5. REGULATOR FUNCTIONS.

 

 
The regulator is equipped with a number of functions that, together with the possibility of creating 
your own program, enable adjusting the regulator's work to the individual needs of the user. Some 
of  the  functions  listed  below  are  activated  after  the  appropriate  programming  of  the  regulator  
(

see section and section 9.

). 

1.

 

Continuous  temperature  measurement  function

,  regardless  of  whether  the  regulator  is  on  

(it must be connected to the power supply) 

 parameter 

d1

 is set to 1. 

2.

 

The  function  of  controlling  the  refrigeration  system  (chiller)

,  depending  on  the  measured 

temperature 

 parameter 

C9

 is set to the value 0. 

3.

 

Light signaling function for switching on the cooling / heating operation

 

 blue LED is on. 

4.

 

Control function of the heating system

, depending on the measured temperature 

 parameter 

C9

 is set to 1. 

5.

 

The stirrer or ventilator control function

, enabling the implementation of the following variants 

of this control 

 depending on the 

F0

 parameter settings: 

a.

 

automatic operation: 

 

cyclic operation of the stirrer / ventilator, independent of the operating condition of the 
chiller (unit) / heating system, 

 

stirrer operates continuously during the operation of the chiller (unit), when the chiller 
is switched off, the stirrer goes into cyclic operation, 

 

stirrer / ventilator operates only when the chiller / heating system is switched on, 

 

continuous  stirrer  /  ventilator  operation  while  the  regulator's  operation  is  on  (main 
application in dryers), 

 

switched off stirrer / ventilator operation, 

b.

 

operation triggered manually: 

 

switching on continuous stirrer / ventilator operation, regardless of whether the control 
operation of the regulator is switched on; in order to end the stirrer operation, press  
the button 

[3]

 

switching  on  the  stirrer  /  ventilator  operation  for  a  strictly  defined  time,  regardless  
of whether the control work of the regulator is switched on. 

6.

 

Blocking  function  of  the  stirrer  and  the  chiller  (unit)  when  the  flap  of  the  milk  cooler  tank 
opens

 (actuation of the limit switch) 

 parameter 

AF

. In dryers it can be used to turn off the 

ventilator, e.g. when the door is opened. 

7.

 

Defining the operation of the limit switch as negative or positive

 

 parameter 

UU

8.

 

The  chiller  (unit)  operation  supervision  function

,  consisting  in  the  possibility  of  setting  

the maximum and minimum operation time of the chiller (unit), as well as its minimum standstill 
time 

 parameters 

E1

 and 

E2

9.

 

The  function  of  registering  the  maximum  and  minimum  temperature  values  throughout  
the  regulator's  working  cycle

.  This  function  is  connected  with  the  possibility  of  temporally 

Содержание SMT-05

Страница 1: ...sing is hermetic IP 65 protection class and therefore resistant to humidity dirt and low temperature electronics of the regulator is able to work in temperatures up to 10 OC The casing is adapted for...

Страница 2: ...ator programmable parameter from 1 min to 60 min standstill time of the stirrer ventilator programmable parameter from 1 min to 60 min temporary operation time of the stirrer ventilator programmable p...

Страница 3: ...egulator is connected to the mains it means the cooling heating operation of the regulator is switched off However you can switch on the stirrer s manual operation by pressing the button 3 If the regu...

Страница 4: ...stirrer ventilator 3 digital temperature meter allowing for current temperature control independently from switching on or off the regulator 6 LEDs signaling the current operating status of the coolin...

Страница 5: ...outin the following way unscrew the screws of the casing cover take off the cover screw the regulator casing to the prepared structure through the fixing holes put on the cover fasten the screws of th...

Страница 6: ...ion of the chiller unit when the chiller is switched off the stirrer goes into cyclic operation stirrer ventilator operates only when the chiller heating system is switched on continuous stirrer venti...

Страница 7: ...d HE This function is connected with the possibility of delaying the time of switching on the alarm system of the regulator from the moment of its activation 11 Monitoring and signaling function of th...

Страница 8: ...s on the display The next pressing of the S button confirms the willingness to make changes Then press the key to enter the access code and confirm with the S button After correct entry into the setti...

Страница 9: ...tion chamber The regulator can control the cooling temperature in the range of 40 OC up to 120 OC In order to limit the scope of the control so as to prevent the user of the cooling device from settin...

Страница 10: ...he regulator by pressing the 1 button also turns off the stirrer operation 7 2 2 Manually triggered stirrer operation The manual stirrer operation can be initiated by pressing the button marked by sym...

Страница 11: ...not immediately stop the operation of the chiller The chiller restarts operation after the flap opening signal disappears taking into account the programmed minimum standstill time of the chiller 8 2...

Страница 12: ...e function to work properly the appropriate temperature range must first be programmed this is parameter A1 temperature below which the alarm will be activated and parameter A2 temperature above which...

Страница 13: ...temperature range is signaled only visually as shown in the figure above The alarm system audible and visual can also be turned off completely by changing the HA parameter to 1 see section 9 8 4 Temp...

Страница 14: ...minimum standstill time of the chiller unit CF 0 00 inactive 0 00 active setting the time from 1 min to 60 min every 1 min 0 time after which the chiller unit is turned off after the flap of the milk...

Страница 15: ...ling the control sensor CU every 0 2 OC scalable value setting the operation of the limit switch of opening the tank s flap UU 0 closing the limit switch raising the flap 1 opening the limit switch ra...

Отзывы: