4.3.2 Profile B: CBA Blind + Buttons
Drive blind | Adjust slats | additional switches
Casambi profile name
Fixture Id
Control element name
Function
Control element type
CBA Blind + Buttons
17802
Position
Position
Slider (0% - 100%)
Angle
Slat angle
Slider (0% - 100%)
Up
Single drive Up
ON/OFF Toggle
Down
Single drive Down
ON/OFF Toggle
Angle
Slat angle
Push Button
Profile parameter
Parameter Casambi
Description parameter
Value
Default | Notes
Drive Time
Drive time for blind operation
0 … 255s (seconds)
60s default
Angle Time
Drive time for slat adjustment
0 ... 65535ms (milliseconds)
2000ms default
Swap Controls Up/
Down
Logical invert of drive direction
No | Yes
Reverse driving direction
Push Button mode
Behavior of the pushbutton inputs
Description see 5.3
Operating elements in the APP