background image

11

Majestic Ashland Series • ASH42 Installation Manual  • 4059-915 • Rev M • 07/20

C. Construct the Chase

A chase is a vertical boxlike structure built to enclose the 

fireplace  and/or  its  vent  system.  Vertical  chimneys  that 

run on the outside of a building must be installed inside a 

chase.
In  cold  climates,  Hearth  &  Home  Technologies  recom

-

mends that the chase be well insulated using batt type in

-

sulation between the joists.
Construction of the chase may vary with the type of build

-

ing. These instructions are not substitutes for the require

-

ments of local building codes. Local building codes MUST 

be checked.
Chases should be constructed in the manner of all outside 

walls of the home to prevent cold air drafting problems. The 

chase  should  not  break  the  outside  building  envelope  in 

any manner. All outer walls need to be insulated.
Building  codes  require  false  ceiling  and  ceiling  firestops/

attic shields at each floor of the chase or every 10 ft (3048 

mm) of clear space to control spread of fire.
Walls,  ceiling,  base  plate  and  cantilever  floor  at  the  first 

level  of  the  chase  should  be  insulated  (see  Figure  3.3.) 

Vapor and air infiltration barriers should be installed in the 

chase as per regional codes for the rest of the home. Ad

-

ditionally, Hearth & Home Technologies recommends that 

the inside surfaces be drywalled and taped (or the use of 

an equivalent method) for maximum air tightness.
Holes and other openings should be caulked with high tem

-

perature caulk or stuffed with unfaced fiber glass insulation.

Ceiling 

Firestop 

Metal Chase Top 

Round Termination Cap

False Ceiling 

Insulation in the 

outside walls 

of the chase 

Attic  

Insulation 

Shield 

Chimney 

Ceiling 

Firestop 

Tabs 

False Ceiling 

False Ceiling 

Insulation 

Insulation 

Storm Collar

Figure 3.3  Chase Assembly

All outside walls should be insulated. 

Figure 3.4  Chase Constructions

 

1.  Fireplace and chimney enclosed in an exterior chase.

  2.  Chimney offset through exterior wall and enclosed in chase.

  3.  Chase constructed on roof.

•  The chase is constructed using framing materials much 

the same as the walls in your home. A variety of siding 

materials may be used including brick, stone, veneer 

brick, or standard siding materials. 

•  In  constructing  the  chase,  several  factors  must  be 

considered:

Maintain a 2 in. (51 mm) air space around the 

chimney.

-  The  chase  top  must  be  constructed  of  non-

combustible material.

-  In cold climates, a firestop spacer and attic insulation 

shield should be installed in an insulated false ceiling 

at  the  8  ft.  (2438  mm)  level  above  the  fireplace 

assembly. This reduces heat loss through the chase.

-  In cold climates, the walls of the chase should be 

insulated to the level of the false ceiling as shown in 

Figure 3.3. This will help reduce heat loss from the 

home around the fireplace.

WARNING! You must install false ceilings and ceil-

ing firestops at each floor of the chase or every 10 ft 

(3.05 m) to control spread of fire.

WARNING! Risk of Fire! DO NOT 

seal area between fire 

stop opening and chimney pipe except where they enter 

the attic or leave the warm air envelope of the home (use 

600° F sealant). 

WARNING! Risk of Fire! 

You must maintain a min-

imum 2 in. (51 mm) air space clearance to insula

-

tion and other materials surrounding the chimney 

system.

•  Insulation and other materials must be firmly secured to 

prevent accidental contact with chimney system.

•  The chase must be properly blocked to prevent blown 

insulation or other combustibles from entering and 

making contact with fireplace or chimney.

•  Failure to prevent contact between insulation or other 

materials and chimney system may cause overheating 

and fire.

Three examples of chase applications are shown in Fig

-

ure 3.4.

Содержание ASH42

Страница 1: ...d other flammable materials away INSTALLER Leave this manual with party responsible for use and operation OWNER Retain this manual for future reference ASH42 NOTICE DO NOT discard this manual DO NOT s...

Страница 2: ...ey and Termination Requirements A Chimney Requirements 15 B Offsets Returns 16 C Termination Requirements 17 5 Chimney Installation A Typical Chimney System 18 B Assemble Chimney Sections 19 C Intall...

Страница 3: ...rty responsible Photographing the installation and copying this checklist for your file That this checklist remain visible at all times on the fireplace until the installation is complete Combustible...

Страница 4: ...ompressed paper Plant fibers Plastic Plywood OSB Sheet rock drywall Any material that can ignite and burn flame proofed or not plastered or un plastered 1 Product Specific Important Safety Information...

Страница 5: ...supports chimney not shown Termination cap Chimney penetrates roof preferably without affecting roof rafters Offset Return with hanger straps Framing headed off in ceiling joists Enclosed space above...

Страница 6: ...ing Where the fireplace is to be installed The vent system configuration to be used Gas supply piping Electrical wiring Framing and finishing details Whether optional accessories devices such as a fan...

Страница 7: ...t point of the roof Wind loading possible Multi level Roofs Windward Leeward Recommended Location Above peak Recommended Insulated exterior chase in cooler climates Recommended Location Above peak Ins...

Страница 8: ...y Remove fireplace and components from packaging and inspect for damage Vent system components and doors are shipped in separate packages Report to your dealer any parts damaged in shipment Read all t...

Страница 9: ...in 1343 mm 3 3 4 in 97 mm 38 in 965 mm 54 in 1372 mm 74 1 8 in 1883 mm 97 1 2in 2477 mm 70 3 4 in 1797 mm 16 1 8 in 408 mm 11 1 8 in 282 mm 6 7 8 in 175 mm 5 in 129 mm 37 1 8 in 943 mm 11 in 281 mm 27...

Страница 10: ...ire You must comply with all minimum air space clearances to combustibles as specified in Figure 3 2 DO NOT pack required air spaces with insulation or other materials Framing or finishing material us...

Страница 11: ...n Storm Collar Figure 3 3 Chase Assembly 1 2 3 All outside walls should be insulated Figure 3 4 Chase Constructions 1 Fireplace and chimney enclosed in an exterior chase 2 Chimney offset through exter...

Страница 12: ...to combustibles around the fire place must be adhered to See Figure 3 2 Any framing across the top of the fireplace must be above the level of the top standoffs No recess above standoffs The finished...

Страница 13: ...combustible surfaces Protective metal hearth strips MUST be installed Hearth extensions MUST be installed exactly as specified WARNING Risk of Fire Prevent contact with sagging loose insulation DO NOT...

Страница 14: ...ng Use 6 in 152 mm flex not supplied to directly connect outside air to fireplace intake Insulate the pipe to prevent frost condensation Use the supplied outside air inlet hoods Seal between the wall...

Страница 15: ...section from the fireplace or at any chimney joint A Chimney Requirements Vertical distances are measured from the base of the fireplace as shown in Figure 4 1 4 Chimney and Termination Requirements T...

Страница 16: ...offset and return A B 1 1 4 in 32 mm OVERLAP Figure 4 2 Chimney Offset Return Example Your A dimension from Figure 4 2 is 14 1 2 in 368 mm Using Table 4 3 the dimension closest to but not less than 14...

Страница 17: ...ee illustration above B Gas Termination Cap A Perpendicular Wall If using decorative cap cover s this distance may need to be increased Refer to the installation instructions supplied with the decorat...

Страница 18: ...ng firestops are required where chimney passes through ceiling or floor Support straps for offsets not shown must be secured to adequate framing Termination Cap Storm Collar Offsets returns must be se...

Страница 19: ...h hanger straps provided fasten to studs or joists Vertical straight runs of chimney must be supported every 35 ft 10 7 m B Assemble Chimney Sections Use only those components described in this manual...

Страница 20: ...top of framing Note Use same dimensional lumber for framing ceiling firestop and joists 2 in 51mm clearance 2 in 51mm clearance WARNING Risk of Fire DO NOT seal area between firestop opening and chim...

Страница 21: ...e off any opening around the bottom If you wish to make a custom shield or barrier follow these guidelines Metal is preferred although any material stiff enough to hold back the insulation can be used...

Страница 22: ...en the flashing plate and the roof to a minimum Caulk the flashing plate and roof junction as well as the vertical seam on the flashing All nail heads must be caulked with a roofing sealant Caulk the...

Страница 23: ...in 51 mm Minimum Height Do NOT block air holes Caulk gaps between storm collar pipe and storm collar chase top Termination cap pipe and chimney section must be snapped together to maintain an overlap...

Страница 24: ...ection of pipe must stop between 2 in 51 mm above top of chase and 4 3 4 in 121 mm below top of chase 2 in 51 mm 4 3 4 in 121 mm Storm Collar Chimney Pipe Chase Top Termination Cap not shown Chase Col...

Страница 25: ...ve been tested for HHT fireplace systems and termination caps 3 in 76 mm minimum Min Base Dim Min Base Dim Min Top Dim Min Top Dim Min Opening Width Min Opening Width Radiation Shield 14 1 2 in 368 mm...

Страница 26: ...Termination Cap Chase Top Radiation Shield 3 in 76 mm Radiation Shield Height Termination Cap Figure 6 4 Roofed Style Shroud Dimensions 3 Roofed Style Shroud Radiation shield required 2 Mailbox Style...

Страница 27: ...at the top and sides between the fireplace and drywall to prevent cold air leaks Only non combustible materials may be used to cover the metal fireplace front Metal strips are placed 2 in 51 mm under...

Страница 28: ...8 in 1067 x 965 mm to allow for door installation If Mortar is applied it should be applied after finishing material is installed Mortar will be applied between finishing materials and molded brick ed...

Страница 29: ...to a minimum R value of 2 06 The hearth extension material MUST be covered with tile stone or other non combustible material Manufactured hearth materials will usually have a published R value resist...

Страница 30: ...re 7 5 Hearth Extension Construction 1 Fireplace Installed Flush on the Floor and Hearth Extension Raised to Bottom of Firebox Opening Non combustible flooring a minimum of 20 in 508 mm in front of an...

Страница 31: ...between the hearth extension and the front of the fireplace with a bead of non combustible sealant or grout Note The bottom of the fireplace opening is 3 3 4 in 95 3mm above the bottom of the fireplac...

Страница 32: ...equivalent material Refer to Figure 7 7 When creating the platform allow for the thickness of the non combustible finishing materials Seal gaps between the hearth extension and the front of the firepl...

Страница 33: ...T cover any air openings in the face of the fireplace Seal joint with non combustible sealant to prevent heat from being drawn into the wall cavity Figure 7 10 Mantel Specifications WARNING Risk of Fi...

Страница 34: ...Side Molded Brick Panel If a gas line is to be installed remove the knockouts in the inner firebox and in the outer shell on the side of your choice Refer to dimension drawings for location of knocko...

Страница 35: ...rod Insert the rod through the hole in the bracket Slip the last ring over the rod on the other side of the bracket Fasten the flat end of the screen rod back in place using the screw removed earlier...

Страница 36: ...lace the gas appliance must only be operated with the fireplace glass door fully open if included Only unvented gas log sets which have been found to comply with the standard for unvented room heaters...

Страница 37: ...L1130 Chimney Offset Return 30 deg FS538 Ceiling Firestop Straight FS540 Ceiling Firestop 30 deg AS10 Straight Attic Insulation Shield 24 in 610 mm JB577 Chimney Joint Band CB576 Chimney Bracket RF570...

Страница 38: ...10 mm JB577 Chimney Joint Band CB576 Chimney Joint Band 13 in 330 mm 2 in 51 mm 13 in 330 mm A B 17 in 432 mm RF570 Roof Flashing RF571 Roof Flashing 39 7 8 in 1013 mm 28 in 711 mm 15 1 4in 387 mm 25...

Страница 39: ...eries ASH42 Installation Manual 4059 915 Rev M 07 20 TR TVK CT 11A B 15 3 4 in 400 mm TR11 TR444 Round Termination Cap ST1175 ST475 Square Termination Cap TCT1175 Terra Cotta Cap TR11T B Round Telesco...

Страница 40: ...ud E D A C B Catalog A B C E E LDS BV in 26 12 5 15 5 22 23 mm 660 318 394 533 584 B A C B C A DTS134 DTS146 DTO134 DTO146 Decorative Caps DTO134 A B C in 34 20 24 mm 864 508 610 DTO146 in 46 22 7 26...

Страница 41: ...ed Duct 42 in 1067 mm 42 in 1067 mm 6 in 152 mm i d ID6 Insulated Duct 6 in 152 mm i d 16 in 406 mm 52 in 1321 mm 1 2 in 13 mm HX3 Hearth Extension A B C D LDS33 LDS46 Decorative Shroud E D A C B LDS...

Страница 42: ...42 Majestic Ashland Series ASH42 Installation Manual 4059 915 Rev M 07 20 This page intentionally left blank...

Страница 43: ...43 Majestic Ashland Series ASH42 Installation Manual 4059 915 Rev M 07 20 This page intentionally left blank...

Страница 44: ...44 Majestic Ashland Series ASH42 Installation Manual 4059 915 Rev M 07 20 Majestic a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www majesticproducts com...

Отзывы: