2.4 Regulations for operation with
fireplaces
Observe the current rules from the German
Federation of Chimney Sweeps (Evaluation
criteria for the joint operation of fireplaces –
domestic ventilation – extractor hoods) as
well as other pertinent regulations and guide-
lines.
The ventilation unit may only be installed
in rooms, apartments or living units of a
comparable size with air-ventilated fire-
places, if:
●
the evaluation criteria drawn up by the
responsible, regional master chimney
sweep are met,
●
a parallel operation of air-ventilated fire-
places for liquid or gaseous fuels and the
air-extracting equipment can be prevented,
or
●
the extraction of exhaust gas from the air-
ventilated fireplaces is monitored by spe-
cial safety equipment. The ventilation unit
or the fireplaces must be switched off if the
equipment is triggered.
Only operate the ventilation system at
the same time as an air-ventilated
fireplace if using differential pressure
control.
NOTICE
The ventilation unit may not be installed in
living units with air-ventilated fireplaces
that are connected to exhaust gas sys-
tems, which themselves have multiple
connections. Combustion air ducts must
be capable of being blocked. In the case
of solid fuel fireplaces, any blocking de-
vice may only be operated manually.