background image

1. Technical Specifications

Product type                                  Dual sense DALI sensor (HF and PIR, daylight harvest)
Operating voltage                          120~277VAC  50/60Hz
Switched power                            Maximum 20pcs devices, maximum 40mA
Power consumption                       < 1W
Detection angle                             360

o

Detection area (DxH)                      12 x 6m (Maximum)
Mounting height                            6m (Maximum)
Detection range                            10% / 50% / 75% / 100%
Hold time                                      2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time                               0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞ 
Stand-by dimming level                 10% / 20% / 30% / 50%
Daylight threshold                          50 ~ 500Lux, Disable
Warmming up time                        30s
Operating temperature                   -20

o

C ~ +55

o

C

Sensor mode                                 PIR, HF, PIR+HF, PIR / HF 

3. Rotary Switch Settings

A rotary switch is built inside the sensor for 
scene selection / fast programming. Total 
16 channels available:

Note: settings can also be changed by remote control 99 190 27. The last action controls.

Rotary switch preset (Please 
see the location in 2. Installation)

Detection 

range 

Channel

0
1
2
3
4
5
6
7
8
9
A




100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%

5s
1min
5min
5min
5min
5min
10min
10min
10min
10min
20min
20min
30min
30min
30min
5s

10s
5min
10min
+∞
+∞
+∞
30min
+∞
+∞
+∞
1h
+∞
+∞
+∞
+∞
10s

10%
10%
10%
10%
10%
30%
10%
10%
10%
30%
10%
30%
10%
30%
50%
10%

Disable
50Lux
50Lux
75Lux
100Lux
200Lux
50Lux
75Lux
100Lux
200Lux
100Lux
200Lux
100Lux
200Lux
400Lux
100Lux

Hold 

time

Stand-by 

time 

Stand-by 

dimming level 

Daylight 

threshold

Switch the power supply to the sensor two times within 2 seconds, the ambient lux level is sampled and set 
as the new daylight threshold / target lux level. This feature enables the daylight sensor to be commissioned 
to the environment in which it is installed. Both the settings on rotary switch and the ambient lux level 
sampled can overwrite each other. The last adjustment remains in memory. This may also easily be carried 
out using the 99 190 27 remote control handset, please see next page (button      ) for details. 

5.3 Ambient Daylight Threshold

By connecting the “SYNC” terminals in parallel (see wiring diagram), no matter which sensor detects 
motion, all 99 190 23 in the group will turn on the lights when surrounding natural light is below the 
daylight threshold. The sensor module is shared and the detection area could be widely enlarged in 
this way. 

5.4 Synchronization Function

Turn off/on the power supply three times within 3 seconds, the light will be turned on for 8 hours, 
even there is no motion detected, then go back to sensor mode automatically.
Note: this 8H manual on mode can be cancelled by turning off/on the power supply one time within 
        1 second.

5.7 8H Manual ON Mode For LED Lamp

5. Functions

The built-in daylight sensor can measure ambient natural light, and calculate how much electrical light is 
needed to reach the target lux level. The demand is given to the LED driver by DALI signal, so as to deliver 
the needed amount of electric light. The target lux level can be adjusted by remote control or long press on 
the push switch.

5.1 Daylight Harvest (Daylight Regulating)

4

2

0

Light level

Time (hrs)

Normal Electric Light 

Daylight controlled light

Energy Saving Zone

Natural light

Hold time

Stand-by time

With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off the 
lights manually, or adjust the target lux level. This makes the product more user-friendly and offers 
more options to fit for extra-ordinary demands.
* Short push (<1s): on/off function;
  ON 

 OFF: the light turns off immediately and cannot be lighten for a certain time (equals to hold 

                     time preset) even movement is detected. After this period, the sensor goes back to 
                     auto sensor mode.
  OFF 

 ON: the light turns on and goes to auto sensor mode.

* Long push (>1s): adjust the target lux level by turning the light up or down. Both the adjustment by 
                             remote control and push switch can overwrite each other, the last adjustment 
                             remains in memory. 
* If no end-user adjustment is desired, simply leave the “push” terminal disconnected.

5.5 Manual Override (Push Function)

The light dims to minimum level even switches off completelly if ambient daylight is sufficient (natural light 
level exceeds target lux level), no matter it is during hold-time or stand-by time, with or without motion.
Note: if the stand-by time is preset at "+∞", the light never turns off even when natural light is sufficient.

5.2 Lux Off Function

Installation and Instruction Manual

 

TM

10

2. Installation 

Warnings: 

1. Installation must be carried out by a
    qualified engineer in accordance with
    local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may
    cause mis-triggering.
4. Ensure environmental conditions are
    suitable for electronic equipment

29

50.2

55.2

Infrared receiver

HF Sensor module

Photocell

PIR

LED indicator

Sensor mode selection

Rotary switch preset

Direct junction “J” box mounting

32.5

53.7

58.7

C - Surface box

B - Facia Cover

a. Separate control board (A) from facia (B) 
    & Surface box (C).  C is not required.
b. Make electrical connections to control board 
    (A). See detailed wiring diagram on next page.
c. Secure control board (A) to junction box.
d. Set-up sensor modes as per sections 3 & 4 
    of this manual.
e. Clip facial plate (B) to control board (A).

Surface mount assembly

a. Separate control board (A) from facia (B) &
    Surface box (C).
b. Securely mount surface box (C) to a flat and
    solid surface.
c. Make electrical connections to control board 
    (A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of
    this manual.
e. Secure control board (A) to surface box (C).
f. Clip facial plate (B) to control board (A).

A - Control Board

4. Sensor Mode Selection

Sensor mode can be easily selected by choosing the correct combination of the DIP switches 
(see table below): 

HF

PIR

HF+PIR

HF/PIR

1 2

I

II

III

IV

HF+PIR: Light is on when both HF 
and PIR sensors are activated.

HF/PIR: Light is on when HF or PIR
sensors are activated. 

SURFACE MOUNT DUAL SENSE MOTION SENSOR 99 190 23

The motion sensor is employed, but only activated on the manual press of the push switch. With 
presence, the light remains on and can interact with ambient natural light, then dims down in 
absence, eventually switching off automatically after the stand-by time has expired.
Note: end-user can choose either function 5.5 or 5.6 for application. Default function is 5.5.

5.6 Semi-auto Function (Absence Detection)

Varning!

Stäng av strömmen, ta ut säkringen på elcentralen eller ställ automatsäkringen till läge ”AV”, innan 
installationsarbetet påbörjas.
Skall installeras av behörig installatör och i enlighet med gällande föreskrifter.

www.malmbergs.com

2017.03.01

Art.no: 99 190 23