trouBlE SHootInG

Malfunction

Cause

Remedy

the load does not work

Incorrect light-control setting selected

adjust setting

load faulty

replace load

Mains switched off

Switch on

the load is always on

continuous movement in the detection zone

check zone setting

the load is on without any 
identifiable movement

the sensor is not mounted reliably for detecting 
movement

Securely mount enclosure

Movement occurred, but not identified by the sensor 
(movement behind wall, movement of small object in 
immediate lamp vicinity etc.)

check zone setting

the load does not work despite 
movement

rapid movements are being suppressed to minimize 
malfunctioning or the detection radius is too small

check zone setting

functIonS

3.1 100H burn-in mode for fluorescent lamp

With simple operation, rapidly turn off/on the fixture 3 cycles within 3 sec. (the green lED on the sensor as well as the 
fixture will blink 3 times to indicate the success of setup), lamp will be 100% on for 100 hours, and then automatically goes 
to sensor mode after 100 hours. this is crucial to secure the lifetime of fluorescent lamp, when new fixture is installed, or old 
lamp is replaced. this 100h burn-in feature can be cancelled by turn off/on the fixture 1 cycle within 1sec.

3.2 Set daylight threshold freely

With simple operation, rapidly turn off/on the fixture 2 cycles within 2 sec:
a. the green lED on the sensor will flash slowly for 5 seconds, meanwhile the fixture blink twice.
b. the daylight sensor measures and remembers the surrounding lux for 1 sec.
c. the fixture and green lED will be on for 10s to indicate the success of learning.
this feature enables the fixture to function well in any real application circumstance, where the daylight that penetrate into 
fixture may vary a lot.
the latest surrounding lux value overwrites previous lux value learned.
Both the setting on DIp switch and the learned ambient lux threshold can overwrite each other. the latest action stays in 
validity.

3.3 Condominium function

By connecting l’ terminal with l’ on another sensor, if any of the master fixture (containing sensor) is triggered, all luminaries
(including slaves and other master unit in group) will also light up.

3.4 Zero-cross relay operation

Designed in the software, the sensor switches on/off the load right on the zero-cross point, to ensure the min. current pass-
ing through the relay contact point, and enable the max. load and life-time of the relay.

3.5 Loop-in and loop-out

Double l n terminal makes it easy for wire loop-in and loop-out, saves the cost of terminal block and assembly time.