CHALLENGER SERIES 80‐120 KVA
INSTALLATION
AG‐SD‐36 Rev. No:0 Rev. Date:15.11.2012 Publish No:1
Shelves will be accessible in touch if batteries are in battery room. Therefore please keep
restricted accessing to battery room. Use necessary safety writings and strips
Espacially, for the external cabinet batteries system of UPS, fuses must definitely be used. These
fuses must be mounted as close as possible to the batteries. This closeness will increase the
electrical operation safety.
THE
TABLE
OF
CHALLENGER
EXTERNAL
BATTERY
USAGE
Device
Power
(KVA)
80
100
120
Total
number
of
Batt.
50
50
50
I
bat.max
@
V
bat.max
(A)
18,6
23,2
27,8
I
bat.max
@
V
cutoff
(A)
136
170
204
Recommended
internal
fuse
(A)
160
200
250
External battery cabinet and battery room applications are given below as an example.
The method of application may vary according to the customer.
Example Battery Chamber Application
CH80120EN08R0