WMC Series Woodburning Fireplace

20000583

FP593

SR/C

11/20/97

Fig. 19 

 Installing firestop spacer.

FP593

Nails (4)

Firestop Spacer

Joist

Attic Installation

Ceiling Installation

Joist

Firestop Spacer

Nails (4)

FP263

Fig. 20 

 Attic shield installlation (Canadian requirement).

IGF263

MBUF

5/9/96

Attic Insula-

tion Shield

Ceiling

Base 

Flanges

Nails

(4 required)

Attic Joist

hole and the angled portion extending down into the 
hole.
Firestop spacers are not available for nor are they re-
quired on vertical walls.

DO NOT 

put any sealant around the area where the 

outer pipe slides through the firestop spacer.  If you seal 
this area, 

it may cause a fire hazard.

Canadian Requirements for

 Insulation Shield

In Canada, an attic insulation shield is required to pre-
vent attic insulation from contacting the chimney sec-
tion.  Framing dimensions for the chimney hole should 
measure 14

¹⁄₂

" x 14

¹⁄₂

"  (368 x 368 mm) for SK8; 17

¹⁄₂

" x 

17

¹⁄₂

" (445 x 445 mm) for 3-wall.  An attic shield MUST 

be installed on top of attic joists (above the floor level).  
(Fig. 20) 

NOTE:

 In the U.S., it is a good idea, although not al-

ways required, to install an attic insulation shield where 
blown-in insulation is planned to be used in the attic.
Install the attic insulation shield with the flanges on its 
base extending down into the framing hole. Nail each 
corner of attic insulation shield to the framing members 
of the ceiling hole using 8d nails.  Attic shields are not 
required at the roof.

Continue Installing Pipe to Complete Run

Continue attaching pipe sections to complete system 
to next level always being careful that the pipe is firmly 
snapped locked in place before proceeding to next pipe 
section.

Chimney Supports

If chimney supports are required, they are installed 
the same as elbows.  Nail chimney support straps to 
adjacent structural framing, as shown on Page 7, Figure 
7. Bend straps as necessary and make sure they are 
secure so they will support the weight of the chimney. A 
chimney support is 2

¹⁄₂

" long when installed. Consider 

this dimension when determining how many straight 
chimney sections are needed.

NOTE:

  Chimney supports are generally used in long 

runs in a chase installation.

Additional Ceilings

If you encounter additional ceilings, repeat same steps 
required for first ceiling installation.  Refer to firestop 
illustration on Figure 19. 

Penetrating the Roof

Run pipe to roof line.  Since chimney system must be 
vented to the out-of-doors, you 

must 

use an approved 

termination.
If a chase is used, refer to the installation manual pro-
vided with the termination cap.

Locate Chimney Centerpoint On Roof

Use same procedure detailed in locating center point of 
the flue system.
Drive a nail up through roof at the center point.  This will 
determine center point on outside of the roof.

Cut and Frame Roof Hole

Size of roof hole varies with the type of chimney ter-
mination installed.  Refer to installation instructions 
provided with the chimney termination to find correct 
size of roof hole.
There must be an air space (1

¹⁄₂

" - SK8; 2" - 3-wall) 

between outermost portion of chimney sections and any 

Содержание WMC36 WMC42

Страница 1: ...se in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 20000583 7 06 Rev 20 FP583A WMC 12 18 98 WMC Series Woodburning Fireplace Homeowner s Installation and Operating Manual ...

Страница 2: ...tion or assembly with a CFM Corporation fireplace system notwithstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such action may possibly cause a fire hazard Consult local building codes to ensure that you are in compliance before installing the fireplace Fireplaces must be vented to the out of doors Do not obstruct or modify air inlet...

Страница 3: ...8 Dia 203mm 3 6 9 1 4 m m Fig 2 WMC42 Series specifications and framing FP592A WMC42 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt 1 6 m m 13mm 36 914mm 35 895mm 40 1016mm 16mm 19 502mm 1 45mm 35 902mm 21 7 197mm 7 191mm Recessed Nailing Flange 11 Dia 279mm Rough Opening Width 41 Rough Opening Height Rough Opening Depth Gas Line Access 47 1194mm 47 1194mm 6 6 1 6 8 3...

Страница 4: ... Surround Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both sides Nailing Flange Standoff Batt Insulation cut out around firestop Firestop Ceiling Level A B C FP1531 hearth dimensions 9 04 djt Front Width Back Width Depth A B C WMC36 33 18 20 851 mm 464 mm 514...

Страница 5: ...5 1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0 1 2 1 68 124 0 1 2 1 1 70 128 0 0 0 3 1 74 134 0 1 1 2 2 78 140 0 0 3 1 2 81 146 0 1 0 3 2 84 151 0 0 2 2 2 87 156 0 1 3 1 2 89 160 0 0 1 3 2 93 166 0 1 2 2 2 95 170 0 0 0 4 2 99 177 0 1 1 3 2 101 1...

Страница 6: ...ust be at least 2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak of the roof is more than 10 3 m a chimney height reference point is established that is on the surface of the roof a distance of 10 3 m from the chimney in a horizontal plane The top of the chimne...

Страница 7: ...ates If you live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncombustible insulation rated for a minimum of 300 F Insulating is very important for outside wall installations over a concrete slab If fireplace is installed on a platform insulation should be pla...

Страница 8: ...tions Read all instructions before beginning installation Fol low instructions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V switch described in the fan or fireplace installa tion instructions Installation Instructions For mounting the speed control a 2 deep standard electrical box should be used Using wire nuts sup plied wit...

Страница 9: ...rporation elbows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very important to install the second elbow in each offset as close to the ceiling or support as possible so the elbow straps can be secured to framing members to help support the weight of the chimney Determi...

Страница 10: ...pical frame for ceiling chimney hole FP551 WF551 BR BC 9 29 97 See Fig 12 See Fig 12 Existing Ceiling Joists Ceiling New Framing Members Chimney Hole Fig 12 Ceiling chimney hole sizes necessary for installing firestop spacer Size of Chimney Vertical 30 8 Flue SKFS2A SKFS6A SK Series 14 x 14 14 x 25 368mm x 368mm 368mm x 648mm 8 Flue FS2A FS6A S Series 3 Wall 17 x 17 17 x 29 445mm x 445mm 454mm x 75...

Страница 11: ...clearly snap together Once sections are snap locked in place it is extremely difficult to get them apart Make sure the pipe is firmly snapped and locked together as each pipe section is mounted When installing elbows only outer pipe will snap lock Middle pipes simply slide into position Be sure to always attach straps on upper elbow to a structural framing member Fig 18 Continue installing the pipe ...

Страница 12: ... the roof Continue Installing Pipe to Complete Run Continue attaching pipe sections to complete system to next level always being careful that the pipe is firmly snapped locked in place before proceeding to next pipe section Chimney Supports If chimney supports are required they are installed the same as elbows Nail chimney support straps to adjacent structural framing as shown on Page 7 Figure 7 B...

Страница 13: ...op spacers and con struction of chase may vary with type of building These instructions are not a substitute for local building codes You must check your local building codes to determine specific requirements for your city or state NOTE Other building materials may be required in addition to Firestop Spacers Finishing CAUTION All joints between the finished wall and the fireplace surround top sides ...

Страница 14: ...of the SP40 with the same wall clearances specified for the SP40 Rt must 1 85 minimum Examples of wall shield insulation 1 Manville CERAFORM 126 K 27 1 2 inches thick 2 CFM Corporation EH2416 K 458 1 inch thick required FP531b Fig 22 Mantel clearance FP531b mantel clearances 9 03 djt 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Combustible Mantel and Trim Finished Wall Header Standoff Noncombustibl...

Страница 15: ... related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R value may be used provided thickness of material is sufficiently greater to maintain an equivalent total thermal resis tance Rt Minimum Wall Clearances WITH Noncombustible Surround Facing WITHOUT Noncombustible Surround Facing Minimum Hearth Exte...

Страница 16: ... of listed material per inch material Example of Determining Hearth Extension Equivalents To determine the thickness required for any new mate rial Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in new re quired thickness FP550 BR BC SEALING DETAILS 9 29 97 Wall Covering Noncombustible Decorative Facing Noncombustible Decorative Covering Seal all cracks between fireplace surround and wall...

Страница 17: ...between the pipe and tube NOTE Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from fireplace side NOTE When installing an ANSI Z21 11 2 ventless appliance the finishing materials used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in fireplace should be rated less than 100 000 BTU Hr Gas pipe ...

Страница 18: ...7554338 7554338 6 Damper Knob Wood 7536177 7536177 7 Screen Pulls two per fireplace 5584139 5584139 8 Firebrick Left Side 3041104 3034102 9 Firebrick Back 3030102 3034104 10 Firebrick Right Side 3041105 3034103 11 Firebrick Hearth 3041103 3034105 12 Screen Rod Assembly 3030126 3032112 13 Top Brick Retainers three per fireplace 3030172 3030172 14 Nailing Flange Bag of 4 w screws 2253160 2253160 15 Ca...

Страница 19: ...In addition such action may void the coverage provided by the owner s insurance Accessories Contact your CFM Corporation distributor or dealer for finishing Mantels available in a wide selection of styles Glass Door Optional Bi Fold door set Brushed Brass finish 36GDKBB WMC36 42GDKBB WMC42 Deluxe Polished finish 36GDKDP WMC36 42GDKDP WMC42 Pewter finish 36GDKS WMC36 42GDKS WMC42 Outside Air Terminatio...

Страница 20: ...le chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Includes adapter Flashing not included SK8 Chimney Sections Pipe used to build 8 SK8 flue systems SK81 1 Long SK818 1 Long SK83 3 Long SK84 4 Long SK8 Chimney Elbows Elbow used to create an offset in an 8...

Страница 21: ...om the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclosure Installs on the over the chimney collar of the CCE SK SK8 fireplace provides outside air to assist in cooling the chimney system Attic Insulation Shield Used to prevent insulation from coming in ...

Страница 22: ...22 WMC Series Woodburning Fireplace 20000583 ...

Страница 23: ...arranty is extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the installation instructions furnished with the Fireplace and oper ated at all times under normal conditions use and service ac cording to the operative instructions furnished with the Fireplace and only if and so long as ...

Страница 24: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation ...

Отзывы: