M&G DuraVent PolyPro 4PPS-ADL Скачать руководство пользователя страница 4

4

LISTING
Listed to ULC S636 
Rated Class IIA, IIB, and IIC vent system

maximum temperature 230°F (110 °C)
maximum positive pressure 15 in-w.c. 

Massachusetts Plumbers Board, 

# G1-0811-42

APPLICATION
ANSI Category II and IV gas-burning 
appliances
Appliances specifically tested and listed to 
use M&G DuraVent PolyPro Venting

PERMITS
Check with your local Building Official, Fire 
Official, or other authority having jurisdiction 
regarding permits, restrictions, and 
installation inspections in your area.

GENERAL INSTALLATION NOTES

Read these instructions before beginning.  
You must use only authorized M&G DuraVent 
PolyPro vent parts, or other parts specifically 
authorized in these instructions and/or listed 
by the appliance manufacturer in order to 
maintain a safe, approved system.

• 

Do not fill any air space clearance   

(Table 1) with insulation.

• 

Do not mix parts or try to match with 
other products or use improvised 
solutions.  

• 

Do not install damaged or modified 
parts. 

• 

Use soapy water to lubricate gaskets.

• 

Never use Petroleum base lubricants.

If these directions and those of the appliance 
manufacturer differ, follow the more 
conservative requirements. If you have any 
questions, contact either your dealer or M&G 
DuraVent directly.  A venting system must 
not be routed into, through, or within any 
other vent, such as an existing masonry or 
factory-built chimney flue, unless that vent 
or chimney is not being used to vent another 
appliance and is only used as a conduit for 
the gas-vent system.  Plastic venting systems 
shall not pass through fire rated separations 
without approved firestopping.   

Refer to the appliance manufacturer's 
instructions for maximum and minimum 
vent lengths permitted with your specific 
appliance model. This information should 
include guidance on the maximum number 
of elbows and related pressure-drops. The 
total vent length from the appliance to 
the termination shall not be greater than 
specified by the appliance manufacturer. 
If specific guidance is not offered by the 
appliance manufacturer as to Equivalent 
Vent Lengths (EVL) for vent components, the 
general guidelines in Table 2 can be used.

CONDENSATE DRAIN (Fig.1)

 

Refer to the appliance manufacturer’s 
installation instructions for requirements of 
condensate drainage.  Ensure proper system 
slope for drainage.  (Fig.7)

Table 1

Clearance to Combustibles

 

VENT PIPE ORIENTATION

Single Wall

Vertical

Horizontal

Up to 190°F

0"

0"

Up to 230°F

0"

¼" (6mm) all around

Concentric

Up to 230°F

0"

0"

 

The vent system must be compliant in 

accordance with local code requirements 

and appropriate National Codes:  In 

the US: NFPA 54 / ANSI Z223.1 National 

Fuel Gas Code or the International Fuel 

Gas Code.  In Canada: CAN/CGA-B149.1 

Natural Gas Installation Code or CAN/CGA-

149.2 Propane Installation Code.

IMPORTANT

Содержание DuraVent PolyPro 4PPS-ADL

Страница 1: ...PolyPro Installation Instructions PolyPro Single Wall Gas Vent System for Category II IV Gas Burning Appliances ...

Страница 2: ...allation Check the integrity of ALL joints upon completion of assembly This venting system must be free to expand and contract under normal operation Assure unrestricted vent movement where required through walls ceilings and roof penetrations This venting system must be supported in accordance with these instructions Do not mix pipe fittings or joining methods from different vent system manufactu...

Страница 3: ...TS 4 GENERAL INSTALLATION NOTES 4 CLEARANCES TABLE 1 4 CONDENSATE DRAIN 4 JOINT CONNECTIONS 5 EQUIVALENT LENGTH CHART TABLE 2 5 APPLIANCE CONNECTION 6 INSTALLATION 7 ENCLOSURE REQUIREMENTS 7 HORIZONTAL TERMINATIONS 8 WALL AND CEILING PENETRATION TABLE 3 9 VERTICAL TERMINATIONS 11 MULTIPLE VENT RUNS 12 ALUMINUM FLEX AIR INTAKE 13 MAINTENANCE 13 WARRANTY 14 ...

Страница 4: ...thin any other vent such as an existing masonry or factory built chimney flue unless that vent or chimney is not being used to vent another appliance and is only used as a conduit for the gas vent system Plastic venting systems shall not pass through fire rated separations without approved firestopping Refer to the appliance manufacturer s instructions for maximum and minimum vent lengths permitte...

Страница 5: ...e female hub Fig 3 For PP Metal pipe with Locking Button Insert locking button into locking band recess rotate button away from Locking Band Clasp insert pipe sections push lock band clamp downward into socket disengage button 1 4 from socket Screws are not allowed for joint connection Never penetrate the wall of PolyPro vent pipe Exception a SS screw may be used outside the building on exterior t...

Страница 6: ...EN CLAMPS ON RUBBER COUPLER ADAPTER OR FERNCO STYLE ADAPTER TO SECURE VENT PIPE TO APPLIANCE mandatory on all exhaust vent joints on pipe sizes from 2 up to 4 Fig 2 3 For 5 8 diameter Locking Bands are not required but strongly recommended at every exhaust vent joint Fig 2 3 Locking bands are optional for air inlet vent joints Fig 2 3 POLYPRO TO DURAVENT SECURITY CHIMNEY METAL VENT CONNECTION Appr...

Страница 7: ...vent and other certain clamp styles or greater All thread may be used as an extension 6 Vertical installations must be supported every 10 feet 3 meters or less Fig 8 7 Do not install enclose PolyPro in the stud space of a wall 8 Elbows andTees are sufficiently supported when a bracket is fixed at the female end of the connected straight section Fig 8 PP Pipe sections must be disengaged 1 4 5 8 per...

Страница 8: ...enclosure and joints cannot buckle wall straps are not required provided upper and lower supports are proper Figure 10 ALIGN TABS WITH MOUNTS GASKET EXTERIOR WALL PLATE INTERIOR WALL PLATE Figure 11 REMOVE GASKET INSERT BIRD GUARD FIRESTOPS Fig 9 1 Firestops are required at each ceiling floor penetration including an attic Firestops are not required at the roof deck penetration 2 Cut and or frame ...

Страница 9: ...mm 6 1 8 155mm N A N A N A TWIN PIPE HORIZONTAL CLASS IIB 7 3 8 x 25 8 187mm x 65mm 8 3 8 x 37 8 212 x 85mm 9 x 43 8 228 x 100mm N A N A N A TWIN PIPE HORIZONTAL CLASS IIC Framing Dimensions 8 x 3 200 x 77mm 8 7 8 x 37 8 225 x 98mm 9 3 8 x 4 3 8 238 x 112mm N A N A N A SINGLE HORIZONTAL CLASS IIB 25 8 65mm 3 3 8 85mm 4 100mm N A N A N A SINGLE HORIZONTAL CLASS IIC Framing Dimensions 3 77mm 3 7 8 9...

Страница 10: ...em to from termination to appliance Horizontal Concentric Fig 13 1 Locate penetration 2 Cut hole Table 3 3 Attach and seal exterior exterior wall plate onto outside wall 4 Slide cap through exterior wall plate into hole from outside building Cap must not be installed sloped downward 5 Orient termination so air intake slots face down 6 Seal termination to exterior wall plate with silicone sealant 7...

Страница 11: ... AIR INLET Figure 18 TERMINATION CAP FLASHING STORM COLLAR SUPPORT CLAMP Figure 17 CENTERLINE OF EXHAUST OUTLET OF APPLIANCE Vertical Concentric Fig 18 1 Locate penetration Fig 17 2 Cut hole in roof Table 3 3 Cut hole in ceiling above appliance Cut hole s big enough for pipe in all ceilings above appliance if installing in a multi story installation 4 Firestop each ceiling penetration 5 Attach fla...

Страница 12: ...The lower portion of the vent system must be supported and firestopped as detailed earlier in these and or the PP Flex instructions provided separately RIGID BLACK UV PROTECTED POLYPRO GASKET PLATE STAINLESS RELINE HANGER BRACKET POLYPRO FLEX LINER RIGID POLYPRO STAINLESS UPPER SUPPORT PLATE GASKET PLATE HANGER MOUNT HARDWARE FLANGE BIRD GUARD Figure 21 CLEARANCE HOLE 1 75 MAT L SPACE MIN Vertical...

Страница 13: ...ed operation See Fig 24 for the lower install MAINTENANCE Have your venting system checked annually This can be done easily by the same technician who inspects services the appliance Recommended areas to inspect are as follows Check areas of the Venting System which are exposed to the elements for wear or damage If damage is found the components should be replaced immediately Where possible look i...

Страница 14: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 15: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 16: ...nty This warranty provides no cash surrender value The terms and conditions of this warranty may not be modified altered or waived by any action inaction or representation whether oral or in writing except upon the express written authority of an executive officer of DuraVent This product is intended for venting only category II IV appliances burning Natural Gas Propane and Oil All other fuels are...

Отзывы: