2. INSTALLATION OF YOUR EQUIPMENT

2.1 MOUNTING

Note : When installing the module in the rack, the protection rating must comply with fire safety standards EN 54-4/

A2: IP30.

• 

Position the temperature sensor as close to the battery as possible.

•  The connections and crimping should be given special care.

• 

A battery fuse adds 1 to 2 mΩ.

3. CONNECTION

3.1 CONNECTION DIAGRAM

2.2 BATTERIES

The battery temperature sensor must be placed as close to the battery as possible.

Important : the openings provided in the cabinet must be used. Do not create additional openings as doing 

so may casue the device to malfunction and voids the warranty.

AES24V MS150 rear panel

AES24V MS40 rear panel

AES24V MS40

AES24V MS150

Model

AES24V MS40

AES24V MS150

Battery wiring instruc-

tions

The power supply takes a resistance measurement of the battery mesh every 4 hours.

The trigger threshold of the fault is 50 mΩ±10 %.

The trigger threshold of the fault is 13 mΩ±10 % 

Exceeding this threshold is signalled by a battery fault and means that the power supply with its associated

battery will not have the desired autonomy in the event of a mains outage. 

To avoid initiating this fault, please note the following elements:

•  Use batteries with a capacity of 24 to 110 Ah.

•  Use Yuasa, Powersonic brand batteries. If you would like to 

use another battery brand, please have them approved (see 

chapter 1.3.4).

•  Use battery cables that are as short and large as possible 

(16 mm² max).

 

for a cross-section of 10 mm², the resistance is 2 mΩ/m.

 

for a cross-section of 16 mm², the resistance is 1.25 mΩ/m.

•  Use authorized batteries (see chapter 1.3.4).

•  Use battery cables that are as short and large as possible 

(35 mm² max).

 

for a cross-section of 10 mm², the resistance is 2 mΩ/m.

 

for a cross-section of 16 mm², the resistance is 1.25 mΩ/m.

 

for a cross-section of 25 mm², the resistance is 0.8 mΩ/m.

 

for a cross-section of 35 mm², the resistance is 0.6 mΩ/m.

Example: for battery cables (+ and -) 1.5 m in length and with a cross-section of 10 mm², the resistance is 6mWΩ.

Battery cables (+ and -) of 1.5 m in length and cross-section of 

16 mm² allow correct operation with all the

recommended batteries.

Battery cables (+ and -) of 1.5 m in length and cross-section of 

25 mm² allow correct operation with all the

recommended batteries.

Содержание AES24V MS40

Страница 1: ...l a Fl a mb re 31300 To u l o u s e FR ANCE T l 33 0 5 61 31 86 87 Fax 33 0 5 61 31 87 73 co mmerc i a l ma j o rco m fr w w w majorcom fr User manual AES24V MS40 AES24V MS150 POWER SUPPLY UNITS USER...

Страница 2: ...d EMC directives immunity and emission It is compliant with standards EN60950 1 2006 EN61000 6 1 2007 EN61000 6 2 2006 EN61000 6 3 2007 EN61000 6 4 2007 and EN 55022 class B 2007 It is also compliant...

Страница 3: ...tage Default 1 2 3 Model AES24V MS40 AES24V MS150 Power voltage 195 264VAC 50 60Hz Primary Current 1A 195VAC 2A 195VAC Breaker Circuit D curve need to be provided Upstream Model AES24V MS40 AES24V MS1...

Страница 4: ...e battery mesh every 4 hours The trigger threshold of the fault is 50 m 10 The trigger threshold of the fault is 13 m 10 Exceeding this threshold is signalled by a battery fault and means that the pow...

Страница 5: ...User manual User manual 4 COMMISSIONING Connect the battery wires to the terminal strip but do not connect the battery terminals After the electrical connections are made mains loads and batteries 1...

Страница 6: ...ry test is performed in the following manner every 30 seconds for the first 20 minutes after commissioning every 15 minutes after the first 20 minutes If a fault is detected the test is performed ever...

Страница 7: ...ed clean and ensure that it is installed in a dry and ventilated location We shall in no case be liable for damages associated with improper use or incorrect maintenance of the equipment WARNING Repla...

Страница 8: ...or equal to 11 5 Vdc Repeat the measurement after having disconnected the load and the battery Recheck the signalling of the indicator lights see chapter 5 If all the steps are validated check the co...

Страница 9: ...a Fl a mb re 31300 To u l o u s e FR ANCE T l 33 0 5 61 31 86 87 Fax 33 0 5 61 31 87 73 co mmerc i a l ma j o rco m fr w w w majorcom fr AES24V MS40 AES24V MS150 POWER SUPPLY UNITS User manual MAJORC...

Отзывы: