noise data Coefficient of local pressure loss ...

Страница 16: ...st not exceed 40 C Dampers must be protected against mechanic damages when transported and manipulated During transportation the damper blade must be in the CLOSED position Dampers are stored indoor in environment without any aggressive vapours gases or dust Indoor temperature must be in the range from 5 C to 40 C and maximum relative humidity 80 Dampers must be protected against mechanic damages ...

Страница 17: ...o Serial number Fert Nr Numéro de serie SAMPLE Provedení Design Ausführung Conception 01 Certifikace Certificate Zulassungs Nr Certifikat Hmotnost Weight Gewicht Poids 1391 CPD 2016 0082 16 200 0 5 EN 15650 2010 TPM 118 16 Brandschutzklappe Clapet coupe feu 100 Mortar or gypsum EIS 120 EIS 90 EIS 60 12 100 Mineral wool boards with fire resistant coating EIS 90 EIS 60 13 100 Mortar or gypsum EIS 12...

Страница 18: ...th inner mechanical control and limit switch CLOSED 11 Thermal with inner mechanical control and two limit switches CLOSED 15 technical specifications TVO disch valve outlet TVP disch valve inlet 60 EIS60 90 EIS90 120 EIS120 design acc Tab 17 1 1 size type ...

Страница 19: ...18 ...