12 Cleaning and maintenance

13

Adjustment hints

Ti interval operation:

: The unit is switched off

during the interval time. Then, the unit runs for
10 minutes with nominal ventilation (full load
level) V2 or in the set level 40 m³/h, 60 m³/h or
100 m³/h.

• Settings menu is automatically exited after 60

seconds without pushing buttons.

11.1.3 ER-AH automatic humidity function

 The control continuously checks the humid-

ity during permanent base load. If the unit is
operated without permanent base load, the
unit starts at reduced speed (base load 20 m³/
h) every 2 minutes for 30 seconds and meas-
ures the relative humidity.

 The start delay is deactivated with the auto-

matic humidity function turned on.

Once the unit is installed, it adjusts to the room
humidity prevailing at that time (relative humidity).
This humidity value is saved as the first reference
value. The reference value does not have to be
specified manually.
If the relative humidity falls below the reference
value during operation, the newly established ref-
erence value is saved. The lowest possible refer-
ence value is 45 % relative humidity.

If the room humidity rises quickly

, the unit is

adjusted upwards in a continuously variable man-
ner (depending on the humidity) to match the hu-
midity. The maximum flow rate at 100 % r. h. is
40 m³/h, 60 m³/h or 100 m³/h, depending on the
setting of V2.

If the humidity falls below the reference value

,

overrun operation mode starts with the set over-
run time. The current reference value is then
saved.

If the humidity does not fall below the refer-
ence value within 60 minutes,

 the unit switches

to the set overrun mode and then switches off.
In the case of 

Light on,

 the unit starts up. If the

light is switched off, the unit continues to run until
the remaining overrun time has passed. The auto-
matic humidity function is then assigned max-
imum priority again and controls the unit as de-
scribed above.

Notes

• ER EC units can also be operated using a light

switch during operation with automatic humidity
function.

• The interval operation is deactivated during the

humidity operating mode.

• Overrun time:

• A set overrun time of 0 minutes is only valid

for manual function with a light switch.

• For operation with automatic humidity func-

tion, the minimum overrun time is 3 minutes.

• For settings > 0 minutes, the overrun time is

the same for manual (light switch) and humid-
ity operating modes.

• Volumetric flows that can be set

V1: 20, 30, 40 m³/h
V2: 40, 60, 100 m³/h
see 

Changing setting parameters [

}

 12]

11.1.4 ER AB motion detector function

If a movement is detected/recognised, the unit
switches to full load level automatically without a
start delay.
If no movement is registered, the overrun delay
starts. Then, the unit switches off.

12 Cleaning and maintenance

12.1 Maintaining the unit

The unit is practically maintenance-free. Only the
air filter needs replacing every 6 months at the
latest, depending on the degree of soiling.

NOTICE The unit will be damaged if incorrect
cleaning agent is used.

Do not use aggressive cleaning agents.

1. Clean cover with dry cloth only.

2. If the cover is very dirty, remove it and clean

with water.

12.2 Filter change

A Activation button

B Bar indicator

17 Air filter

Содержание 0084.0361

Страница 1: ...Installation and operating instructions ER EC covers for ER EC flush surface mounted exhaust air systems according DIN 18017 3 ER A ER AK ER AH ER AB www maico ventilatoren com...

Страница 2: ...3 Technical data table 9 8 4 Storage 9 9 Fan insert 10 9 1 Installation of fan insert 10 9 2 Commissioning 10 9 3 Removing fan insert 11 10 Installing the cover ER A ER AK ER AH ER AB 11 11 Operating...

Страница 3: ...s ER A Article no 0084 0361 Standard cover Lower and upper part of cover TimeStrip on title page of these instructions ER AK Article no 0084 0362 Comfort cover Lower and upper part of cover ER AH Arti...

Страница 4: ...le page ER AK comfort cover 1 Cover upper part 4 Cover lower part with touch control unit Cover with ER AH humidity control 1 Cover upper part 5 Cover lower part with touch control unit 6 Humidity sen...

Страница 5: ...NGER Indicates a possibly hazardous situation which will result in death or serious injuries if not avoided WARNING Indicates a possibly hazardous situation which could result in death or serious inju...

Страница 6: ...f the relevant regula tions for electrical installations are not ob served Before removing the housing cover or removing the fan insert and before installing the electrics switch off all supply circui...

Страница 7: ...ble to rotate the cover by 5 to com pensate for housings which have been fitted at an angle ER AH and ER AB are barrier free products In automatic mode they switch the fan automatic ally on and off ER...

Страница 8: ...oad 20 m h 30 m h or 100 m h Full load level on off via light switch or separate switch During manual operation e g using light switch the start delay and overrun time apply Full load operation 60 m h...

Страница 9: ...ia drawn up by the respons ible regional master chimney sweep are met Parallel operation of air ventilated fireplaces for liquid or gaseous fuels and air extracting equip ment can be prevented using s...

Страница 10: ...vement of shutter When in stalled it must close automatically 5 Check that connection data matches the tech nical data on the unit rating plate 6 Plug the fan insert directly into the 3 studs with loc...

Страница 11: ...entral screw If in stalling on a wall ensure that the Maico name is on the bottom right 4 Insert air filter and fold down the upper part of the cover upper part must audibly engage 5 Run function test...

Страница 12: ...the next 6 months 11 1 2 Changing setting parameters LEDs 1 flashe s 1 2 3 4 5 V1 20 30 40 60 100 V2 20 60 30 100 40 60 100 Te 0 30 60 90 120 Ta 0 3 6 15 24 30 Ti 0 1 2 4 6 12 Additional setting valu...

Страница 13: ...ved If the humidity does not fall below the refer ence value within 60 minutes the unit switches to the set overrun mode and then switches off In the case of Light on the unit starts up If the light i...

Страница 14: ...art no 0093 0923 13 Fault rectification Fault finding and repairs only permissible when carried out by qualified electricians Fault Cause Measure Fan performance inad equate Dirty filter Replace filt...

Страница 15: ...AH and ER AB Article no 0093 0759 100x ZF EC replacement air filters filter class G2 ZRF replacement air filter for ER ZR second room connection set Article no 0093 0923 5x replacement air filters fo...

Страница 16: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Deutschland Service 49 7720 6940 info maico de D06 21_EN_DSW AS AV...

Отзывы: