Installation

Chimney Supports

 

The chimney system is supported by the fireplace for 
vertical chimney heights less than 30' (9m) above the 
hearth. Chimney supports are required if the vertical 
height exceeds 30' (9m) with SK8 chimneys or 20' (6m) 
with 3-wall chimneys. Locate chimney supports at ceil-
ing holes or other structural framing at 30' (9m) (SK8) 
or 20' (6m) (3-wall) heights. Spacing between chimney 
supports 

must not

 exceed 30' (9m) (SK8) or 20' (6m) 

(3-wall).  Use Chimney Support Model SKCS8.  

(NOTE:  

The SKCS8 can not be mounted directly to the 
fireplace.) 

 Support provided by elbow straps fulfills the 

support requirement only if they are spaced as previ-
ously described. (A chimney support is 2

¹⁄₂

"  (64mm) 

long when installed.)
Angled chimney runs require a support every 6' (1.8m) 
in addition to the elbow straps. Chimney supports are 
used for this function. (Fig. 9) 

Chase Installation

A chase is a vertical box-like structure which encloses 
the fireplace and/or chimney. Chases are typically built 
on the outside of the house with fireplace opening cut 
into the outer wall of a room. (Page 5, Fig. 5)
If you need help in determining fireplace location or how 
the chimney system should be run, contact your Majes-
tic Fireplaces dealer for assistance.

If you live in a cold climate, it is not required but 

highly recommended

 that you insulate fireplace 

enclosure to eliminate cold air penetration as much as 
possible.
Insulate base of fireplace with a noncombustible 
insulation rated for a minimum of 300°F.  Insulating 
is 

very important

 for outside wall installations over 

a concrete slab. If fireplace is installed on a platform, 
insulation should be placed on top of the platform 

before 

fireplace is set. (Fig. 10)

When a fireplace is installed in a chase or on a 
outside wall, enclosure should be treated like any 
outside wall in a home. Insulation should be installed 
on the inside wall as well as the outside wall(s). In a 
chase, it is also a good idea to install a firestop at the 
first ceiling level above the fireplace and enclose the 
chase with sheeting material. Insulation may then be 
installed above sheeting material to assure the space 
around the fireplace is totally protected. (Fig. 5)
When installing the chimney, 

DO NOT

 caulk between 

outer pipe and firestop. It is vital that some air be al-
lowed to flow through this very thin gap.

CAUTION:  WHEN INSTALLING A FIREPLACE 
IN AN INSULATED ENCLOSURE, BE SURE ALL 
REQUIRED AIR SPACES ARE MAINTAINED. (Page 
14, Figure 20)

FP284

Fig. 9 

 Chimney support installation

IWF284

MBUF

5/25/96

Chimney Sup-

port Strap

SKCS8

Содержание Royalton BC36

Страница 1: ...Woodburning Fireplace For Models BR36 BR42 BC36 BC42 DO NOT DISCARD THIS MANUAL Retain for future use 7412944 12 06 Rev 19 For use in U S Canada Underwriter s Laboratories Report No MH6018 Homeowner...

Страница 2: ...se of any component part not manufactured or approved by CFM Corpo ration in combination or assembly with a Majes tic Fireplaces replace system notwithstanding any independent testing laboratory or ot...

Страница 3: ...1041mm 8 Dia 203mm 8 2 2 m m If elbows are offset to the back of the unit chase depth will be 22 575mm Fig 2 BC36 Series speci cations and framing BC36 Series Woodburning Fireplace Circulating Model 1...

Страница 4: ...Air Gas Line Access Electrical Access 1194mm 8 Dia 203mm 8 9 5 m m If elbows are offset to the back of the unit chase depth will be 22 575mm BR42 Series Woodburning Fireplace Fig 3 BR42 Series speci c...

Страница 5: ...Collar Pan Flashing Draftstop Standoff Surround Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Outside Air Cover Plate Electrical Access Gas Line...

Страница 6: ...42 Maximum 90 0 90 0 Minimum Without Elbows 12 6 12 6 With 2 Elbows 14 6 14 6 With 4 Elbows 21 0 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a structu...

Страница 7: ...nning a chimney system it is important to know 1 The height of a chimney is measured from the hearth to the exit point on the termination 2 A chimney cannot be offset more than 30 from a vertical plan...

Страница 8: ...location or how the chimney system should be run contact your Majes tic Fireplaces dealer for assistance If you live in a cold climate it is not required but highly recommended that you insulate repl...

Страница 9: ...kit Remove knockout in the center of the back of the EB1 and install listed cable clamps Feed electrical wire through listed cable clamp leaving approximately 6 152 mm of wire exposed through the EB1...

Страница 10: ...requirement at attic level Offset Installation In order to clear an obstruction it may be necessary to offset chimney from vertical This is accomplished by using CFM Corporation elbows Use the 30 Offs...

Страница 11: ...ls strips provided with the replace Note Safety strips are not required over noncombusti ble oors where all supports at the base of the replace are noncombustible Four 4 nailing anges are supplied wit...

Страница 12: ...de minimum required air space to chimney pipe for ceiling thickness up to 8 203mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 203mm adjustments must be mad...

Страница 13: ...additional ceilings repeat same steps required for rst ceiling installation See restop illus tration on Page 12 Figure 18 Penetrating the Roof Run pipe to roo ine Since chimney system must be vented...

Страница 14: ...he wall with material of your choice Do not install a combustible mantel shelf less than 12 305mm from the top of the replace opening for radiant models and 12 305mm from top of grille opening for cir...

Страница 15: ...2 305mm Min 1 38mm 6 159mm Min 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Mantel Clearance Radiant Model No Noncombustible Facing Material Combustible Mantel and Trim Finished Wall Header Standoff N...

Страница 16: ...ecure the hearth extension to the oor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the replace hearth and hearth extension with a noncombusti...

Страница 17: ...inch Units of K BTU SQ FT HR F IN Thickness of Listed Material FP533ADD Addendum 6 1 99 djt 8 4 99 changed 2 to 1 one inch to 1 2 inch djt FP533ADD Fig 24 Hearth extension material factors FP550 Fig 2...

Страница 18: ...ll chisel and hammer carefully tap around the knockout until it loosens and falls out Install 1 2 inch certi ed gas pipe through opening After gas pipe installation is complete use insulation that was...

Страница 19: ...03 or 20007494 3032103 or 20007496 6b Firebrick Rear 3030102 or 20007495 3032102 or 20007497 6c Firebrick Rt Side 3030160 or 20007492 3030160 or 20007492 6d Firebrick Lt Side 3030104 or 20007493 30301...

Страница 20: ...provided by the owner s insurance Accessories Contact your Majestic Fireplaces distributor or dealer for nishing Marble and Mantels available in a wide selection of styles Glass Door Standard Bi Fold...

Страница 21: ...himney through CT100 a chase top Appropriate adapter required Flashing not included Adapter Kit Unites Square Chase Termination with chimney CTSK pipe required Chase Top Housing Low pro le pyramid sty...

Страница 22: ...ion Shield Used to prevent insulation from coming in AIS SK contact with the chimney system SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN 1 Long roof SK84CAN 4 Long 45 Chim...

Страница 23: ...s extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the installation instructions fu...

Страница 24: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: