DV360/580 Series Direct Vent Gas Fireplace

20010667

Installation & Operating Instructions

This gas appliance should be installed by a qualified installer in 
accordance with local building codes and with current 

CSA-

B149.1

 Installation codes for Gas Burning Appliances and 

Equipment.  If the unit is being installed in a mobile home, the 
installation should comply with the current 

CAN/CSA Z 240.4

 

code. For U.S.A Installations follow local codes and/or the cur-
rent 

National Fuel Gas Code. ANSI Z223.1/NFPA 54.

In the Commonwealth of Massachusetts, all gas fittings and 
installation of this appliance shall be done by a licensed 
gas fitter or licensed plumber.
FOR SAFE INSTALLATION AND OPERATION PLEASE 
NOTE THE FOLLOWING:

1 .  This fireplace gives off high temperatures and should be 

located out of high traffic areas and away from furniture and 
draperies.

2.   Children and adults should be alerted to the hazards of the 

high surface temperatures of this fireplace and should stay 
away to avoid burns or ignition of clothing.

3.   Children should be carefully supervised when in the same 

room as your fireplace.

4.   Under no circumstances should this fireplace be modified. 

Parts removed for servicing should be replaced prior to 
operating this fireplace again.

5.  Installation and any repairs to this fireplace must be per-

formed by a qualified installer, service agency or gas sup-
plier. A professional service person should be contacted to 
inspect this fireplace annually. Make it a practice to have 
all of your gas fireplaces checked annually. More frequent 
cleaning may be required due to excess lint and dust from 
carpeting, bedding material, etc.

6.  Control compartments, burners and air passages in this fire-

place should be kept clean and free of dust and lint. Make 
sure the gas valve and pilot light are turned off before you 
attempt to clean this fireplace.

7.  The venting system (chimney) of this fireplace should be 

checked at least once a year and if needed your venting 
system should be cleaned.

8.  Keep the area around your fireplace clear of combustible 

materials, gasoline and other flammable vapor and liquids. 
This fireplace should not be used as a drying rack for cloth-
ing, nor should Christmas stocking or decorations be hung in 
the area of it.

9.  Under no circumstances should any solid fuels (wood, coal, 

paper or cardboard etc.) be used in this fireplace.

10. The flow of combustion and ventilation air must not be ob-

structed in any way. 

11. When fireplace is installed directly on carpeting, vinyl tile 

or any combustible material other than wood, this fireplace 
must be installed on a metal or wood panel extending the full 
width and depth of the fireplace.

12. This fireplace requires adequate ventilation and combustion 

air to operate properly.

13. This fireplace must not be connected to a chimney flue serv-

ing a separate solid fuel burning fireplace.

14. When the fireplace is not in use it is recommended that the 

gas valve be left in the OFF position.

Proposition 65 Warning:

 Fuels used in gas, woodburning or 

oil fired appliances, and the products of combustion of such 
fuels, contain chemicals known to the State of California to 
cause cancer, birth defects and other reproductive harm.
California Health & Safety Code Sec. 25249.6

This appliance may be installed in an aftermarket 
permanently located, manufactured home or mobile 
home, where not prohibited by local codes.
This appliance is only for use with the type of gas 
indi-cated on the rating plate. This appliance is not 
convertible for use with other gases, unless a certi-
fied kit is used.

IMPORTANT:

PLEASE READ THE FOLLOWING CAREFULLY

Remove any plastic from trim parts before turning the 
fireplace ON.
It is normal for fireplaces fabricated of steel to give off 
some expansion and/or contraction noises during the 
start up or cool down cycle. Similar noises are found 
with your furnace heat exchanger or car engine.  It is 
not unusual for your CFM Corporation gas fireplace to 
give off some odor the first time it is burned. This is due 
to the manufacturing process.

Please ensure that your room is well ventilated

-open all windows.

It is recommended that you burn your fireplace for at 
least ten (10) hours the first time you use it. If the op-
tional fan kit has been installed, place the fan switch in 
the “OFF” position during this time.

Y

E

A

B

C

D

F

Y

B

X

LU584-1

Locating unit

2/4/99   djt

Locating Your Fireplace

LU584-1

A) Flat on wall  

B) Cross corner 

C)  **Island

D) *Room divider  E) *Flat on wall corner 

F)   Chase installation

Y) 6” minimum

Note (Fig. 1):

  

** Island (C) and Room Divider (D) installation is possible as long as 
the horizontal portion of the vent system (X) does not exceed 20’ (6 m).  
See details in Venting Section.
*  When you install your fireplace in(D) Room divider or (E) Flat on wall 
corner positions (Y), a minimum of 6“ (152 mm) clearance must be 
maintained from the perpendicular wall and the front of the fireplace.

Fig. 1

  Locating gas fireplace.

WARNING: Check with your electronics manufac-
turer before installing a television or other electronic 
device above this fireplace.

Содержание DV580

Страница 1: ...any appliance Do not touch any electric switch do not sue any phone in your building Immediately call your gas supplier from your neighbor s phone Follow the gas supplier s instructions If you cannot...

Страница 2: ...cal Sidewall Application Installation 16 Below Grade Installation 20 Vertical Through the Roof Application Installation 20 Venting Components 23 Operating Instructions Glass Information 24 Louvre Remo...

Страница 3: ...be ob structed in any way 11 When replace is installed directly on carpeting vinyl tile or any combustible material other than wood this replace must be installed on a metal or wood panel extending t...

Страница 4: ...ensions Ref DV360 DV580 A 41 1041 mm 47 1194 mm B 37 940 mm 41 1048 mm C 36 914 mm 42 1067 mm D 24 622 mm 28 724 mm E 7 178 mm 7 178 mm F 6 152 mm 6 152 mm G 1 32 mm 1 32 mm H 19 489 mm 23 591 mm I 5...

Страница 5: ...and framing dimensions Ref DV360 DV580 A 41 1041 mm 47 1194 mm B 37 940 mm 41 1048 mm C 36 914 mm 42 1067 mm D 24 622 mm 28 724 mm E 7 178 mm 7 178 mm F 6 152 mm 6 152 mm G 1 32 mm 1 32 mm H 19 489 m...

Страница 6: ...01 sta Maintain minimum 3 4 19 mm clear ance to combustibles Louvre Assembly top Top of Combustion Chamber CFM146 Bottom of Door Trim Mantel Chart Mantel Shelf Mantel from Top Ref or Breast Plate Ref...

Страница 7: ...ded over the edges of the face of the replace Do not cover the window frame assembly any vent louvre assembly top or louvre assembly bottom If a Trim Kit is to be installed brick and tile will have to...

Страница 8: ...not use an open ame for leak testing The replace valve must not be subjected to any test pressures exceeding 1 2 psi Isolate or disconnect this or any other gas appliance control from the gas line wh...

Страница 9: ...f the socket as sembly 6 Connect the white wire of the power line to the chrome screw of the socket assembly 7 Connect the ground wire of the supply line to the green screw of the socket assembly 8 Re...

Страница 10: ...e sure not to damage any gasket material FP1030 Outer Collar Adapter Flue Pipe 2 16 00 djt Outer Collar Adapter Flue Pipe Remove Screws 5 Remove Screws 5 FP1030 Fig 11 Remove screws from outer collar...

Страница 11: ...g which incorporates the use of ex venting shall have an inclining slope from the unit of 1 25 mm per 24 610 mm There must not be any obstruction such as bushes gar den sheds fences decks or utility b...

Страница 12: ...arance to service regulator vent outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Bt...

Страница 13: ...gh Temperature Sealant Hose Clamp FP1471 Fig 17 Apply high temperature sealant to 4 and 7 pipes Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with combustibl...

Страница 14: ...the point of this intersection draw a vertical line to the bottom of the graph 3 Select the indicated dimension and position the replace in accordance with same EXAMPLE A If the vertical dimension fr...

Страница 15: ...Wall 7 190 mm Fireplace Hearth VO584 100 Fig 22 Locate vent opening on wall ZCS101 Zero Clearance Sleeve 3 11 99 djt Adjustable Zero Clearance Sleeve Max Length 12 305 mm 8 Screws 2 Firestop 8 Screws...

Страница 16: ...n limitations as to vent con gurations apply and must be strictly adhered to The Vent Graph showing the relationship between ver tical and horizontal side wall venting will help to deter mine the vari...

Страница 17: ...mum horizontal run with no rise 7 6 2 3m A B A B 17 Max 5 2m FP1178 Fig 29 Horizontal run reduction V584 201 Horizontal Run 2 99 djt A 10 3 m 7 2 1 m 8 2 4 m V584 201 B Fig 30 Maximum vent run with el...

Страница 18: ...ess and cut zero clearance sleeve parts to proper length MAXIMUM 12 305 mm Assemble sleeve and attach to restop with 8 sheet metal screws supplied Install restop assembly Fig 33 Zero clearance sleeve...

Страница 19: ...springs on the 4 ex vent pipe When installing the spacer springs around the 4 pipe stretch the spring to approximately 15 381 mm wrap the spring around the pipe and interlock the ends of the spacer sp...

Страница 20: ...ow Well Gravel Drain BG402a Fig 38 Below grade installation Zero Clearance Sleeve if required A minimum of 24 610 mm vertical pipe must be installed when using the 7TDVSNORK Kit 24 610mm Minimum Screw...

Страница 21: ...Attic Insulation Shield 7DVAIS into position and secure Fig 42 7 Install roof support Fig 43 and roof ashing making sure upper ange is below the shingles Fig 45 8 Install appropriate pipe sections unt...

Страница 22: ...rt apps Typical Roof Support Application Typical Ceiling Support Application FP1184 Fig 43 Venting supports Min 2 610 mm FP1185 Fig 44 Minimum termination to roof clearance TWL101a Twist Lock Pipe 2 8...

Страница 23: ...Termination Kit Starter Kit Model 7TDVSKV Vertical Venting for 7TDVSKV A order 1 12 to 6 12 roof pitch for 7TDVSKV B order 7 12 to 12 12 roof pitch for 7TDVSKV F order at roof Starter Kit for Below Gr...

Страница 24: ...dically During start up condensation which is normal forms on the inside of the glass and causes lint dust and other air borne particles to cling to the glass surface Also initial paint curing may dep...

Страница 25: ...0677 Log Overlay 20010674 NOTE Refer to Figure 49 for bracket and bend loca tions 1 Place the log front right Hold the log with the pointed end toward the left Place on top of burner toward the right...

Страница 26: ...he rear log bracket and the left side of the burner Fig 49 Set the log on the rear log bracket The notch on the right side will go over the pilot Swing the left end of the log toward the front until i...

Страница 27: ...r placement Log Front Center E11 DV580 Refer to Figure 51 1 Place rear log E8 on rear bracket ensure the notch on the left end is centered on the left side of rear bracket so it will not move from sid...

Страница 28: ...ll valve LO H I FP390 FLAME ADJUSTMENT KNOB 11 21 96 Turn counterclockwise to increase flame height Turn clockwise to decrease flame height Fig 57 Flame adjustment knob for SIT valve Flame Characteris...

Страница 29: ...29 DV360 580 Series Direct Vent Gas Fireplace 20010667 Yellow Flame Red Glow Fig 59 Correct burner ame apperance for DV360 and DV580 Yellow Flame Red Glow LG396 DV360 DV580 LG444...

Страница 30: ...w these instruc tions exactly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF...

Страница 31: ...try to repair it call a quali ed service technician Force or attempting repair may result in a re or explosion D Do not use this appliance if any part has been under water Immediately call a quali ed...

Страница 32: ...indicating the transmitter will now work with the re ceiver valve If the switch continues in the REMOTE position the transmitter will now control the main valve ame modulation level and fan control 7...

Страница 33: ...1 Remove cover on the backside of the transmitter Install 3 AAA batteries as shown and reattach cover 2 Once steps 1 3 in OPERATION are completed receiver valve and transmitter are now ready Press any...

Страница 34: ...etting is above room temperature on the transmitter does the main valve and fan turn on If the setting is below room temperature on the transmitter does the main valve and fan turn off Turn pilotstat...

Страница 35: ...te wait period Cycle switch once and leave in remote Press any key on transmit ter for recognition operation Local Path Move switch from local to remote Press any key on transmitter Move switch back t...

Страница 36: ...ll Wiring Connections Replace Piezo Ignitor Supply Line Hooked Up Shutoff Valve Open Pilot Stays Lit For Air In The Lines Thermopile Needs A Min 325mv Adjust Pilot Flame Height All Wiring Connections...

Страница 37: ...ock not supplied must be used to conduct this test 3 Pilot burning no gas to A Wall switch or wires Check wall switch and wires for proper connections main burner defective Jumper wire accross termina...

Страница 38: ...URES ARE GOOD AND PILOT BURNER ORIFICE IS NOT BLOCKED CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL CHECK FOR 24VAC ACROSS PV MVPV TERMINALS ON MODULE IF VOLTAGE IS OKA...

Страница 39: ...ame Continuously Monitored Heating Cycle Complete LED OFF NO YES NO NO YES Abnormal Operation 5 sec Inter Trial Delay LED Steady Flash Lockout Flame detected out of sequence Reset by interrupting ON O...

Страница 40: ...ve and discard the three 3 pressure regulator mounting screws A pressure regulator tower B and the spring and diaphragm assembly C Fig 64 FC107 SIT820 valve conversion 10 03 A B C OFF P I L O T O N FC...

Страница 41: ...Secure the bracket gasket as sembly using the screw removed earlier Fig 67a LP Bracket Gas ket Assembly in place for use with LP Gas remove for use with Natu ral Gas Screw CO132 Fig 67a LP bracket ga...

Страница 42: ...reviously installed CAUTION Logs may be hot 3 Remove and replace plug on lower right hand side of the valve Red for LP and blue for NG Fig 74 4 Remove motor top cap Depress and turn center plunger unt...

Страница 43: ...g 71 5 Replace only the rear air shutters Natural Gas Rear air shutter fully open Front air shutter fully open LP Rear air shutter fully open Front air shutter fully open 6 Re install manifold to burn...

Страница 44: ...llivolt gas valve Most of these components may require only an oc casional checkup and cleaning and some may require adjustment If repair is necessary it should be per formed by a quali ed technician...

Страница 45: ...b 30 31 27 32 28 29 33 34 35a b 36 37 38 39 40 41 42 46 47 48 49 50 51 52 53 54 55 56 LOCAL REMOTE O N PILOT OFF L E D 57a b 58 60a b 63 59a b 61 62 64 65a b 66 67 68 69 70a HI LO 71a b 72a b 10667 D...

Страница 46: ...9a Ceramic Panel Left Side 10007995 9b Ceramic Panel Right Side 10007996 10 Glass with Gasket 20002369 11 Gasket Glass 10000992 12 Door Frame Assy 10007538 12a Door Assy 20002622 13 Clamp Frame Window...

Страница 47: ...t 10007518 47 Plate Relief w Gasket Assembly Burner Tray 10004192 48 Firestop 52523 52523 49 Zero Clearance Sleeve 54623 54623 50 Plate Cover Air Inlet Ass y 10002766 20002461 51 Gasket Plate Air Inle...

Страница 48: ...nsing Electrode w Cable EN EP not shown 57885 57885 74 Wire Harness Honeywell EN EP not shown 57899 57899 75 Tubing 3 8 OD Aluminum 20010564 76 Nut 3 8 ID Brass Compression 7523136 77 Wire Harness EN...

Страница 49: ...s Option B The speed control can be installed in an electrical box at normal wall switch height for conve nient access 4 The power supply may be connected in 2 ways Method A Route the 6 1 8m lead tted...

Страница 50: ...02 rear ceramic support 2 23 99 djt Rear Ceramic Panel Back of Firebox Burner Rear Log Support H102 Fig 83 Rear ceramic panel placement Decorative Bay Windows The bay window kit is available for the D...

Страница 51: ...manesque Arch 41DVARFKB Black 41DVARFKR Rustic Bronze 41DVARFKS Pewter Romanesque Square 41DVSRFKB Black 41DVSRFKR Rustic Bronze 41DVSRFKS Pewter Marquette Arch 41DVAMTKB Black 41DVAMTKR Rustic Bronze...

Страница 52: ...er service agency or gas supplier A professional service person should be contacted to inspect replace annually More frequent cleaning may be required due to excess lint and dust from carpeting beddin...

Страница 53: ...gas It is convertible to natural gas by the instal lation of a color coded conversion screw To insert the conversion screw refer to the instructions and diagrams in the Honeywell Installation Instruc...

Страница 54: ...54 DV360 580 Series Direct Vent Gas Fireplace 20010667...

Страница 55: ...If upon inspection the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provi...

Страница 56: ...53 83 84 64 DV360EN 53 82 83 64 DV360EP 53 83 84 64 DV360RFN 53 82 83 64 DV360RFP 53 83 84 64 DV580RN 51 1 82 83 64 DV580RP 51 1 83 84 64 DV580EN 51 1 82 83 64 DV580EP 51 1 83 84 64 DV580RFN 51 1 82 8...

Отзывы: