Commissioning and operation
20
Starting
Danger:
Before starting the engine, ensure that nobody is in the danger area around
the engine.
Operation with asynchronous generator
D
Operate starter to crank engine with gas supply shut off and without ignition for a few
seconds (air purge).
D
Starting control will close throttle valve in gas mixer (gas mixer is not part of MAN’s ex-
tent of delivery).
D
Switch on ignition.
D
Solenoid valve for gas supply opens (not part of MAN’s extent of delivery).
D
Engine will start firing and run up to 1,300 to 1,400 rpm without generator load on id-
ling gas flow.
D
The starting control will move the throttle valve into operating position. Simultaneously,
the generator will be connected to the system.
Operation with synchronous generator
D
Operate starter and crank engine with gas supply shut off and without ignition for a few
seconds (air purge). The electronic speed governor (not part of MAN’s extent of deliv-
ery) has to be switched on at the same time.
D
Switch on ignition.
D
Solenoid valve for gas supply opens (not part of MAN’s extent of delivery).
D
Engine will start firing.
D
The electronic speed governor (nicht Lieferumfang von MAN) maintains the engine
speed at the value set on the set-point potentiometer.
Danger:
Ensure that the engine cannot be started by unauthorised persons.
Содержание E 0824 E 301
Страница 1: ......
Страница 2: ......
Страница 14: ...Commissioning and operation 12 Engine views E 0824 E 301 302 1 2 3 4 5 6 7 8 9 10 11 12...
Страница 16: ...Commissioning and operation 14 Engine views E 0826 E 301 302 1 2 3 4 5 6 7 8 9 10 11 12...
Страница 35: ...Notes 33...
Страница 41: ...39 Circuit diagrams...
Страница 45: ...Notes 43...
Страница 47: ......
Страница 48: ......