3. Safety instructions and warnings │ UK 

 

15 

any flammable materials, liquids or gases 

near the fan, which may ignite in the event of 

heat or sparks and catch fire. 

 

Explosive gases and dusts may 

ignite and cause serious explosions 

or fire.

 Never use fan unit in an 

explosive atmosphere (risk of explosion). 

 

Risk from operating in single air 

extraction systems in accordance 

with DIN 18017-3

. Fan does not satisfy 

the DIN 18017-3 standard. Do not use fan in 

systems in accordance with DIN 18017-3. 

 

Risk to health from chemicals or 

aggressive gases/vapours. 

Chemicals 

or aggressive gases/vapours may harm 

health, especially if they are distributed 

throughout the rooms by the fan. Never use 

fan to convey chemicals or aggressive 

gases/vapours. 

 

 

Read all the safety instructions. 

 

Risks for children and 

people with reduced physical, 

sensory or mental capabilities or a lack of 

knowledge. 

Fan may only be installed, 

commissioned, cleaned and maintained by 

people who can safely recognise and avoid 

the risks associated with this work.

 

 

Danger of injury due to suction from 

fan and rotating impeller.

 Hair, 

clothing, jewellery etc. may be pulled into the 

fan if you get too close to it. During operation 

always keep far enough away to prevent this 

from happening. 

 

Danger of injury if foreign bodies are 

inserted into the unit. 

Do not insert 

any objects in the unit. 

 
 
 
 
 
 

A fan that is not installed correctly 

may result in non-intended operation 

or impermissible operation. 

Operation 

is only permitted with a correct installation 

position (see “TOP” on unit), with mounted 

design cover and outer protective grille.  

The fan may be operated only if the protec-

tion against accidental contact with the 

impeller is guaranteed to be in accordance 

with EN 13857. 

 

Risk of injury and health risk in the 

event of changes or modifications  

or if components which are not 

permitted are used. 

The unit may only be 

operated with original components. Changes 

and modifications are not permitted and 

release the manufacturer from any guarantee 

obligations and liability, e.g. if the unit is 

drilled at a point which is not permitted. 

Danger of injury when working at 

heights.

 Use appropriate climbing aids 

(ladders). Stability should be ensured, if 

necessary have the ladders steadied by a 

2nd person. Ensure that you are standing 

securely and cannot lose your balance and 

that there is no one under the unit. 

 

Risk of death from carbon monoxide 

when operating with air-ventilated 

fireplaces. 

When operating with air-

ventilated fireplaces and in 

"air extraction" 

installation position

, a sufficient fresh air 

supply must be ensured.  The maximum 

permitted pressure difference per living unit is 

4 Pa. The consent of a professional chimney 

sweep is needed in all cases. 

 

Danger of electric shock from 

operating with the unit not fully 

mounted.

 Before taking off the  

electronics cover, shut down all supply 

circuits (switch off mains fuse), secure 

against being accidentally switched back on 

and position a visible warning sign. Only 

operate the fan when it is completely 

installed. Do not commission a damaged unit. 

Содержание AKE 100

Страница 1: ...ung Automatische Kellerentfeuchtung Mounting and operating instructions Automatic cellar dehumidification Notice de montage et mode d emploi D shumidification automatique des caves AKE 100 www maico v...

Страница 2: ...Innengitter 9 Leitungst lle 10 Au enverschlussklappe Wandst ck 11 Au enverschlussklappe Au enst ck 12 Au en Klimasensor mit Sensorverbindungskabel Inhaltsverzeichnis 1 Lieferumfang 3 2 Qualifikation...

Страница 3: ...ses Ger t ist ausschlie lich f r den h uslichen Gebrauch und hnliche Zwecke vorgesehen Das Ger t dient zur Entfeuchtung von Kellern Abstell und Vorratsr umen Austellungs r umen B ros Umkleidekabinen u...

Страница 4: ...es Fl gelrad Haare Kleidung Schmuck etc k nnen in den Ventilator eingezogen werden wenn Sie sich zu nahe am Ventilator aufhalten Bei Betrieb unbedingt gen gend Abstand halten damit dies nicht passiere...

Страница 5: ...mgang mit Ver packungsmaterialien Geltende Sicherheits und Unfallverh tungsvorschriften einhalten Verpackungsmaterial au er Reichweite von Kindern aufbewahren Zuluftnachstr mung innerhalb der Wohnung...

Страница 6: ...gserfolg erreicht mit Taste 1 r cksetzbar Gleichzeitiges Blinken Ein gleichm iges Blinken von LED 1 oder LED 2 entspricht einer Betriebsart bzw Funktion Bei gleichzeitigem Blinken beider LEDs liegt ei...

Страница 7: ...chaltkontakt mehr als 10 Sekunden geschlossen ist Das manuelle L ften mit einem externen Taster entspricht der Verwendung von Taster 2 Ist ein externer Schalter angeschlossen wird das manuelle L ften...

Страница 8: ...in der Steigleitung einplanen Montagevorbereitungen wie in Kapitel 8 1 beschrieben vornehmen 8 3 Rohr 1 Kanten der Rohrinnenseite entgraten 2 Montagevorbereitungen wie in Kapitel 8 1 beschrieben vorne...

Страница 9: ...bel mit Klebeband m glichst auf Unterseite in Wanddurchbruch Wandh lse befestigen F r die Verbindung mit der Steuerelektronik werden maximal 10 cm im Ventilatorgeh use ben tigt 9 3 Geh useeinbau Venti...

Страница 10: ...rch Strom schlag Netzsicherung ausschalten ACHTUNG Ger tebesch digung bei Kurzschluss Schutzleiter und nicht ben tigte Adern isolieren 1 Im Ger t nur Einzeladern verlegen Dazu Mantel der Netzleitung a...

Страница 11: ...ttel Abdeckung 4 und Design abdeckung 3 nur mit Wasser reinigen Keine aggressiven Reinigungsmittel verwenden 1 Innenteile des Ventilators nur mit einem trockenen Tuch reinigen 2 Bei stark verunreinigt...

Страница 12: ...ng ausschalten 1 Abdeckungen entriegeln Pfeil und abnehmen 2 Elektronikabdeckung 6 entfernen 3 Rastnasen 3 Netzleitung entfernen 4 Ventilator ausbauen 14 Entsorgung Nicht in den Restm ll Das Ger t ent...

Страница 13: ...rd 8 Internal grille 9 Cable grommet 10 External shutter wall piece 11 External shutter outer piece 12 External climate sensor with sensor connection cable Table of contents 1 Scope of delivery 14 2 S...

Страница 14: ...intended for domestic use and similar purposes The unit serves to dehumidify cellars storage rooms showrooms offices changing rooms and similar rooms up to a floor area of approximately 25 m2 Operati...

Страница 15: ...ermissible operation Operation is only permitted with a correct installation position see TOP on unit with mounted design cover and outer protective grille The fan may be operated only if the protec t...

Страница 16: ...he AKE 100 is installed A room from which the air has to be extracted must be fitted with a non closable free supply air cross section of at least 150 cm e g with Maico door ventilation grille MLK 5 P...

Страница 17: ...the AKE 100 signals successful dehumidification by LED 2 blinking A reference value of 9 g m3 is set on site A new reference value can be set at any time by pushing button 1 during ongoing operation...

Страница 18: ...e manual ventilation when using an external switch 6 Environmental conditions and operating limits Permissible maximum temperature of air medium 40 C Sufficient supply air intake must be ensured durin...

Страница 19: ...ver s locking hook unlock arrow using a screwdriver 2 Remove internal climate sensor 5 3 Remove the electronics cover 6 Unlock locking hook arrow with screwdriver 4 Fit supplied sealing strip centred...

Страница 20: ...dowels 4 Push cable grommet 9 carefully out of housing and remove NOTICE Danger of short circuits and damage to the unit Water will penetrate if the power cable is incorrectly fed into the fan housin...

Страница 21: ...le cores to 9 to 10 mm 2 Electrically connect power cable to spring clip 13 according to connection wiring diagram 14 also see wiring diagram in Chapter 15 3 Check position of cable grommet 9 It must...

Страница 22: ...nd clean with water 3 Fit designer cover 3 12 Fault rectification Call on the services of a trained electrician any time there is a fault Repairs should only be carried out by a trained electrician DA...

Страница 23: ...part materials that can be recycled and in part substances that should not end up in the domestic waste Dispose of the unit once it has reached the end of its service life according to the regulation...

Страница 24: ...olet de fermeture ext rieur l ment ext rieur 12 D tecteur d atmosph re ext rieure avec c ble de raccordement du d tecteur Sommaire 1 Volume de fourniture 25 2 Qualification de l installateur sp cialis...

Страница 25: ...c blage et en toute s curit conna t les dangers de l lectricit et peut les viter 3 Utilisation conforme Cet appareil est exclusivement r serv l usage domestique et similaires L appareil sert d shumidi...

Страница 26: ...toutes les instructions de s curit Danger pour les enfants et les personnes ayant des capacit s physiques sensorielles ou psychiques r duites ou sans connaissances suffisantes L installation la mise...

Страница 27: ...e bien visible La r glementation en vigueur pour l installation lectrique p ex EN 50110 1 et notamment pour l Allemagne la norme DIN VDE 0100 et les parties correspon dantes doivent tre respect es Pr...

Страница 28: ...marre automa tiquement et un cycle de d shumidification commence p riode active L insufflation et l vacuation d air dure environ 10 minutes Le ventilateur est ensuite teint pendant 10 autres minutes...

Страница 29: ...ode manuel s arr te par actionnement r p t du bouton 2 ou automatiquement au bout de 20 minutes Le mode manuel peut galement tre command par un bouton externe voir le sch ma de branchement au chapitre...

Страница 30: ...ION Risque de court circuit et d endommagement de l appareil r sultant de la formation de condensat dans le bo tier de l a rateur Effectuer une isolation thermique des gaines d air dans les r gles de...

Страница 31: ...ection externe 1 Introduire le bo tier de la protection externe 10 dans le per age de cloison la gaine murale 2 Aligner le bo tier horizontalement et marquer les orifices des chevilles 3 D poser le bo...

Страница 32: ...r plus facilement le c ble secteur et de poser correctement le cache lectronique 6 Poser le manchon de c ble 9 dans les r gles de l art tanch ifier sur site si besoin est 5 Introduire le manchon de c...

Страница 33: ...re ce qu elle ne bloque pas le montage du d tecteur d atmosph re int rieure ATTENTION Risque de court circuit et d en dommagement de l appareil P n tration d humidit en cas de mauvais positionnement d...

Страница 34: ...s lectriciens qualifi s DANGER Danger de mort par lectrocution En cas d intervention sur le branchement lectrique d connecter le fusible secteur Les deux LED son teintes Pas de tension du secteur Cont...

Страница 35: ...es substances recyclables ainsi que des substances qui ne doivent pas tre m l es aux ordures m nag res L appareil hors d usage doit tre limin conform ment aux prescriptions en vigueur dans votre pays...

Страница 36: ...s L ften Optional button for manual ventilation Bouton en option pour la ventilation manuelle Z Anschluss f r optionales Zuluftelement z B ECA 11 E Connection for optional supply air element e g ECA 1...

Отзывы: