Majestic • MDVI30IN, MDVI35IN, MDVI30IL, MDVI35IL Installation Manual • 2205-980 Rev. H • 12/16
B. Mantel and Wall Projections
WARNING! Risk of Fire!
Comply with all minimum clear-
ances to combustibles as speci
fi
ed. Framing or
fi
nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Clearance to combustible material under the insert is 1/4
inch (6 mm). Clearance from top of
fi
replace opening for
combustibles extending 12 inches max. is 12 inches.
• Use leveling legs to raise insert minimum 1/4 inch (6 mm)
above combustible material or outer wrap of factory built
fi
rebox.
Combustible facings must not extend behind the insert
surround. For non-combustible material speci
fi
cations
refer to Section 1.E.
Figure 4.4 Mantel Clearances
12 IN. MIN.
12 IN. MAX.
EXISTING NON-COMBUSTIBLE FACING
10 IN. MIN.
2 IN.
MAX.
Figure 4.3 Firebox Opening - Deep Surround
C
D
SURROUND
APPLIANCE
1-1/2 IN.
B
D
A
D
APPLIANCE
SURROUND
TOP VIEW
SIDE VIEW
MINIMUM FIREBOX OPENING
Location
MDVI35IN/IL
MDVI30IN/IL
Inches
Millimeters
Inches
Millimeters
A
D
Alternate Unit Width
33-1/2
851
29-1/2
749
B
D
Alternate Unit Depth
15-1/8
384
14
356
C
D
Alternate Unit Height
23
584
19-3/8
492
Note: Dimensions assume 1/4 inch clearance on all sides.
Note: If exhaust collar on insert and
fi
replace damper do not line up, add 4 inches (102 mm) to minimum
fi
replace height for bends in vent pipe.