SR/SC Series "A" 

Woodburning Fireplace

For Models:

 SC36A, SR36A

 SC42A, SR42A

For use in U.S./Canada
Underwriter's Laboratories Report No. MH6018

DO NOT DISCARD THIS MANUAL: Retain for future use.

948

SR cover

11/18/97

948

SC cover

11/18/97

7412948  7/08  Rev. 19

Homeowner's Installation 

and Operating Manual

Содержание SR/SC Series "A" SC36A

Страница 1: ...SC36A SR36A SC42A SR42A For use in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 948 SR cover 11 18 97 948 SC cover 11 18 97 7412948 7 08 Rev...

Страница 2: ...anufactured or approved by MHSC in combination or assembly with a Majestic Fire places replace system notwithstanding any independent testing laboratory or other third party approval of such component...

Страница 3: ...ss 8 Dia 203mm 3 4 8 7 6 m m FP590 Fig 2 SC36A Series speci cations and framing SC36A Series Woodburning Fireplace Circulating Model 36 914mm 14 372mm 15 391mm 11 279mm 40 1016mm 39 1006mm 3 76mm 5 8...

Страница 4: ...8 Dia 203mm 3 6 9 1 4 m m FP592 Fig 4 SC42A Series speci cations and framing SC42A Series Woodburning Fireplace Circulating Model 42 1067mm 46 1168mm 39 1006mm 5 8 16mm 5 8 1 6 m m 1 2 13mm 1 2 22 57...

Страница 5: ...Collar Pan Flashing Draftstop Batt Insulation cut out around estop Firestop Ceiling Level Nailing Flange Gas Line Access both sides Electrical Access Outside Air Cover Plate Metal Safety Strips 1 2 o...

Страница 6: ...C42A Maximum 90 0 90 0 Minimum Without Elbows 12 6 12 6 With 2 Elbows 14 6 14 6 With 4 Elbows 21 0 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a struc...

Страница 7: ...to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above the highest point where it passes throu...

Страница 8: ...FIREPLACE IN AN INSULATED ENCLOSURE BE SURE ALL RE QUIRED AIR SPACES ARE MAINTAINED Page 14 Fig 20 Installation Chimney Supports The chimney system is supported by the replace for vertical chimney he...

Страница 9: ...ri cal wire through listed cable clamp leaving approxi mately six 6 inches of wire exposed through the EB1 Secure listed cable clamp to the wire Attach white wire from power source to one 1 wire of re...

Страница 10: ...gh a straight up chimney arrangement is to be used Mea sure your offset dimension from straight up chimney center point on ceiling Ceiling Chimney Hole Possible Obstructions The size of the hole in ce...

Страница 11: ...on top of the replace Install the pipe as pictured in Figure 16 When you get a good lock you will hear the pipe clearly snap together Once sections are snap locked in place it is extremely dif cult t...

Страница 12: ...cer with the ange on the top of the framed hole and the angled portion extending down into the hole Firestop spacers are not available for nor are they re quired on vertical walls DO NOT put any seala...

Страница 13: ...tructions are horizontal dimen sions therefore the hole size must be marked on the roof accordingly Cover the opening of the installed chimney so debris cannot get into the system Cut and frame the ho...

Страница 14: ...nd 12 305 mm from top of grille opening for circulating models Do not install a mantel face plate less than 6 159 mm from top of replace opening for radiant models and 6 159 mm from top of grille open...

Страница 15: ...8mm 12 305mm Min 1 38mm 6 159mm Min 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Mantel Clearance Radiant Model No Noncombustible Facing Material Combustible Mantel and Trim Finished Wall Header Stand...

Страница 16: ...al FIREPLACE HEARTH COMBUSTIBLE FLOOR MINIMUM INSULATION VALUE R 4 MIN FP594 SR SC 11 20 97 FIREBOX OPENING A Min clearance to combustible perpendicular wall B Min clearance to combustible perpendicul...

Страница 17: ...al resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R value may be used provided thickness of material is suf ciently greater to maintain an equivalent to...

Страница 18: ...ce the nishing material used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in replace should be rated less than 100 000 BTU Hr Gas pipe installation is intend...

Страница 19: ...er replace 20005487 20005631 5 Screen Pulls 5584139 5584139 6a Firebrick Hearth 20005621 20005421 6b Firebrick Rear 20005627 20005462 6c Firebrick Right Side 20005626 20005461 6d Firebrick Left Side 2...

Страница 20: ...insurance Glass Door Standard Bi Fold door set Brushed Brass nish 36GDKBBSR SR SC36A 42GDKBBSR SR SC42A Black nish 36GDKBKSR SR SC36A 42GDKBKSR SR SC42A Polished Brass nish 36GDKDPSR SR SC36A 42GDKDPS...

Страница 21: ...ate chimney through CT100 a chase top Appropriate adapter required Flashing not included Adapter Kit Unites Square Chase Termination with chimney CTSK pipe required Chase Top Housing Low pro le pyrami...

Страница 22: ...ation Shield Used to prevent insulation from coming in AIS SK contact with the chimney system SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN 1 Long roof SK84CAN 4 Long 45 Ch...

Страница 23: ...re dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this replace to be in compliance with your local bui...

Страница 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...