16

SR/SC Series "A" Woodburning Fireplace

7412948

Hearth Installation

A hearth extension is required to protect a combustible 
floor in front of the fireplace. Refer to Figure 23 for mini-
mum dimensions and mounting detail.

NOTE:  Hearth Extension must not cover the air 
inlet opening of a fireplace.

The hearth extension described in Figure 23 must be a 
durable noncombustible material with a minimum (total) 
Rt value of 1.09; refer to Figure 24 for examples. The 
overall height (above a combustible floor), depth and 
width must be as indicated, with the extension centered 
to the fireplace opening.
The top of insulation must be covered with a noncom-
bustible decorative covering 

or

 a piece of .018” mini-

mum sheet metal, to protect hearth extension material.  
(Fig. 23)
Secure the hearth extension to the floor to prevent 
shifting, using trim molding or other similar means at 
three (3) outer edges. Seal crack between the fireplace 
hearth and hearth extension with a noncombustible 
material.  (Figs. 23 and 25)

Minimum Wall Clearances

WITH

Noncombustible

Surround Facing

WITHOUT

Noncombustible

Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

G

H

G

J

Seal cracks

between the 

fireplace

and hearth

extension with

noncombustible

material

Safety strips 

must overlap 

1/2" minimum

May install 

noncombustible 

decorative 

covering

OR .018" min. 

sheet metal

FIREPLACE 

HEARTH

COMBUSTIBLE 

FLOOR

MINIMUM 

INSULATION 

VALUE "R"

4" MIN.

FP594
SR/SC
11/20/97

FIREBOX

OPENING

A

 - Min. clearance 

to combustible
perpendicular wall

B

 - Min. clearance 

to combustible
perpendicular wall when
using noncombustible wall shield*

SIDE
WALL

SIDE
WALL

F**

C**

E

E

D

4" BRICK
(Example material)

Combustible material permitted within shaded area.  

 * Noncombustible wall shield requires 1" MHSC EH2416 

    insulation (minimum R Value = 1.85) between decorative 
    noncombustible rigid covering and combustible wall.  
    Minimum height and width is 40" x 40".
** Dimension/degree of angle will vary depending on thickness 

    of noncombustible surround facing.

4"

Shaded area starts

1/2" away from 

edge of unit.

FP594

Fig. 23

  Combustible side wall protection and hearth extension dimensions.

   

J

  SR/SC36A

 

16" 

12" 

48° 

41° 

18" 

14" 

7

³⁄₄

16" 

48"

   

406 mm  305 mm 

 

 

457 mm  356 mm  197 mm  406 mm 1219 mm

 

SR/SC42A

 

20" 

12" 

42° 

35° 

18" 

14" 

11

¹⁄₂

20" 

61

¹⁄₂

"

   

508 mm  305 mm 

 

 

457 mm  356 mm  292 mm  508 mm 1562 mm

Side Wall Protection

Adjacent combustible side walls that are within the mini-
mum dimensions shown in Figure 23 of fireplace open-
ing must be protected with MHSC Wall Shield Model 
SP40 or a specifically built wall shield described below.
The special wall shield design described in Figure 20 is 
an alternate method of adding protection to side walls 
and can be used in place of the SP40 with the same 
wall clearances specified for the SP40. Rt must =1.85 
minimum.

Examples of wall shield insulation:

1.  Manville - CERAFORM 126, K=.27, 
  1/2 inches thick

2.  

MHSC

 - EH2416, K = .458, 

  1 inch thick required.

Содержание SR/SC Series "A" SC36A

Страница 1: ...SC36A SR36A SC42A SR42A For use in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 948 SR cover 11 18 97 948 SC cover 11 18 97 7412948 7 08 Rev...

Страница 2: ...anufactured or approved by MHSC in combination or assembly with a Majestic Fire places replace system notwithstanding any independent testing laboratory or other third party approval of such component...

Страница 3: ...ss 8 Dia 203mm 3 4 8 7 6 m m FP590 Fig 2 SC36A Series speci cations and framing SC36A Series Woodburning Fireplace Circulating Model 36 914mm 14 372mm 15 391mm 11 279mm 40 1016mm 39 1006mm 3 76mm 5 8...

Страница 4: ...8 Dia 203mm 3 6 9 1 4 m m FP592 Fig 4 SC42A Series speci cations and framing SC42A Series Woodburning Fireplace Circulating Model 42 1067mm 46 1168mm 39 1006mm 5 8 16mm 5 8 1 6 m m 1 2 13mm 1 2 22 57...

Страница 5: ...Collar Pan Flashing Draftstop Batt Insulation cut out around estop Firestop Ceiling Level Nailing Flange Gas Line Access both sides Electrical Access Outside Air Cover Plate Metal Safety Strips 1 2 o...

Страница 6: ...C42A Maximum 90 0 90 0 Minimum Without Elbows 12 6 12 6 With 2 Elbows 14 6 14 6 With 4 Elbows 21 0 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a struc...

Страница 7: ...to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above the highest point where it passes throu...

Страница 8: ...FIREPLACE IN AN INSULATED ENCLOSURE BE SURE ALL RE QUIRED AIR SPACES ARE MAINTAINED Page 14 Fig 20 Installation Chimney Supports The chimney system is supported by the replace for vertical chimney he...

Страница 9: ...ri cal wire through listed cable clamp leaving approxi mately six 6 inches of wire exposed through the EB1 Secure listed cable clamp to the wire Attach white wire from power source to one 1 wire of re...

Страница 10: ...gh a straight up chimney arrangement is to be used Mea sure your offset dimension from straight up chimney center point on ceiling Ceiling Chimney Hole Possible Obstructions The size of the hole in ce...

Страница 11: ...on top of the replace Install the pipe as pictured in Figure 16 When you get a good lock you will hear the pipe clearly snap together Once sections are snap locked in place it is extremely dif cult t...

Страница 12: ...cer with the ange on the top of the framed hole and the angled portion extending down into the hole Firestop spacers are not available for nor are they re quired on vertical walls DO NOT put any seala...

Страница 13: ...tructions are horizontal dimen sions therefore the hole size must be marked on the roof accordingly Cover the opening of the installed chimney so debris cannot get into the system Cut and frame the ho...

Страница 14: ...nd 12 305 mm from top of grille opening for circulating models Do not install a mantel face plate less than 6 159 mm from top of replace opening for radiant models and 6 159 mm from top of grille open...

Страница 15: ...8mm 12 305mm Min 1 38mm 6 159mm Min 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Mantel Clearance Radiant Model No Noncombustible Facing Material Combustible Mantel and Trim Finished Wall Header Stand...

Страница 16: ...al FIREPLACE HEARTH COMBUSTIBLE FLOOR MINIMUM INSULATION VALUE R 4 MIN FP594 SR SC 11 20 97 FIREBOX OPENING A Min clearance to combustible perpendicular wall B Min clearance to combustible perpendicul...

Страница 17: ...al resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R value may be used provided thickness of material is suf ciently greater to maintain an equivalent to...

Страница 18: ...ce the nishing material used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in replace should be rated less than 100 000 BTU Hr Gas pipe installation is intend...

Страница 19: ...er replace 20005487 20005631 5 Screen Pulls 5584139 5584139 6a Firebrick Hearth 20005621 20005421 6b Firebrick Rear 20005627 20005462 6c Firebrick Right Side 20005626 20005461 6d Firebrick Left Side 2...

Страница 20: ...insurance Glass Door Standard Bi Fold door set Brushed Brass nish 36GDKBBSR SR SC36A 42GDKBBSR SR SC42A Black nish 36GDKBKSR SR SC36A 42GDKBKSR SR SC42A Polished Brass nish 36GDKDPSR SR SC36A 42GDKDPS...

Страница 21: ...ate chimney through CT100 a chase top Appropriate adapter required Flashing not included Adapter Kit Unites Square Chase Termination with chimney CTSK pipe required Chase Top Housing Low pro le pyrami...

Страница 22: ...ation Shield Used to prevent insulation from coming in AIS SK contact with the chimney system SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN 1 Long roof SK84CAN 4 Long 45 Ch...

Страница 23: ...re dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this replace to be in compliance with your local bui...

Страница 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: