7

Majestic  •  QUARTZ32IFTN/L, QUARTZ36IFTN/L, QUARTZ42IFTN/L Installation Manual  •  2641-980 Rev. C  •  9/20

Getting Started 

A.  Design and Installation Considerations

WARNING! Risk of Fire or Explosion! 

Read all instruc

-

tions before starting the installation. 

Majestic direct vent gas appliances are designed to oper

-

ate with all combustion air siphoned from outside of the 

building and all exhaust gases expelled to the outside. No 

additional outside air source is required.
Installation MUST comply with local, regional, state and 

national codes and regulations. Consult insurance carrier, 

local building inspector, fire officials or authorities having 

jurisdiction  over  restrictions,  installation  inspection  and 

permits.
Before installing, determine the following:
•  Where the appliance is to be installed.
•  The vent system configuration to be used.
•  Gas supply piping requirements.
•  Provisions for optional heat management system.
•  Electrical wiring requirements.
•  Framing and finishing details. 
•  Whether optional accessories—devices such as a fan, 

wall switch, or remote control—are desired.

C.  Tools and Supplies Needed

Before beginning the installation be sure that the following 

tools and building supplies are available.
Hand Tools

 

Tape measure

Level 

Framing material

Manometer 

Framing square

Voltmeter 

Electric drill and bits (1/4 in.)

Plumb line 

Safety glasses/Gloves 

Wrenches 

Reciprocating saw 

1/4 in. nut driver
Non-corrosive leak check solution
1/2 - 3/4 in. length, #6 or #8 Self-drilling screws
Caulking material (300 ºF minimum continuous exposure 

rating)

Improper  installation,  adjustment,  alteration,  service  or 

maintenance  can  cause  injury  or  property  damage.  For 

assistance  or  additional  information,  consult  a  qualified 

service technician, service agency or your dealer.

Figure 2.1   Good Faith Wall Surface Temperatures Above Appliance

B.  Good Faith Wall Surface

NOTICE: 

Surface temperatures listed above are taken with 

a temperature measuring probe as prescribed by the test 

standard  used  for  appliance  certification.  Temperatures 

on walls or mantels taken with an infrared thermometer 

may yield increased temperatures of up to 30 

°

F (17 

°

C) or 

more depending on the thermometer settings and mate

rial 

characteristics being measured.  Use appropriate finishing 

materials that are able to withstand these conditions.  For 

additional finishing guidelines, see Section 10. 

Installation and service of this appliance should be performed by 

qualified personnel. Hearth & Home Technologies recommends 

HHT Factory Trained or NFI certified professionals.

MEASUREMENTS FROM

TOP EDGE OF THE OPENING

6 in.

18 in.

24 in.

30 in.

TO CEILING

12 in.

127°F

123°F

132°F

135°F

147°F

APPLIANCE FRONT

FIREPLACE 

OPENING

Содержание QUARTZ Series

Страница 1: ...installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Models QUARTZ32IFTN QUA...

Страница 2: ...tion Location and Vent Information A Approved Pipe 14 B Vent Termination Minimum Clearances 14 C Vent Terminal Clearances 16 D Use of Elbows 17 E Use of Flex Vent SLP FLEX Series 6 5 8 Inch 18 F Vent...

Страница 3: ...tion 9 Pg 53 55 Proper appliance for fuel type ___________________________ Was a conversion performed ___________________________ Leak check performed and inlet pressure veri ed ______________________...

Страница 4: ...tions at elevations above 4500 feet 1370 m Check with your local gas utility to determine proper orifice size B Glass Specifications Hearth Home Technologies appliances manufactured with tempered glas...

Страница 5: ...r not or plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the ab...

Страница 6: ...ally vented gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The sta...

Страница 7: ...l Framing material Manometer Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Gloves Wrenches Reciprocating saw 1 4 in nut driver Non corrosive leak check solution 1 2...

Страница 8: ...er Carefully remove the appliance and components from the packaging The vent system components and decorative barrier fronts may be shipped in separate packages If packaged separately the log set and...

Страница 9: ...s A 36 914 41 1041 48 1219 B 31 1 8 791 36 1 8 918 43 1092 C 27 3 16 691 32 1 16 814 39 1 16 992 D 18 1 16 459 21 1 2 546 23 9 16 599 E 34 1 16 865 37 5 8 956 39 9 16 1005 F 3 9 16 90 3 9 16 90 3 9 16...

Страница 10: ...ith the hot viewing glass DO NOT operate the fireplace with the barrier removed If decorative barrier front is not present contact dealer STANDARD DECORATIVE BARRIER FRONT A B F G E D C Barrier Mesh I...

Страница 11: ...ign preference Figure 3 3 Appliance Locations Models A B C D E Min F G H I J K L M QUARTZ32IFT in 42 37 59 1 2 See Section 10 for Mantel Projections 1 2 44 62 1 4 16 1 4 48 1 2 68 3 4 15 1 16 7 1 2 1...

Страница 12: ...ht DVP Pipe SLP Pipe Rough Opening Width Clearance to Ceiling Combustible Floor Minimum Hearth Required Behind Appliance Sides of Appliance Front of Appliance Rough Opening Width Rough Opening Width R...

Страница 13: ...eld and ceiling firestops should be sealed with caulk with a minimum of 300 F continuous exposure rating to seal gaps Gas line holes and other openings should be sealed with caulk with a minimum of 30...

Страница 14: ...es DVP or SLP venting systems Refer to Sec tion 12 A for vent component information and dimensions Only use listed decorative termination caps shrouds with Hearth Home Technologies approved venting sy...

Страница 15: ...sider proximity to doors traffic areas or where people may pass or gather sidewalk deck patio etc Listed cap shields available Contact your dealer Local codes or regulations may require different clea...

Страница 16: ...14 mm H clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance termination mechanical or non mechanical 9 in min 229 mm min 12 in min 305 mm min I...

Страница 17: ...E E F F E C T I V E L E N G T H Y X X X DVP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP...

Страница 18: ...pports A support is required at each change in venting direction and in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Figure 4...

Страница 19: ...must be installed When penetrating a combustible ceiling a ceiling firestop must be installed Horizontal runs of vent do not require vertical rise horizontal runs may be level Horizontal termination c...

Страница 20: ...fireplaces a one foot minimum vertical vent section is required before installing first elbow WARNING V1 Minimum H1 Maximum 90 Elbow 18 in 457 mm 1 2 ft 152 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm...

Страница 21: ...d fireplaces a one foot minimum vertical vent section is required before installing first elbow WARNING Figure 4 13 V Minimum H1 H2 Maximum 90 Elbow 1 2 ft 152 mm 1 2 ft 152 mm 1 ft 305 mm 1 1 2 ft 45...

Страница 22: ...vent section is required before installing first elbow WARNING V1 Minimum H1 H2 Maximum V2 V1 V2 Min 90 Elbow 2 ft 610 mm 1 2 ft 152 mm 6 ft 1 8 m 1 1 2 ft 457 mm 10 ft 3 0 m 2 1 2 ft 762 mm 12 ft 3...

Страница 23: ...after exhaust restrictor installation Exhaust restrictor Instructions Exhaust restrictors are recommended for these verti cally terminated products which have excessive draft Exhaust restrictors will...

Страница 24: ...MAX V2 V1 V2 MIN 90 Elbow 1 1 2 ft 457 mm 1 2 ft 152 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 15 ft 4 6 m H MAX 15 ft 4 6 m V1 V2...

Страница 25: ...V1 MIN H MAX V2 V1 V2 MIN 90 Elbow 1 2 ft 152 mm 1 2 ft 152 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H MAX 14 ft 4 3 m...

Страница 26: ...mponents only Figure 4 19 Top Vent Vertical Termination continued V1 H1 V2 V3 H2 V1 Min H1 Max V2 Min H2 Max V3 Min 1 1 2 ft 457 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 0 m V1 V2 V3 H1 H2 Maxim...

Страница 27: ...20 Note Use DVP Series components only Figure 4 21 H1 H1 9 in 229 mm Maximum Rear Vent Horizontal Termination One 45 Elbow For corner installation of models QUARTZ32IFT and QUARTZ36IFT ONLY Note Do no...

Страница 28: ...ft 305 mm 2 1 2 ft 762 mm 3 ft 914 mm 1 ft 305 mm 3 ft 914 mm 6 ft 1 8 m 5 ft 1 5 m 3 ft 914 mm 5 ft 1 5 m 10 ft 3 0 m 7 ft 2 1 m 5 ft 1 5 m 7 ft 2 1 m 14 ft 4 3 m H1 MAX 7 ft 2 1 m H1 H2 MAX 14 ft 4...

Страница 29: ...ents only V1 MIN H1 MAX 1 ft 305 mm 3 1 2 ft 1 1 m 2 ft 610 mm 5 1 2 ft 1 7 m 3 ft 914 mm 7 1 2 ft 2 3 m H MAX 7 1 2 ft 2 3 m V1 H1 MAX 40 ft 12 2 m INSTALLED HORIZONTALLY H1 H2 V2 H1 H2 MAX V1 MIN 1...

Страница 30: ...H1 Note Use DVP Series components only H1 Maximum V1 Minimum H2 Maximum H1 H2 Maximum 1 1 2 ft 457 mm Back to Back Elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 1 2 ft 1 1 m 1 ft 305 mm 3 ft 914 mm 6 1 2 ft 2...

Страница 31: ...as appliance Have the chimney and adjacent structure inspected and cleaned by qualified professionals Hearth Home Technologies recommends that NFI or CSIA certified professionals or technicians under...

Страница 32: ...t pipe to the inlet collar on top of the DV 46DVA GCL adapter with three self tapping screws To minimize cold air drafts seal around the flex vents at the damper inside the chimney with non combustibl...

Страница 33: ...in 25 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm DVP heat shield designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in the ex...

Страница 34: ...estop must be placed on each side of an interior wall A minimum 1 1 2 in 38 mm overlap of attached heat shields must be main tained DVP pipe A wall shield firestop is required on one side only on inte...

Страница 35: ...T pack insu lation around the vent Maintain clearances to vent to prevent overheating A ceiling firestop MUST be used between floors and attics DVP pipe only Frame an opening 10 in by 10 in 254 mm by...

Страница 36: ...l vertical requirement V1 Refer to the SLP FLEX7 Se ries installation instructions for the minimum initial vertical requirements The following provisions must be followed 1 The elbow heat shield is no...

Страница 37: ...the preceding component in the vent system 90 elbows may be installed and rotated to any point around the preceding component s vertical axis If an elbow does not end up in a locked position with the...

Страница 38: ...section of vent pipe make sure to use the fiberglass gasket to seal between the first vent component and the outer fireplace wrap Use 2 self tapping screws to secure the gasket to the outer wrap 2 SCR...

Страница 39: ...the insulation gasket Figure 6 13 Generic Fireplace Shown Cut the metal retaining band and fold the sides out Figure 6 14 Generic Fireplace Shown Fold the center parts of the retaining band out and us...

Страница 40: ...astic Framing and other combustible materials WARNING DO NOT remove standoffs or notch the framing around the appliance standoffs Failure to maintain air space clearance could cause overheating and fi...

Страница 41: ...holes DO NOT penetrate inner pipe All outer pipe joints must be sealed using one of the meth ods below including the slip section that connects directly to the horizontal termination cap Apply a bead...

Страница 42: ...e Silicone Sealant NOTICE When installing a vent system with an HRC termination cap all pipe system joints shall be sealed using a high temperature silicone sealant 300 F minimum continuous exposure r...

Страница 43: ...joining sections See Figure 7 1 OR Apply a bead of silicone sealant 300 F minimum con tinuous exposure rating to the outside of connecting joint after joining sections OR Apply aluminum foil tape 300...

Страница 44: ...ead of silicone sealant 300 F minimum continuous exposure rating inside the female outer pipe joint prior to joining sections Only outer pipes are sealed sealing the inner flue is not required All uni...

Страница 45: ...0 Rev C 9 20 D Disassemble Vent Sections Rotate either section see Figure 7 10 so the seams on both pipe sections are aligned as shown in Figure 7 11 Pull carefully to separate the pieces of pipe Figu...

Страница 46: ...ure 7 12 Seal the exposed pipe section seams that are located above the roof SEAL Figure 7 12 Figure 7 12 Assemble and Install Storm Collar CAUTION Risk of Cuts Abrasions or Flying Debris Wear protect...

Страница 47: ...igure 7 15 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached...

Страница 48: ...se Flash and seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CA...

Страница 49: ...h the junction box receptacle to the outer shell A General Information WARNING Risk of Shock DO NOT wire 110 120 VAC to the ignition module or to the appliance wall switch IPI Incorrect wiring will da...

Страница 50: ...Component Tray The electrical components are installed on the component tray If it becomes necessary to remove the components use the information in Figure 8 2 to remove them and reinstall them correc...

Страница 51: ...the event of an emergency power outage Batteries should not be used as a primary long term power source Batteries tend to corrode over time When using batteries as a power source the 6 volt transform...

Страница 52: ...the junction box and connect to the top fan switch connector 1 4 inch male as shown Red Switch Switch Box Red Black Black Green Green White Power Supply Wires White Red Black Green White Minimum 14 3...

Страница 53: ...f valve if line pressure is greater than 1 2 psig 9 9 Gas Information Gas Pressure Natural Gas Propane Minimum inlet pressure 5 0 in w c 11 0 in w c Maximum inlet pressure 10 0 in w c 13 0 in w c Mani...

Страница 54: ...Adjustment The air shutter may be adjusted by locating and loosening the wing nut shown in Figure 9 1 Push Slide the wing nut toward the back of the appliance to close the shutter Pull Slide the wing...

Страница 55: ...sed for identification and veri fication purposes This task should be performed by a qualified service technician The logs and burner must be removed to see these identification marks Disconnect the p...

Страница 56: ...ith air flow through decorative barrier fronts Metal front of appliance may be covered with non combustible materials only Facing and or finishing materials must not interfere with air flow through de...

Страница 57: ...7 6 32 CEILING 1 5 6 7 8 9 10 4 12 11 13 3 13 14 15 16 14 15 16 17 TOP OF HOOD OR FIREPLACE OPENING See Dimension V on Appliance Dimension Diagram Figure 3 1 12 11 10 9 8 7 6 32 CEILING 8 9 10 12 11...

Страница 58: ...ion Manual 2641 980 Rev C 9 20 58 3 1 2 IN MIN 12 IN MINIMUM WITH ELBOW HEAT SHIELD INSTALLED 15 INCH MINIMUM WITHOUT ELBOW HEAT SHIELD INSTALLED Figure 10 7 Rear Vent Non Combustible Zone Above Appli...

Страница 59: ...Barrier Front Dimensions for Finishing Note Refer to Section 3 for individual decorative barrier front dimensions as installed on appliance Stop finishing material flush with fireplace surround openin...

Страница 60: ...y the decorative barrier front of the ap pliance depending on the fireplace model Splatter guards must be removed before appliance is fired WARNING Risk of Fire Close the ball valve before in stalling...

Страница 61: ...hown Figure 3 Hand Bend Tab Locations QUARTZ36 Shown HAND BEND TABS HAND BEND TABS 1 Locate the four hand bend tab on the base pan and bend each tab up to 90 degrees See Figure 3 LEFT REAR BASE LOG LE...

Страница 62: ...pin The left side of this log will be positioned by the front left hand bend tab The face of the log should contact the base pan edge See Figure 6 Figure 6 Install Left Front Base Log 5 Locate and in...

Страница 63: ...re 8 Install log by placing it on top of the log voids The tip of the log will contact front lip of base pan See Figure 11 Figure 12 Install Middle Right Cross Log 10 The middle right cross log 7 will...

Страница 64: ...s on the base pan and bend each tab up to 90 degrees Note the locations of the three log pins See Figure 3 5 1 1 2 3 4 6 7 Reference Figure 1 for identification of logs It is important to lay the logs...

Страница 65: ...e 6 Figure 6 Install Log 3 5 LOG 4 Locate and install the Log 4 by installing the left end of the log over the right log pin and press ing down to engage the log pin The face of the log should contact...

Страница 66: ...he manual bag assembly and left with the homeowner Do not store beneath the appliance Install Lava Rock by placing it by hand in the locations denoted by arrows in Figure 13 Care should be taken to av...

Страница 67: ...ndle fixed glass assembly with care Inspect the gasket to ensure it is undamaged and inspect the glass for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with g...

Страница 68: ...ontact with the hot viewing glass DO NOT operate the fireplace with the barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly inst...

Страница 69: ...87 mm 11 3 8 in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart Effect...

Страница 70: ...minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field tr...

Страница 71: ...8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8...

Страница 72: ...m 5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Per...

Страница 73: ...in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm DVP HRC ZC SS Figure 12 5 Vent Components DECORATIVE TERMINATIONS SHROUDS Only use listed decorative te...

Страница 74: ...E 48 A Vent Components Diagrams continued PVV SLP Vertical Power Vent Note A wire harness is required to power the PVV SLP and connect it to the appliance It is ordered separately from the PVV SLP Con...

Страница 75: ...ance and are ordered separately from PVI SLP B Contact your dealer to order 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN...

Страница 76: ...356 mm 15 1 2 IN 394 mm 11 1 2 IN 292 mm 8 IN 203 mm 4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN 135 mm 2 1 4 IN 57 mm 9 1 2 IN 241 mm 4 3 4 IN 121 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 4 IN 159 mm Front Vi...

Страница 77: ...tive Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter 6 1 2 in 165 mm 25 3 16 in 640 mm 8 1 16 in 205 mm 10 7 8 in 276 mm 8...

Страница 78: ...is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 133 mm...

Страница 79: ...Termination Kit 14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TV...

Страница 80: ...Coaxial Colinear Appliance Connector 768 380A Required Stainless Steel Flex Pipe DVP 2SL Adapter COAXIAL to COLINEAR VENTING Figure 12 13 Coaxial to Colinear Vent Components SLP HHW2 Horizontal High...

Страница 81: ...s included with accessories Contact your dealer for a list of ap proved accessories WARNING Risk of Fire and Electric Shock Use ONLY Hearth Home Technologies approved optional acces sories with this a...

Отзывы: