73D0129

13

DVKHL Series Gas Fireplace

VentInG InStaLLatIOn 

X

VENT TERMINATION  

AIR SUPPLY INLET 

AREA WHERE TERMINAL IS NOT PERMITTED 

 

Fixed

Closed

Operable

Operable

Fixed

Closed

CFM145a 
DV Termin Location 
5/01/01 Rev. 12/05/01  
sta 

INSIDE 

CORNER DETAIL 

CFM145a 

GeneraL VentInG InFOrMatIOn - terMInatIOn LOcatIOn

  A =  Clearance above grade, veranda, porch,  

12” (30 cm) 

12” (30 cm)

 

 

deck, or balcony

  B =  Clearance to window or door that may be  

6” (15 cm) for appliances  

6” (15 cm) for appliances

   

opened 

< 10,000BTU/h (3kW), 12” (30 cm)  

< 10,000 BTU/h (3kW), 9” 

 

   

 

for appliances > 10,000 Btuh (3kW) and 

(23 cm) for appliances > 10,000 

   

 

< 100,000 BTU/h (30kW), 36” (91 cm) 

Btuh (3kW) and < 50,000 BTU/h 

   

 

for appliances > 100,000 BTU/h (30kW) 

(15kW), 12” (30 cm) for 

   

 

 

appliances > 50,000 BTU/h(15kW)

  C =  Clearance to permanently closed window 

12” (305 mm) recommended to 

12” (305 mm) recommended to  

   

 

prevent window condensation 

prevent window condensation

  D = Vertical clearance to ventilated soffit located   

 

 

 

 

 

  above the terminal within a horizontal  

18” (458 mm) 

18” (458 mm) 

 

 

  distance of 2’ (610mm) from the center 

 

 

 

 

 

 

  line of the terminal
  E =  Clearance to unventilated soffit 

12” (305 mm) 

12” (305 mm)

  F =  Clearance to outside corner  

see next page 

see next page

  G = Clearance to inside corner (see next page) 

see next page 

see next page

  H =  Clearance to each inside of center line 

3’ (91 cm) within a height of 15’ (5 m)  

3’ (91 cm) within a height of 15’ 

   

extended above meter/regulator assembly 

above the meter/regulator assembly 

(5 m) above the meter/regulator 

   

 

 

assy

  I =  Clearance to service regulator vent outlet 

3’ (91 cm) 

3’ (91 cm)

  J =  Clearance to nonmechanical air supply inlet  6” (15 cm) for appliances < 10,000 

6” (15 cm) for appliances

   

to building or the combustion air inlet to any  BTU/h (3kW), 12” (30 cm) for 

< 10,000 BTU/h (3kW), 9”

   

other appliances 

appliances > 10,000 BTU/h (3kW) and   

(23 cm) for appliances > 10,000

   

 

< 100,000 Btuh (30kW), 36” (91 cm) 

BTU/h (3kW) and < 50,000 BTU/h

   

 

for appliances > 100,000 BTU/h (30kW) 

(15kW), 12” (30 cm) for  

   

 

 

appliances > 50,000 BTU/h(15kW)

  K =  Clearance to a mechanical air supply inlet 

6’ (1.83 m) 

3’ (91 cm) above if within 10'   

    

 

 

(3 m) horizontally

  L =  Clearance  above paved sidewalk or paved  7’ (2.13 m)† 

 

7’ (2.13 m)†

   

driveway located on public property

  M = Clearance under veranda, porch, deck or 

12” (30 cm) 

 

12” (30cm)

   

balcony 

 

 

 

1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel 
Gas Codes
† A vent shall not terminate directly above a sidewalk or paved 
driveway which is located between two single family  

 

dwellings and serves both dwellings
 only permitted if veranda, porch, deck or balcony is fully open on a 
minimum 2 sides beneath the floor:

 

 

canadian Installations

1

 

uS Installations

2

NOTE: 1. Local codes or regulations may require different    
 

  clearances.

 

2. The special venting system used on Direct Vent Fireplaces  

 

  are certified as part of the appliance, with clearances  

 

  tested and approved by the listing agency.

 

3. MHSC assumes no responsibility for the improper   

 

  performance of the appliance when the venting system  

 

  does not meet these requirements.

Figure 8 - 
Termination Locations

Содержание 400DVKHL

Страница 1: ...or additional information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile ho...

Страница 2: ...Burner 29 To Turn Off Gas 29 Check Gas Pressure Signature Command 30 Electrical Installation Signature Command 30 Electrical Wiring 30 Junction Box Wiring 31 Command Center Wall Installation 31 Wall...

Страница 3: ...ank s inside any structure Locate propane LP supply tank s outdoors To prevent performance prob lems do not use propane LP fuel tank of less than 100 lbs capacity 3 If you smell gas shut off gas suppl...

Страница 4: ...for servicing and proper operation 17 When the appliance is installed directly on carpeting tile or other combustible material other than wood floor ing you must set appliance on a metal or wood pane...

Страница 5: ...H ELEVATIONS Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4 500 feet 1 370 m above sea level For elevations above 4 500 feet 1 370 m in USA installat...

Страница 6: ...B 35Z x 902 mm 39Z x 1003 mm C 32 813 mm 36 914 mm D 22Z x 572 mm 24Z x 622 mm E 28Z 714 mm 32Z 816 mm F 30 762 mm 30 762 mm G 38M zn 976 mm 38M zn 976 mm H 23M 606 mm 23M 606 mm I 44C 1127 mm 44C 112...

Страница 7: ...ation or other materials This could cause a fire NOTE COLD CLIMATE INSULATION If you live in a cold climate seal all cracks around your appliance and wherever cold air could enter the room with noncom...

Страница 8: ...appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing Refer to the Venting section found...

Страница 9: ...om the mantel ceiling and side wall 6 5 3 21 2 41 2 45 1 31 2 FP2129 mantel leg 11 2 FP2129 Fireplace Opening Figure 5 Mantel clearances Top View WARNING Follow these instructions carefully to ensure...

Страница 10: ...mbustible materials i e brick tile slate steel or other materials with a UL fire rating of Zero may be used to cover the black painted face of the appliance It is permissible to bring combustible wall...

Страница 11: ...ystem could result in serious injury property damage or loss of life NOTICE Failure to follow these instructions will void the warranty 1 FP2131 Vent pipe clearances 1 3 73 1854 mm 24 Vertical Rise Re...

Страница 12: ...A Vent System in an Outside Chase below If pipe is enclosed in chase it is not exposed It is very important that the venting system maintain its balance between the combustion air intake and the flue...

Страница 13: ...ly above the meter regulator assembly 5 m above the meter regulator assy I Clearance to service regulator vent outlet 3 91 cm 3 91 cm J Clearance to nonmechanical air supply inlet 6 15 cm for applianc...

Страница 14: ...to the face of the outer wall must not exceed 16 4 9 m Sidewall Vent Graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system Figure 10 Rear Wall Ventin...

Страница 15: ...ase of the flue collars to the center of the wall opening Figure 12 Step 4 Using appropriate length of pipe section s attach to fire place with three 3 screws Follow with the installation of the elbow...

Страница 16: ...ber of offsets and horizontal vent length The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace or the top of the Transition Elbow to the face of the fi...

Страница 17: ...on depth down to 7 178 mm below grade level The 7 178 mm is measured from the center of the horizontal vent pipe as it penetrates through the wall Ensure that sidewall venting clearances are observed...

Страница 18: ...allowed in the system is 270 Figure 23 The minimum height of the vent above the highest point of penetration through the roof is 2 610 mm FP1183 max height 40 Maximum Height 12 Minimum Height 10 Maxi...

Страница 19: ...rpendicular to each other NOTE Pay special attention to these installation instructions for required clearances air space to combustibles when passing through ceilings walls roofs enclosures attic raf...

Страница 20: ...combustible material 4 Connect a section of pipe and extend up through the hole NOTE If an offset is needed to avoid obstructions you must support the vent pipe every three 3 feet Use wall straps for...

Страница 21: ...er must supply an external regulator The external regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming g...

Страница 22: ...ikely to freeze A sediment trap collects moisture and contaminants and keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner...

Страница 23: ...nter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point Turn unit to high Figure 30 After taking pressure reading be sure and turn captured screw clockwise firmly to reseal...

Страница 24: ...to cool before proceeding 2 Clean the inside of the firebox wall and floor where the blower and wires will be installed Make sure the firebox wall and floor are clean and dry before mounting the blowe...

Страница 25: ...x Run the two wires mentioned earlier up the left firebox wall and snap wires into clip assembled in 10 on the outer shell wall Make the connection to the left blower Replace the refractory and hearth...

Страница 26: ...re 36 Blower Access Covers FP2136 blower access plates Figure 35 Blower Access Covers FP2136 Figure 38 Attach Blowers to Brackets Figure 37 Install New Louvers FP2233 attach blower brackets 1 09 FP223...

Страница 27: ...attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to inspect the appliance and to r...

Страница 28: ...The gas control knob is designed to be operated by hand DO NOT use any tools during this operation Damaged knobs may result in serious injury WARNING 1 Depress and turn knob counterclockwise to pilot...

Страница 29: ...ing the burner Depress and turn the knob counterclockwise to the ON position Figure 41 It will take less than four 4 seconds for the burner to ignite Pilot position Depress and turn knob to pilot posi...

Страница 30: ...ace is equipped with the Signature Control valve which operates on 6 volts The AC adapter plugs into the fireplace junction box A C power supply Four 4 AA batteries are used for back up during power o...

Страница 31: ...ot extend beyond the 15 ft wire cable provided If a longer distance is required the 15 ft may be extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from junction...

Страница 32: ...Connector Control Board to Solenoid Gas In Gas Out Pilot Gas Tubing Valve A C Module FP2704 SCS wiring diagram To Outlet Light 300 Watt Max Optional Blower 300 Watt Max Rear Burner Solenoid 300 Watt...

Страница 33: ...correctly WARNING Electrical connections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the fan to the main electrical power supply...

Страница 34: ...ow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not function by...

Страница 35: ...gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will l...

Страница 36: ...battery Indication for Transmitter X Child Proof Lock out X LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blower Modu...

Страница 37: ...s button One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confirmation Refer to Figure 48 for location 2 After the RF receiver is on holding the OFF button on the Command...

Страница 38: ...Low then Off 3 Hold the OFF button anytime for three seconds or by turning off the wall switch These two commands of OFF are Memory Off the system will remember all last settings before turning off T...

Страница 39: ...s The blue LED backlight lights up for 8 seconds when any of the touch buttons is pressed The menus include TIMER THERMO LIGHT FAN and AUX Rear Burner Control The adjustment arrows include ON up and O...

Страница 40: ...n and the green LED on the Command Cen ter will flash for 10 seconds FP2649 set privace code Figure 51 FP2650 command ctr ctrl brd RF Receiver ON OFF Control Board Figure 52 FP2650 command ctr ctrl br...

Страница 41: ...ro 6 To exit Timer Mode a Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to zero Or c Slide down on the arrow buttons to exit TIMER mode and shut o...

Страница 42: ...he blower speed will take effect right away if the fireplace is off the receiver will remember this setting and the blower is still off see blower On Delay and Off Delay in the next section 4 After th...

Страница 43: ...ons then press TIMER but ton and THERMO button at the same time for 3 sec onds The backlight will flash once to indicate that the setting has changed to B 2 When the current setting is B pressing TIME...

Страница 44: ...heck battery installation or replace batteries 3 LCD display shows funny display 3 Reset the transmitter see Resetting the Transmitter section 4 Appliance does not come on 2 The transmitter did not ma...

Страница 45: ...f the glass toward the glass 4 Remove glass frame by releasing the three latches located at the top of the firebox Tilt glass away from the unit lift glass frame up and away from the unit Figure 63 FP...

Страница 46: ...d to secure the panel in place 4 Place the rear lower panel by setting it over the channel behind the light socket Make sure the grout line lines up with the one on the side 5 NOTE Have the left panel...

Страница 47: ...e wide end toward the back and the branch toward the front and left Set the log by having the protrusion on the bottom of the log rest to the left side of the grate bar and behind the pilot shield Als...

Страница 48: ...surface of the middle log When this log is in place the pointed end will come in contact with the back of the pilot log placed in step 2 Step 6 LG599 KHLDV upper right log LG599 6 Place the right uppe...

Страница 49: ...gs clean by vacuuming or brushing at least twice a year Make sure the burner porting pilot air opening and burner air opening are free of obstructions at all times Pilot Flame The flames from the pilo...

Страница 50: ...s may be used Handle glass door with care to avoid striking or scratching it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film deposit...

Страница 51: ...hermocouple connection at the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter lead wir...

Страница 52: ...he pilot flame for maximum flame impingement on thermocouple A Check for flue product leak Replace defective pipe section B Check horizontal venting piping is running upward 1 4 per foot Do not run th...

Страница 53: ...h Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check v...

Страница 54: ...t shown 1 26D2128K 26D2128K 5 Light Lens 1 73D0022 73D0022 6 Panel Access Door 2 73D0029K 73D0029K 7a Cottage Clay Firebrick Set 1 FBKHLDV40CC FBKHLDV500CC 7b Cottage Red Firebrick Set 1 FBKHLDV400CR...

Страница 55: ...73D0129 55 DVKHL Series Gas Fireplace REPLACEMENT PARTS Standing Pilot Millivolt control 1 3 4 5 6 7 8 2C 2I 2T 2 10 11 12 13 14 730024 khldv mv valve parts...

Страница 56: ...030 69D0030 69D0030 69D0030 5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 7 Rear Injector 1 58D0102 58D0052 57D0679 57D0680 7 Front Injector 1 57D...

Страница 57: ...73D0129 57 DVKHL Series Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 730024 KHLDV SG parts 12 08 1 2 3 4 14 5a b c d e 6 7a b 8a b 9 13 16 17...

Страница 58: ...1 57D0612 58D0056 56D3059 62D3005 8a Rear Burner Assembly 1 73D3270 73D3270 73D3268 73D3268 8b Front Burner Assembly 1 73D3269 73D3269 73D3267 73D3267 9 Venturi 1 45D0600 45D0600 45D0600 45D0600 10 W...

Страница 59: ...s REPLACEMENT PARTS Item Description Qty 400DVKHL 500DVKHL 1 Log 1 1 73D0539 73D0200 2 Log 2 1 73D0540 73D0201 3 Log 3 1 73D0541 73D0202 4 Log 4 1 73D0542 73D0203 5 Log 5 1 73D0543 73D0204 6 Log 6 1 7...

Страница 60: ...60 73D0129 DVKHL Series Gas Fireplace HOT 1 2 3 4 5 6 9 7 8 10 730024 KHLDV vent parts VENTing components REPLACEMENT PARTS...

Страница 61: ...K Heat Deflector Firestop 90 Elbow and Adjustable Pipe 11 to 14 24 Section of Pipe 2 1 Vertical Termination see below see below 5DT VC 2 1 Extended Vertical Termination 58DVA VCE 1283 2 1 High Wind Ve...

Страница 62: ...cordance with the above provisions shall comply with NFPA 720 and ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanently mounted to the exterior of...

Страница 63: ...ifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly...

Страница 64: ...ris Kentucky 40361 www mhsc com Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency 400DVKHLNV 69 6 400DVKHLPV 78 2 400DVKHLNSC 73 2 400DVKHLPSC 82 2 500DVKHLNV 75 2 500DVKHLPV 69 8 500DVK...

Отзывы: