21
Majestic • QUARTZ32, QUARTZ36, QUARTZ42 Installation Manual • 2412-980 Rev. Q • 3/19
Two Elbows
Top Vent - Horizontal Termination - (continued)
Figure 4.11
Note
: Use SLP Series
components only.
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
Fire Risk.
• When using SLP-HRC-SS termination cap
on top vented fireplaces, a one foot minimum
vertical vent section is required before installing
first elbow.
WARNING *
V Minimum
*
H
1
+ H
2
Maximum
**
90 Elbow
1/2 ft.
152 mm
1/2 ft.
152 mm
1 ft.
305 mm
1-1/2 ft.
457 mm
2 ft.
610 mm
2-1/2 ft.
762 mm
4 ft.
1.2 m
3-1/2 ft.
1.1 m
6 ft.
1.8 m
4-1/2 ft.
1.4 m
14 ft.
4.3 m
H + H
1
MAX. =14 ft. (4.3 m)
V + H + H
1
MAX. = 40 ft. (12.2 m)
*
See warning below
**
Note
: When using
SLP-FLEX (6-5/8 in.)
venting, there
MUST
be a 25% reduction in total H when using flex vent.