9 Commissioning
43
+
ventilation
mode/ventila-
tion level.
If no button is
pressed for
120 seconds
+
in service
mode, service
mode is auto-
matically ex-
ited.
9.2 RLS 45 O service menu
Bold
Factory settings
LED flashes quickly
LED flashes slowly
LEDs
Parameters
Set value / Bin-
ary display*
Setting / description
Device type on RLS
(Fan1/Fan2)
1
2
PP 45
PPB 30 O
The type family, which is con-
nected to the Fan1/Fan2 fan in-
terface, is selected here.
Notice: Only single-type PP 45
or PPB 30 unit combinations
are permitted at the fan inter-
face!
Number of device pairs /
devices on RLS (Fan1/
Fan2)
1
2
3
4
5
1 PP 45 or 1 PPB 30 unit pair
2 PP 45 or 2 PPB 30 unit pairs
3 PP 45 or 3 PPB 30 unit pairs
Odd number 3 PP 45 units
Odd number 5 PP 45 units
The number of units connected
to the fan interface (Fan1/Fan2)
is selected here.
Ventilation levels
1
2
Ventilation level “0” possible
Ventilation level “0” blocked
If ventilation level “0” is set to
blocked, the ventilation units
cannot be switched off at this
control. The units then run with
at least ventilation level 1.
* The service menu items are set according to the 3-digit binary code 111, e.g. the adjuster "5" is dis-
played as 101 → Upper and lower LEDs light up.
Bold
Factory settings
LED flashes quickly
LED flashes slowly
Содержание PPB 30 K
Страница 3: ...Steuerungskonzept PPB 30 3 Steuerungskonzept PPB 30...
Страница 4: ...Steuerungskonzept PP 45 RC PPB 30 RC Funk 4 Steuerungskonzept PP 45 RC PPB 30 RC Funk...
Страница 29: ...PPB 30 control concept 29 PPB 30 control concept...
Страница 30: ...PP 45 RC PPB 30 RC wireless control concept 30 PP 45 RC PPB 30 RC wireless control concept...
Страница 53: ...Concept de commande PPB 30 53 Concept de commande PPB 30...
Страница 54: ...Concept de commande PP 45 RC PPB 30 RC radio 54 Concept de commande PP 45 RC PPB 30 RC radio...
Страница 95: ...Produktdatenbl tter Product data sheets Fiches techniques du produit 95 PPB 30 O...