background image

13

ODSHR  Outdoor Woodburning Fireplace

20002264

Firestop spacers are not available for, nor are they 
required on, vertical walls.
The CFM Corporation chimney components have been 
tested and approved with the area where the outer 
pipe slides through the firestop spacer sealed with a 
noncombustible caulk if desired, or left completely open 
with no sealant.

Continue Installing Pipe to Complete Run

Continue attaching pipe sections to complete system 
to next level always being careful that the pipe is firmly 
snap locked in place before proceeding to next pipe 
section.

Chimney Supports

If chimney supports are required, they are installed 
the same as elbows.  Nail chimney support straps to 
adjacent structural framing, as shown in Page 8, Figure 
9. Bend straps as necessary and make sure they are 
secure so they will support the weight of the chimney. A 
chimney support is 2

¹⁄₂

"  (64 mm) long when installed. 

Consider this dimension when determining how many 
straight chimney sections are needed.

Note:

  Chimney supports are generally used in long 

runs in a chase installation.

Additional Ceilings

If you encounter additional ceilings, repeat same steps 
required for first ceiling installation.  See firestop illus-
tration on Page 12, Figure 19. 

Penetrating the Roof

Run pipe to roofline.  Since chimney system must be 
vented to the out-of-doors, you 

must 

use an approved 

CFM Corporation termination.
If a chase is used, refer to the installation manual pro-
vided with the termination cap.

Locate Chimney Centerpoint On Roof

Use same procedure detailed in locating center point of 
the flue system.
Drive a nail up through roof at the center point.  This will 
determine center point on outside of the roof.

Cut and Frame Roof Hole

Size of roof hole varies with the type of chimney 
termination installed.  Refer to installation instructions 
provided with CFM Corporation chimney termination to 
find correct size of roof hole.
There must be a 2" (51 mm) air space between out-
ermost portion of chimney sections and any adjacent 
combustible surfaces. (Combustible surfaces include 
burnable materials such as:  ceiling members, joists, 
flooring, combustible insulation and roof structures.)

WARNING:  DO NOT PACK REQUIRED AIR SPACES 
WITH INSULATION OR OTHER MATERIALS.

Mark an outline of the roof hole around the centerpoint 
of the nail. 

NOTE:

 Hole dimensions given in the chim-

ney top installation instructions are 

horizontal 

dimen-

sions; therefore, the hole size must be marked on the 
roof accordingly.
Cover the opening of the installed chimney so debris 
cannot get into the system.
Cut and frame the hole. It is good practice to use fram-
ing lumber that is the same size as the rafters.  Install 
the frame securely because the chimney top and flash-
ing anchored to the frame must be able to withstand 
heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your 
termination according to the 

Ten Foot Rule

, continue to 

install pipe to the predetermined height.
Check the chimney top installation instructions for 
details on how high above the roof top the chimney 
sections (all pipes) should extend.

Installing Top Housing or Termination

Follow the installation instructions provided with the 
CFM Corporation chimney termination you have se-
lected.

Installing Chimney In a Chase

Refer to Page 5, Figure 4 for an illustration of a typical 
chase installation.

CAUTION:

  Treatment of firestop spacers and con-

struction of chase may vary with type of building.  
These instructions are not a substitute for local building 
codes. You 

must

 check your local building codes to 

determine specific requirements for your city or state. 

NOTE:

  Other building materials may be required in ad-

dition to Firestop Spacers.

Finishing

CAUTION:  

All joints between the finished wall and 

the fireplace surround (top/sides) must be sealed with 
noncombustible material to prevent cold air leakage 
into the room. Only noncombustible material may be 
applied to the facing of the fireplace surround. (Fig. 20)

Содержание ODSHR42

Страница 1: ...djt Homeowner s Installation and Operating Manual DO NOT DISCARD THIS MANUAL Retain for future use 20002264 1 08 Rev 18 Model ODSHR42 Underwriter s Laboratories Report No MH20546 ODSHR Series Outdoor...

Страница 2: ...re hazard and will void the warranty Safety Information 2 Speci cations and Framing Dimensions 3 Hearth Dimensions 4 Chase Installations 5 Freestanding Installation 5 Chimney Requirements 6 Planning...

Страница 3: ...als and increasing the risk of spreading a re do not use the replace to cook or warm food Do not obstruct or modify air inlets outlets in any manner Do not install combustible materials on any of the...

Страница 4: ...Air Gas Line Access Gas Line Access 62 1578 mm 340 mm 279 mm Fig 1 ODSHR42 Series speci cations and framing ODSHR42 Series Woodburning Fireplace A B C FP1531 hearth dimensions 9 04 djt Front Width Ba...

Страница 5: ...FP1001 fireplace setting 1 4 00 djt NOTE If the replace is a free standing unit it must be located a minimum of 10 3 m from the opening of the rebox to a com bustible structure A minimum height of 6...

Страница 6: ...ured from the hearth to the chimney exit ODSHR42 Maximum 90 27 4 m Minimum Without Elbows 14 6 4 4 m With 2 Elbows 15 6 4 7 m With 4 Elbows 21 0 6 4 m B Do not use more than 4 elbows per chimney Attac...

Страница 7: ...will be set and how the chimney system will be run Mounting the Fireplace A replace may only be mounted on the following sur faces 1 A at combustible surface 2 A raised wooden platform 3 A concrete bl...

Страница 8: ...e in a cold climate it is not required but highly recommended that you insulate replace enclosure to eliminate cold air penetration as much as possible Insulate base of replace with a noncombustible i...

Страница 9: ...CK THE END CONNECTION OF CHIMNEY SECTIONS AND ELBOWS NOTE ODSHR Series Fireplaces must use CFM Cor poration model 11CF 11 inch 2 wall chimney systems The installation procedure described in this manua...

Страница 10: ...bers Chimney Hole Size FP551b SHR 5 11 99 djt New Framing Members Existing Ceiling Joists Chimney Hole 17 445 mm 17 445 mm FP551b Fig 13 Typical frame for ceiling chimney hole Fig 12 Ceiling chimney h...

Страница 11: ...re place are noncombustible Four 4 nailing anges are supplied with the replace found on the replace hearth To level the box and secure it rmly in place remove the nailing anges from the hearth and ins...

Страница 12: ...o chimney pipe for ceiling thickness up to 8 203 mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 203 mm adjust ments must be made in framing to assure that...

Страница 13: ...ize of roof hole There must be a 2 51 mm air space between out ermost portion of chimney sections and any adjacent combustible surfaces Combustible surfaces include burnable materials such as ceiling...

Страница 14: ...djt Air Space Clearances Combustible framing material MUST NOT pen etrate AIR SPACE shaded areas Standoff 2 Air Space to Sides Firestop Front View Side View Wall Shield Air Space to Back Air Space to...

Страница 15: ...ff Noncombustible Material Surround Face Fireplace Opening Noncombustible Facing Material Must be sealed with non combustible material Ledge Bracket Finished Wall 2 x 4 Stud Finished Wall Must be seal...

Страница 16: ...ensions FP838 Minimum Wall Clearances WITH Noncombustible Surround Facing WITHOUT Noncombustible Surround Facing Minimum Hearth Extension Dimensions for On Site Construction 12 20 12 66 Seal cracks be...

Страница 17: ...acent combustible side walls and hearth extension dimensions FP1171 sealing detail 12 20 01 djt Wall Covering 2 x 4 Header Do Not Notch at Ledge Brackets Fig 20 Hearth Extension Hearth Extension Insul...

Страница 18: ...place Surround and Wall Materials with Noncombustible Material Noncombustible Decorative Cover ing Majestic Safety Strips Must be Overlapped 1 2 Min Seal Crack Between Fire place and Hearth Exten sion...

Страница 19: ...djt 1 2 5 7 6 4 3 12 11 8 10 9a b 13 Ref Description Part Number 1 Damper Blade 3990185 2 Damper Handle 20001418 3 Screen Rail 20002262 4 Screen Rod 20002222 5 Screen two per replace 20002223 6 Scree...

Страница 20: ...ustion in the rebox This accessory must be installed before replace is installed Located on the oor in front of replace to protect the oor from heat hot embers ashes etc Used to patch cracks in hearth...

Страница 21: ...se with CF11 pipe RLTCF11L 11 ue 11CF1 1 long 11CF18 1 long 11CF3 3 long 11CF4 4 long 11CF30 2 11 30 ue S20BR BT BW S20UB Upper Baf e 20002673 FS2100 HT Contact the CFM Corporation with questions con...

Страница 22: ...22 ODSHR Outdoor Woodburning Fireplace 20002264...

Страница 23: ...y is extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the in stallation instruction...

Страница 24: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: