background image

SB5400/SB5400HB M

odels

I

nstallatIon

, o

peratIon

 

and

 M

aIntenance

 M

anual

F

or

 r

esIdentIal

 I

nstallatIon

53D9026. Rev 2 9/08

t

hIs

 

FIreplace

 

Is

 u.l. 

lIsted

 

For

 

use

 

wIth

  

the

 

“l” s

erIes

 

chIMney

 

systeM

 

coMponents

.

ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM 

HEATER, ANSI/IAS/AGA Z21.11.2, ARE TO BE INSTALLED IN THIS FIREPLACE.

WHEN AN APPROVED ANSI/ISA/AGA Z21.11.2 UNVENTED ROOM HEATER IS INSTALLED IN THIS FIREPLACE, AN H2853 

CANOPY MUST ALSO BE INSTALLED.

WARNING: DO NOT OPERATE AN UNVENTED GAS LOG SET IN THIS FIREPLACE WITH THE CHIMNEY REMOVED.

Содержание SB5400

Страница 1: ...ponents ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATER ANSI IAS AGA Z21 11 2 ARE TO BE INSTALLED IN THIS FIREPLACE WHEN AN APPROVED ANSI ISA AGA...

Страница 2: ...hat failure to install operate and maintain this or any other factory built fireplace properly can result in a house fire or other occurrences that could cause deaths injuries and property damages It...

Страница 3: ...mended for use in such areas Intended Product Usage The fireplace is designed to sit directly on a combustible floor The fireplace must be installed with clearances to combustible building materials s...

Страница 4: ...to close the damper When the fireplace is not in use the damper should be closed to prevent cold air form entering the chimney as well as preventing warm air in the room from escaping up the chimney N...

Страница 5: ...GHT 2 30 ELBOWS 21 FT MN HEIGHT 4 30 ELBOWS 86FT MAX HEIGHT CHIMNEY SUPPORT EVERY 25 FT FIRESTOP MODEL LF FS 2 REQUIRES 17x17 FRAMING 54 STORM COLLAR MODEL LC CHIMNEY CAP ROOF FLASHING MODEL 612 CAUTI...

Страница 6: ...L 4 8 L 1 8 L 3 6 39 5 16 76 11 16 L SERIES CHIMNEY SECTIONS 47 5 8 47 L48 35 5 8 35 17 5 8 17 11 5 8 11 L18 L36 L12 L18 L18 34 5 8 34 LINEAR GAIN L18 L36 52 LINEAR GAIN 52 5 8 L36 L36 70 5 8 70 LINEA...

Страница 7: ...replace required spacing to combustible walls and some suggested fireplace locations When selecting a location choose one that is away from frequently opened doors central heat outlets or returns or o...

Страница 8: ...trees or above the roof of a single story wing of a two story building as shown by Figure 8 All these conditions can cause turbulence or pressure conditions that can cause poor chimney draft and smok...

Страница 9: ...IMNEY CAP FIRESTOP SPACER LF FS 2 2 AIR SPACE CLEARANCE TO COMBUSTIBLES 17 SQUARE OPENING IN JOIST 17 SQUARE OPENING IN JOIST 612 OR 1212 FLUE OUTLET HEIGHT 2 CLEARANCE TO COMBUSTIBLES MIN 3 FT MIN HE...

Страница 10: ...as enough compressive strength to support the weight of the covering materials and persons standing on it and insulating qualities equal to or better than the 1 2 covering provided by the H2068 20 MIN...

Страница 11: ...by 1 2 50 K 43 R The material thickness divided by K Example R 1 2 50 divided by 43 R 1 16 With either type hearth extension minor shifting of the supporting floor or expansion and contraction may ev...

Страница 12: ...11 53D9026 Fireplace Components Figure 13...

Страница 13: ...he fireplace and chimney Chimney Installation In order to assure safe and satisfactory performance of the fireplace it is very important to properly install the chimney This is an important part of th...

Страница 14: ...ess down until the snap locks engage Continue the process adding the chimney sections on top of each other until the chimney is at least six inches above the roof opening on all sided As the chimney s...

Страница 15: ...12 1 12 2 12 3 12 4 12 5 12 6 12 7 12 8 12 9 12 10 12 11 12 12 12 INSTALLATION OF FIRESTOP SPACER AT FLOOR LEVELS INSTALLATION OF FIRESTOP SPACER AT ATTIC LEVEL FLUE PIPE FLUE PIPE FIRESTOP SPACER FL...

Страница 16: ...minimum air space clearance to the chimney at the extremities of the offset It is recommended that enclosing material not follow the inclined portions of the chimney Offset Installation Sequence 1 Det...

Страница 17: ...CONTINUE CHIMNEY THROUGH ROOF AND INSTALL ROUND CHIMNEY CAP OR CHIMNEY HOUSING FIRESTOP SPACER DIAGONAL CHIMNEY ENCLOSURE RISE FIRESTOP SPACER 2 AIR SPACE CLEARANCE TO COMBUSTIBLES SUPPORT STRAPS DIA...

Страница 18: ...the last section of inlet air duct in place and slide the flashing over the chimney Adjust the chimney to assure that the proper minimum clearances are maintained 5 Nail the flashing securely in place...

Страница 19: ...ONS 4 0 0 1 0 1 1 0 1 1 0 2 1 0 2 1 0 2 1 3 2 1 3 2 1 3 2 4 3 2 4 3 2 4 3 5 4 3 5 4 3 5 4 6 5 4 6 5 4 6 5 7 6 5 7 6 5 7 6 8 3 1 0 0 1 0 0 2 0 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3...

Страница 20: ...ey caps should be at least 24 inches apart to help prevent smoke from a fireplace in use from being drawn down the chimney of a fireplace that is not in use Additional spacing between caps or staggeri...

Страница 21: ...D GASKET STEP 1 SECURE OUTSIDE AIR STARTING COLLAR TO LEFT SIDE OF FIREPLACE WITH FOUR SHEET METAL SCREWS PROVIDED NOTE THE STARTING COLLAR EXTENDS THROUGH THE OUTER FIREPLACE JACKET AND WILL SEAL AGA...

Страница 22: ...ustion assemblies 2 The combustion air assembly should be located at an exterior location which is not likely to be accidentally blocked in any manner The assembly should be located above the snow lin...

Страница 23: ...ce of the wall to which the AK 4 inlet air vent will be attached The duct may be cut with a standard pocket knife use FP 4 U duct for maximum efficiency and safety Do not use a combustible duct Always...

Страница 24: ...NSI IAS AGA Z21 11 2 unvented room heater is installed in this fireplace a H2853 CANOPY must also be installed Warning Do not operate an unvented gas log set in this fireplace with the chimney removed...

Страница 25: ...sure it is fastened snugly to the face of the fireplace A crack between the material and the face of the fireplace could pose a fire hazard and impair the proper operation of the fireplace Blocking th...

Страница 26: ...Glass Door Installation This fireplace has been tested and listed for use with optional Model WSB54 glass doors For installation of the Model WSB54 glass doors see the instructions provided with the d...

Страница 27: ...ve but a little combined with other wood goes a long way Start your fire with a mixture of softwood and hardwood then add some fruit or nut wood for nostalgic aroma Since most woods will not burn well...

Страница 28: ...quipped with glass doors close them DO NOT LEAVE CHILDREN OR PHYSICALLY OR MENTALLY HANDICAPPED OR SENILE PERSONS ALONE WITH A BURNING FIREPLACE You ll need a minimum of three logs preferably four to...

Страница 29: ...mine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney fire The chimney cap can be removed for inspection maintenance and cleaning by...

Страница 30: ...he installation of the fireplace 4 Do insulate the exterior walls surrounding the fireplace to prevent excessive heat loss from the fireplace 5 Do trim the face of the fireplace only with noncombustib...

Страница 31: ...thing or other articles near the fireplace 15 Don t store or place flammable liquids gases or pressurized containers near the fireplace 16 Don t neglect to instruct all responsible persons in the prop...

Страница 32: ...through your local dealer To ensure prompt and accurate service please provide the following information when placing a repair part order Model number of your Appliance Part Name Part Number and Quant...

Страница 33: ...through your local dealer To ensure prompt and accurate service please provide the following information when placing a repair part order Model number of your Appliance Part Name Part Number and Quant...

Страница 34: ...ace before you purchase it Blowers or fans which are warranted separately Heat loss due to the passage of heat or air through or around the fireplace Also under our five year coverage we do not pay th...

Страница 35: ...53D9026 ATTENTION APPLIANCE INSTALLER PLEASE RETURN THESE OPERATING AND INSTALLATION INSTRUCTIONS TO THE APPLIANCE FOR CONSUMER USE...

Страница 36: ...SEPTEMBER 2008 53D9026 Rev 2 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: