MODELS: 300DVBH & 400DVBH

  

DVBH SERIES 

DIRECT VENT GAS FIREPLACE

 

WARNINGS

IF THE INFORMATION IN THESE INSTRuCTIONS ARE 

NOT FOLLOWED ExACTLy, A FIRE OR ExPLOSION 

MAy  RESuLT  CAuSING  PROPERTy  DAMAGE, 

PERSONAL INjuRy OR LOSS OF LIFE.

–  Do not store or use gasoline or other flammable 

vapors and liquids in the vicinity of this or any 

other appliance.

–  WHAT TO DO IF yOu SMELL GAS
  •  Do not try to light any appliance.

  •  Do not touch any electrical switch; do not use 

any phone in your building.

  •  Immediately  call  your  gas  supplier  from  a 

neighbor's  phone.  Follow  the  gas  supplier's 

instructions.

  •  If you cannot reach your gas supplier, call the 

fire department.

–  Installation  and  service  must  be  performed 

by  a  qualified  installer,  service  agency  or  the 

gas supplier.

WARNING:  Improper  installation,  adjustment, 

alteration, services or maintenance can cause injury or 

property damage. Refer to this manual. For assistance 

or additional information consult a qualified installer, 

service agency or the gas supplier.   

This appliance may be installed in an aftermarket*, 

permanently  located,  manufactured  home  (USA 

only)  or  mobile  home,  where  not  prohibited  by 

local codes.

This appliance is only for use with the type of gas 

indicated  on  the  rating  plate.  This  appliance  is 

not convertible for use with other gases, unless a 

certified kit is used. 

*  Aftermarket:  Completion  of  sale, not  for  purpose  of  resale, 

from the manufacturer.

DuE  TO  HIGH  TEMPERATuRES,  THE 

APPLIANCE  SHOuLD  BE  LOCATED 

OuT  OF  TRAFFIC  AND  AWAy  FROM 

FuRNITuRE AND DRAPERIES.
CHILDREN  AND  ADuLTS  SHOuLD 

BE  ALERTED  TO  THE  HAZARDS  OF 

HIGH  SuRFACE  TEMPERATuRE  AND 

SHOuLD STAy AWAy TO AVOID BuRNS 

OR CLOTHING IGNITION.
y O u N G   C H I L D R E N   S H O u L D   B E 

SuPERVISED  WHEN  THEy ARE  IN  THE 

SAME ROOM AS THE APPLIANCE.
CLOTHING  OR  OTHER  FLAMMABLE 

MATERIAL SHOuLD NOT BE PLACED ON 

OR NEAR THE APPLIANCE.
KEEP  THE  ROOM  AREA  CLEAR  AND 

FREE FROM COMBuSTIBLE MATERIALS, 

GASOLINE, AND  OTHER  FLAMMABLE 

VAPORS AND LIquIDS.

READ BEFORE INSTALLING. SAVE THESE INSTRuCTIONS

INSTALLATION AND OPERATING INSTRuCTIONS

Содержание 300DVBH

Страница 1: ...l information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not...

Страница 2: ...n 28 Check Gas Type 28 Installing Gas Piping to Fireplace Burner System Location 28 Checking Gas Pressure 30 Electrical Installation 30 Electrical Wiring 30 Remote Wall Mounted Switch 31 Remote Wall S...

Страница 3: ...this unit is not properly installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide pois...

Страница 4: ...ll a qualified service person to arrange for replacement of the unit 19 Do not operate fireplace if any log is broken 20 Do not use a blower insert heat exchanger insert or any other accessory not app...

Страница 5: ...y rating determined under continuous operating conditions and was deter mined independently of any installed system Thermal efficiency up to 75 AFUE efficiency up to 71 Hi Lo Knob product SPECIFICATIO...

Страница 6: ...been received You should have the following Fireplace Firebox and Burner System Rock Wool Log Set Items Required For Installation Tools Building Supplies Phillips Screwdriver Framing Materials Hammer...

Страница 7: ...lowing Figure 2 and the chart below for your specific installation requirements See Figure 3 on Page 8 for firebox dimensions The framing headers may rest on the top of the firebox standoffs Do not br...

Страница 8: ...Pipe Rear L R D 161 2 181 2 Rear Width E 28 29 Glass Height F 18 203 8 Total Height G 337 8 405 8 Depth H 15 181 4 Figure 3 Fireplace Dimensions DESCRIPTION Key Letter 300DVBH 400DVBH Height to Stando...

Страница 9: ...and draperies due to heat from appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See...

Страница 10: ...l flooring the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING clearances Clearances to combustibles mantel cleara...

Страница 11: ...lace to the floor Use four 4 screws to attach fireplace to framing The side nailing flanges are 1 2 or 5 8 to accommodate different wall thickness SECURING FIREPLACE to floor or framing Figure 6 Secur...

Страница 12: ...Be aware of electrical wiring locations in walls and ceilings The following actions will void the warranty on your venting system Installation of any damaged venting component Unauthorized modificatio...

Страница 13: ...f this vent system require a minimum of 3 clearances to combustibles at the top of the flue and 1 clearance at the sides and bottom until the flue penetrates the outside wall A minimum 1 clearance all...

Страница 14: ...1 Remove the eight 8 screws securing the flue pipe adapter to the fireplace body See Figure 9 2 Set the flue pipe adapter aside complete with the gasket Do not damage the gaskets as the adapter and ga...

Страница 15: ...each floor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exterior of the house See Installi...

Страница 16: ...ventilated soffit located above the terminal within a horizontal distance of two 2 feet 610mm from the centerline of the terminal 18 457mm minimum E Clearance to unventilated soffits 12 305mm minimum...

Страница 17: ...he vertical and horizontal dimensions of the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the outer wall Using this dimension on the Sidewall Vent Graph...

Страница 18: ...r s tabs Attach Simpson s DirectVent Pro by fully inserting into the collar and securing with self tapping screws The screws shall only penetrate the flue outer wall Refer to vent manufacturer s insta...

Страница 19: ...o All Four Sides Vent Cap Wood Screw Cut Vinyl Siding Away to Fit Standoff Wood Screw Simpson Termination 985 Bolt Apply Mastic to All Four Sides Nut Standof 950 Figure 20 Installing Firestop on Horiz...

Страница 20: ...exits through foundations less than 20 below outcrop the termination must be flush up with outcropped wall above It is best to locate the fireplace in such a way that minimizes the number of offsets...

Страница 21: ...n A plus B must not be greater than 17 5 2m The maximum number of 45 elbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For eac...

Страница 22: ...ase of snorkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approximately 4 below snorkel See Figure 26 3 Install vent system 4 Ensur...

Страница 23: ...y 18 450mm Example Maximum horizontal length No elbows 10 3m 1x45 elbows 8 5 2 6m 2x45 elbows 7 2 1m A minimum of an 8 2 5m vertical rise is required Two sets of 45 elbows offsets may be used within t...

Страница 24: ...e plumb down from the ceiling to the position of the flue exit Mark the center point where the vent will penetrate the ceiling Drill a small locating hole a this point Drop a plumb line from the insid...

Страница 25: ...p roof pitches Nearby trees adjoining roof lines steep pitched roofs and other similar factors may cause poor draft or down drafting in high winds Increasing the vent height may solve this problem NOT...

Страница 26: ...parately UL1777 listed type flex venting only 3 Start the flexible vent as follows A Installing the inner flex adaptor and pipe see Figure 1 1 Insert the long side of the 4 inner ring inte exhaust pip...

Страница 27: ...bed by the flexible vent manufacture and in such a way as to maintain concentric inner and outer vent spacing D Attaching flexible venting to vertical termination assemblies 1 When using Simpson pipe...

Страница 28: ...alling gas piping to fireplace burner system location installation items needed Before installing fireplace and burner system make sure you have the items listed below External regulator supplied by i...

Страница 29: ...ip leg in supply line as shown in Figure 40 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and burner system Locate sediment trap drip...

Страница 30: ...ure reading be sure and turn captured screw clockwise firmly to reseal Do not over torque Check test points for gas leaks Figure 41 Gas Pressure Check at Gas Valve Pressure Test IN Pressure Test OUT H...

Страница 31: ...lways check with local code Figure 42 Wiring Diagram for Wall Switch Do not connect 110V to wall switch WARNING Electrical installation Figure 43 Blower Wiring Diagram Remote Wall Switch Position the...

Страница 32: ...ter firebrick panel on the back wall first Stand firebrick panel straight up against the back of fireplace with the bottom edge at bottom of inner firebox 4 Repeat Step 3 with the left and right side...

Страница 33: ...the unit to establish yellow flame in the front See Figure 46 4 Place log 1 into place by setting the log over the two pins on the grate toward the back The two round holes on the bottom of the logs s...

Страница 34: ...he two notches on the bottom of this log with the two protrusions on log 1 2 This log when seated fits in the middle above logs 1 2 See Figure 50 8 Place log 5 into place by matching the two notches o...

Страница 35: ...bar Figure 52 Placement of Log 6 Figure 53 Placement of Log 7 HBDV400 only Figure 54 a b Andiron Placement 400DVBH and 300DVBH Figure 55 Universal Andirons final installation installing universal and...

Страница 36: ...air may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to inspect the appliance and to replace any par...

Страница 37: ...closed it is possible to start the lighting operation The gas control knob is designed to be operated by hand DO NOT use any tools during this operation Damaged knobs may result in serious injury WARN...

Страница 38: ...lows you to turn on and to turn off the main burner without using the gas valve knob Make sure the button is in the ON position to light the main burner See Figure 57 Lighting the burner Depress and t...

Страница 39: ...in operation See Figure 61 The pilot flame has three distinct flames one engulfing the thermopile one engulfing the thermocouple and the other reaching to the main burner burner Inspect area around th...

Страница 40: ...Handle glass door with care to avoid striking or scratching it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film deposit on the inside...

Страница 41: ...nection at the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter lead wire on the thermo...

Страница 42: ...for maximum flame impinge ment on thermocouple A Check for flue product leak Replace defective pipe section B Check horizontal venting piping is running upward 1 4 per foot Do not run the pipe level...

Страница 43: ...54D5032 43 1 2 3 5 6 7 10 4 9 11 replacement partS fireplace components...

Страница 44: ...k Right TB 1 54D0285 54D0187 7 Standard Firebrick Left TB 1 54D0285 54D0186 5 Standard Firebrick Center CR 1 26D7097 26D7105 6 Standard Firebrick Right CR 1 26D7096 26D7104 7 Standard Firebrick Left C...

Страница 45: ...54D5032 45 1 2 3 4 5 6 7 11 12 13 14 15 2T 2I 2C 8 8A 400DVBH 8B 300HBDV 10 Millivolt engine replacement partS...

Страница 46: ...03 14D0503 7 Injector 1 62D3006 20H3156 62D3004 33D5039 8 Burner Assembly 1 54D5115 54D5115 54D5006 54D5006 9 Venturi 1 45D0600 45D0600 45D0600 45D0600 10 Wire Assembly 1 44D0500 44D0500 44D0500 44D05...

Страница 47: ...Profile Vertical Termination Cap 46DVA VC 980 4DT VC 1 1 Square Horizontal Termination Cap aluminum 46DVA HC 985 4DT HC Round Horizontal Termination Cap Square Base aluminum 46DVA HRCS Sconce Termina...

Страница 48: ...Description Qty 300DVBH 400DVBH 1 Rear Log 1 54D5125 54D5040 2 Right Log 1 54D5126 54D5041 3 Left Log 1 54D5127 54D5042 4 Mid Top Log 1 54D5129 54D5043 5 Right Top Log 1 54D5128 54D5044 6 Left Front L...

Страница 49: ...feet above finished grade in the area of the venting including but not limited to decks and porches the following requirements shall be satisfied 1 INSTALLATION OF CARBON MONOXIDE DETECTORS At the tim...

Страница 50: ...purposes c MANUFACTURER REQUIREMENTS GAS EQUIPMENTVENTING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or ven...

Страница 51: ...y will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly dam age by acci...

Страница 52: ...52 54D5032 AUGUST 2008 54D5032 Rev 5 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: