ELECTRICAL WIRING
A. COMPLETE MILLI-VOLT SYSTEM CHECK
(“A” Reading - Thermostat contacts CLOSED - Control Knob “ON” - Main burner should turn ON)
a. If the reading is more than 100 milli-volts and the automatic valve still does not come on, replace the control.
b. If the closed circuit reading (“A” reading) is less than 100 millivolts, determine cause for low reading, proceed to
Section B below.
B. Thermopile Output Reading Check
(“B” Reading - Thermostat contacts OPEN - Main burner OFF)
1. Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, then check pilot
voltage, 325 millivolts minimum. If the minimum milli-volt reading is not obtainable, replace pilot.
CONNECT
METER
SWITCH OR
METER
CHECK
TO
LEADS TO
THERMOSTAT
READING
TEST
TEST
TERMINALS
CONTACTS
SHOULD BE
A
COMPLETE
2 & 3
CLOSED
CLOSED
SYSTEM
B
THERMOPILE
1 & 2
OPEN
OPEN
OUTPUT
CHECKING SYSTEM OPERATION
The milli-volt system and individual com-
ponents may be checked with a milli-volt
meter having a 0-1000 mV range. Conduct
each check shown in chart below by con
-
nection meter test leads to terminals as
indicated.
CONNECTING REMOTE RECEIVER
THESE InSTRUCTIOnS SUPERCEdE THE SEC-
TIOn EnTITLEd “HEaRTH MOUnT” In THE MILLI-
VOLT Hand-HELd REMOTE InSTRUCTIOnS SUP-
PLIEd WITH THE REMOTE.
1. Remove cover on control panel to show opening for
remote receiver.
See Figure 18.
2. Connect the remote connectors located in the unit
(Figure
18).
3. Slide remote receiver in the opening of control panel.
Use two screws provided to attach remote receiver to the
control panel.
See Figure 18.
4. Replace cover.
NOTE: Do not place remote in combustion
chamber.
Figure 18 - Installing Remote Receiver
Remote
Receiver
Cover