background image

4

UVDR Series Unvented Gas Fireplaces

20007469

Locating the Fireplace

Figure 2 shows some of the many ways your fireplace 
may be installed. Consider the traffic pattern in your 
room and the location of doors and windows. Moving 
air from ceiling fans, open doors and hot air grilles may 
cause the flames to soot. If a disturbance is found that 
effects the flames, it must be eliminated by turning off 
the ceiling fan, closing the door or closing or moving 
the hot air register. A corner location may be best where 
space is limited.
Your fireplace weighs no more than some of your fine 
furniture. If the fireplace is located near a load bear-
ing wall, additional supports to the foundation will not 
be necessary. HEAVY FACINGS SUCH AS BRICK, 
STONE, ETC., MAY REQUIRE ADDITIONAL FOUNDA-
TION SUPPORT.

ALTHOUGH THIS UNIT MAY BE INSTALLED ON 
COMBUSTIBLE SURFACES, IT MUST NOT BE IN-
STALLED ON CARPET OR VINYL.

Room Divider

Partial Room

Projection

Full Room

Projection

Flush

Corner

T224

place fireplace

2/04

T224

Fig. 2

  Locating the fireplace.

Gas Line

The gas line must be installed before framing in the fire-
place by a licensed gas line installer.

Drafts

Do not locate the fireplace in high traffic areas or areas 
exposed to high drafts and winds. Locate the fireplace 
away from furniture and draperies.

Fireplace Clearances

The fireplace may be placed directly on a combustible 
floor, against a combustible wall at marked clearances 
or on a raised wooden platform.

If the fireplace is to be installed on a raised wooden 
platform, the platform must be a continuous level sur-
face. The fireplace must be secured in place so it can-
not shift positions. The nailing flanges on the sides of 
the firebox make securing it to the framing easy. They 
were designed to allow the installation of 1/2” wallboard 
or plywood flush with the face of the fireplace.
Only the header (Fig. 1) may rest on the standoffs on 
top of the firebox.
When the fireplace is installed over carpeting, vinyl, tile 
or any combustible material other than wood flooring, it 
must be installed on a metal or wood panel extending 
its full width and depth. Alternatively, the carpeting, vinyl 
tile, etc., may be removed from beneath the fireplace 
before installing. COMBUSTIBLE MATERIALS MUST 
NOT BE INSTALLED OVER OR TOUCH ANY BLACK 
PAINTED SURFACE. DO NOT BLOCK HEAT CIRCU-
LATING AIR OUTLETS. DOING SO MAY RESULT IN 
POTENTIAL FIRE HAZARD.

Clearances

To ensure a safe installation the following instructions 
must be carefully observed.

1.  Sidewall Clearances: 

 Clearances from the side of 

the fireplace opening to any combustible wall should 
not be less than 5”. (Fig. 3a)

2.  Ceiling Clearances:

  The ceiling height should not 

be less than 42” from the top of the fireplace open-
ing.

3.  Mantel Clearances:

a.  If the fireplace has no mantelpiece, then the heat 

resistant material must extend upwards a dis-
tance of at least 9

¹⁄₂

" from the fireplace opening. 

A mantel projection must be a minimum of 24” 
above the top fireplace opening if a canopy is not 
installed. (Fig. 3b)

b.  Noncombustible materials used in this installation 

such as slate, marble, tile, etc. must be at least  
1/2" thick. Do not install a combustible material 
behind sheet metal. Failure to use noncombus-
tible materials above the opening as specified 
in these instructions may cause damage to the 
materials used and create a fire hazard.

c.  A heat reducing canopy is shipped with the 

fireplace. Use of this canopy is optional in order 
to reduce mantel heights as shown in Figure 3d.  
If the canopy is installed, a combustible mantel 
piece may project 2" from the wall at 6

¹⁄₂

" above 

the fireplace opening. A 6" mantel projection at 
13" above the fireplace opening and a 10" projec-
tion at 22" above the opening. (Fig. 3a and 3d)  

  To install the optional canopy, remove the four (4) 

screws supplied with a Phillips screwdriver. Two (2) 

Installation Instructions

Содержание FireStage UVDR36C

Страница 1: ...i e building inspectors re marshals etc should be consulted before installation to determine the need to obtain a permit When installing the Blower Kit it is neces sary to bring the power source to t...

Страница 2: ...nstallation 8 UVDR36C Installation 8 UVDR42C Installation 8 Install Optional Outside Air Kit 9 Replacement Parts 11 Accessories 12 Servicing 12 Warranty 15 Table of Contents UVDR36C UVDR42C Certi ed T...

Страница 3: ...E D B A 6 78984 ADF36 42C SPECS 2 04 Fireplace Dimensions Fig 1a UVDR36 42C speci cations and framing dimensions 1 2 Clearance to Combustibles not Required at this Point 1 2 Clear ance to Combustibles...

Страница 4: ...ace of the replace Only the header Fig 1 may rest on the standoffs on top of the rebox When the replace is installed over carpeting vinyl tile or any combustible material other than wood ooring it mus...

Страница 5: ...ed hearth effect This can be done by adding a small platform to achieve the desired height NOTE Refer to Pre wiring the Junction Box and Electri cal Service on Page 7 Step 2 Install the Firebox Instal...

Страница 6: ...Instal lations The insulation and sealing of the enclosure around the replace is very important in cold climates If the en closure is insulated and sealed properly you can avoid future cold air probl...

Страница 7: ...f the rebox opening where facing materials such as brick or stone are used on the face of the rebox It acts as a support restop It should be attached to the face of the replace with screws and sealed...

Страница 8: ...ck from the replace and carefully place it to the side to prevent damage Use a at blade screwdriver to gently lift up the front edge of the brick then pull forward to remove Step 4 Locate the blower a...

Страница 9: ...lar to duct termina tion This will provide the least restriction to air ow No more than four 4 90 elbows can be used Duct run may be horizontal vertical inclined or any combina tion of these Fig 12 Yo...

Страница 10: ...ain cap 7 6 00 djt Caulking Duct Ter mination Rain Cap Wall FP1061 Fig 15 Caulk and install duct termination rain cap in place Operating Precautions and Instructions Operation is automatic A slight ne...

Страница 11: ...ireplaces Description UVDR36C UVDR42C 1 Firescreen Rod 2 per replace 68403 65864 2 Firescreeen w Rings 2 per replace 66146 62197 3 Screen Retainer 4 per replace 62222 62222 4 Black Canopy 68779 69554...

Страница 12: ...urnish contact CFM Corporation 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Servicing Repair and replacement work should only be done by a quali ed service person Always shut off the gas supply...

Страница 13: ...13 UVDR Series Unvented Gas Fireplaces 20007469...

Страница 14: ...14 UVDR Series Unvented Gas Fireplaces 20007469...

Страница 15: ...ction the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this...

Страница 16: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: