SHR Series Woodburning Fireplace

20001384

Installation

Chimney Supports

The chimney system is supported by the fireplace for 
vertical chimney heights less than 30 feet above the 
hearth.  Chimney supports are required if the vertical 
height exceeds 30 feet with 11CF chimneys.  Locate 
chimney supports at ceiling holes or other structural 
framing at 30 foot heights.  Spacing between chimney 
supports 

must not

 exceed 30 feet.  Use Chimney 

Support Model 11CS.  

(NOTE:  The 11CS can not be 

mounted directly to the fireplace.) 

 Support provided 

by elbow straps fulfills the support requirement only if 
they are spaced as previously described. (A chimney 
support is 2

¹⁄₂

" long when installed.)

Angled chimney runs require a support every six (6) 
feet in addition to the elbow straps. Chimney supports 
are used for this function. (Fig. 9) 

Chase Installation

A chase is a vertical boxlike structure which encloses 
the fireplace and/or chimney.  Chases are typically built 
on the outside of the house with fireplace opening cut 
into the outer wall of a room.  (Page 5, Fig. 5)
If you need help in determining fireplace location or how 
the chimney system should be run, contact your Majes-
tic Fireplaces dealer for assistance.

 Insulating Fireplace 

Enclosure for Cold Climates

If you live in a cold climate, it is not required but 

highly recommended

 that you insulate the fireplace 

enclosure to eliminate cold air penetration as much 
as possible.
Insulate base of fireplace with a noncombustible 
insulation rated for a minimum of 300° F.  Insulating 
is 

very important

 for outside wall installations over 

a concrete slab. If fireplace is installed on a platform, 
insulation should be placed on top of the platform 

before 

fireplace is set. (Fig. 10)

When a fireplace is installed in a chase or on an 
outside wall, enclosure should be treated like any 
outside wall in a home. Insulation should be installed 
on the inside wall as well as the outside wall(s). In 
a chase, it is also a good idea to install a firestop at 
the first ceiling level above the fireplace and enclose 
the chase with sheeting material. Insulation may 
then be installed above sheeting material to assure 
the space around the fireplace is totally protected. 
(Fig. 5) 

CAUTION:  WHEN INSTALLING A FIREPLACE IN 
AN INSULATED ENCLOSURE, BE SURE ALL RE-
QUIRED AIR SPACES ARE MAINTAINED.

 (Page 

15, Fig. 19)

IWF284

MBUF

5/25/96

FP284

Fig. 9

  Chimney support installation

Chimney Support 

Strap

11CS

Содержание SHR36

Страница 1: ...HR Series Woodburning Fireplace For Models SHR36 SHR42A SHR48 SHR52 Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 20001384 12 06 Rev 18 Homeowner s Insta...

Страница 2: ...d ing any independent testing laboratory or other third party approval of such component parts or accessory Any such action may possibly cause a re hazard Consult local building codes to ensure that y...

Страница 3: ...Gas Line Access Gas Line Access 1365mm FP546A Fig 2 SHR42A Series speci cations and framing SHR42A Series Woodburning Fireplace 36 914mm 46 1175mm 44 1118mm 610mm 189mm 13 Dia 340mm Rough Opening Widt...

Страница 4: ...Access Gas Line Access 1518mm SHR48 Series Woodburning Fireplace Fig 3 SHR48 Series speci cations and framing FP545A 9 235mm 52 1321mm 62 1584mm 52 1334mm 838mm 189mm 13 Dia Rough Opening Width 63 Rou...

Страница 5: ...att Insulation cut out around restop Firestop Ceiling Level Draftstop Ledge Bracket Surround Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 Outside Air C...

Страница 6: ...h to the chimney exit SHR36 SHR42A SHR48 SHR52 Max 90 90 90 90 Min 0 Elbows 14 6 14 6 16 0 16 0 2 Elbows 15 6 15 6 19 0 19 0 4 Elbows 21 0 21 0 24 0 24 0 B Do not use more than 4 elbows per chim ney A...

Страница 7: ...2 A chimney cannot be offset more than 30 degrees from a vertical plane 3 A chimney may run straight up or it may be neces sary to offset it to avoid obstructions 4 The maximum length of an angled run...

Страница 8: ...how the chimney system should be run contact your Majes tic Fireplaces dealer for assistance Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate it is not required but high...

Страница 9: ...corner be hind the end of the left rebrick Push both panels back as far as possible into the left side and corner 4 Swing the right side of the back rebrick into place Attach the left brick in place u...

Страница 10: ...hed by using CFM Corporation elbows Use the 30 Offset Elbow table on Page 6 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support st...

Страница 11: ...fety strips are not required over noncombusti ble oors where all supports at the base of the replace are noncombustible Four 4 nailing anges are supplied with the replace found on the replace hearth T...

Страница 12: ...Spacer in the Ceiling Hole A restop spacer is used to keep pipe spaced properly and required for safety Nail the restop spacer at each corner to the framing members of the ceiling hole Note A restop...

Страница 13: ...m Drive a nail up through roof at the center point This will determine center point on outside of the roof Cut and Frame Roof Hole Size of roof hole varies with the type of chimney termi nation instal...

Страница 14: ...Finish the wall with material of your choice Do not install a combustible mantel shelf less than 12 305 mm from the top of the replace opening Do not install a mantel face plate less than 6 159 mm fr...

Страница 15: ...min 1 12 305mm Max 12 305mm min 1 6 159mm Min 1 FP531 Fig 23 Mantel clearance Header Must be sealed with non combustible material Surround Face Finished Wall Ledge Bracket Finished Wall Ledge Bracket...

Страница 16: ...g front 12 20 01 djt CAUTION Do Not Place Finishing Ma terial Beyond These Edges or Cover Air Inlets Screen Rail Hearth FP1168 Fig 27 Finishing front of replace MA81 rev 8 5 97 rev 4 18 01 1 Ref Combu...

Страница 17: ...alue of the al ternate material employed is greater than or equal to R 1 09 Thermal resistance R or thermal conductivity K may be obtained from manufacturer of the material Factors are related by the...

Страница 18: ...will vary depending on thickness of noncombustible surround facing 4 Shaded area starts 1 2 away from edge of unit A B C D E F G H J SHR36 20 12 35 42 18 14 8 16 52 508 mm 305 mm 457 mm 356 mm 203 mm...

Страница 19: ...Corporation replaces Be sure to have the appliance installed in accordance with building codes Gas connection may enter from either left or right side of the replace Locate appropriate gas line in the...

Страница 20: ...20006021 20001431 20005569 4 Screen Rod two per replace 7554181 7554199 20001428 20005790 5 Screen two per replace 7554295 20001723 20001723 20005278 6 Screen Pull two per replace 5584139 5584139 5584...

Страница 21: ...ccessories for this appliance are available from your local Majestic Fireplaces distributor Should you need additional information beyond what your distributor can furnish contact CFM Corporation 2695...

Страница 22: ...CFM Corporation Type 11CF Chimney Systems Used to terminate chimney at top of chase Adapter kit included Flashing not included Used to build 11CF chimney systems Used to develop 30 offset chimney sys...

Страница 23: ...is extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the installation instructions f...

Страница 24: ...CFM Corporation 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: