DUCT TEMPERATURE SENSORS

Page 3 of 4

RoHS

CHECKOUT

Allow the sensor to stabilize in the duct air stream for a minimum of five 

minutes before taking a resistance measurement.

1.  Disconnect the sensor lead wires from the controller.
2.  Connect an ohmmeter across the lead wires.
3.  Ensure that nominal resistance measurements are in accordance 

     with the resistance/temperature curves.  (Refer to 

Tables 1

 

& 2

.     

     For complete 

Resistance vs. Temperature

 tables, please refer to 

     TI.700-11

 - Temperature Sensor section.)

4.  Reconnect sensor lead wires to the controller.
5.  Check operation of the complete control system.

MAINTENANCE

Regular maintenance of the total system is recommended to 

assure sustained optimum performance.

FIELD REPAIR

None. Replace with a functional unit.

DIMENSIONAL DATA

TE-701/702 Duct Temperature Sensor dimensions shown in inches and 

millimeters (mm).

Figure 4

TE-701-A & TE-701-B

Figure 5

TE-701-C & TE-701-D