MAGNUM DIGITAL CONTROLLER (MDC)- LIST OF POSSIBLE ALARMS/DESCRIPTIONS
Shut down and warning fault conditions and the displayed message are described in the following table:
No.
Events
Specification
Protection
Type
Information
on Binary
Output
Available
Description
1
AnInIOM Sd
SD
YES
Shutdown alarm configurable on the input of IG-IOM/IGS-PTM.
2
AnInIOM Wrn
WRN
YES
Warning alarm configurable on the input of IG-IOM/IGS-PTM.
3
Battery Flat
SD
YES
If the controller switches off during starting sequence due to
bad battery condition it doesn't try to start again and activates
this protection.
4
Binary Input
Configurable
YES
Configurable Warning/Shutdown alarms on the inputs of IL-NT.
5
ChrgAlternFail WRN
YES
Failure of the alternator for charging the battery.
6
EmergencyStop
SD
NO
If the input
Emergency stop
is opened shutdown is immediately
activated.
7
Engine Temp Sd
SD
NO
Water temperature is greater than
Sd Water temp
setpoint.
8
Engine Temp Wrn
WRN
YES
Water temperature is greater than
Wrn Water temp
setpoint.
9
Fgen <, >
SD
YES
The generator frequency is out of limits given by
Gen >f
and
Gen <f
setpoints.
10 Fuel Level Sd
SD
YES
Fuel level is less than
Sd Fuel Level
setpoint.
11 Fuel Level Wrn
WRN
YES
Fuel level is less than
Wrn Fuel Leve
l setpoint.
12 GCB fail
SD
NO
Failure of the generator circuit breaker.
13 Igen unbl
SD
NO
The generator current is unbalanced.
14 Low BackupBatt
WRN
NO
RTC backup battery is flat.
15 Oil Press Sd
SD
NO
Oil pressure is less than
Sd Oil press
setpoint.
16 Oil Press Wrn
WRN
YES
Oil pressure is less than
Wrn Oil press
setpoint.
17 Overload
SD
YES
The load is greater than the value given by
Overload
setpoint.
18 Overspeed
SD
YES
The protection comes active if the speed is greater than
Overspeed
setpoint.
19 ParamFail
NONE
NO
Wrong checksum of parameters. Happens typically after
downloading new firmware or changing of the parameter. The
controller stays in INIT mode. Check all parameters write at
least one new parameter.
20 PickupFault
SD
NO
Failure of the magnetic pick-up sensor for speed measurement.
21 Sd IOM fail
SD
NO
Shutdown alarm in case of lost connection to IG-IOM/IGS-PTM
module.
22 SprinklActive
WRN
NO
The protection is active if the output
Sprinkler
is closed.
23 Start failed
SD
YES
Gen-set start failed
24 Stop fail
SD
YES
Gen-set stop failed.
25 Ubat
WRN
YES
Battery voltage is out of limits given by
Batt overvolt
and
Batt
undervolt
setpoints.
26 Underspeed
SD
YES
During starting of the engine when the RPM reaches the value
of
Starting RPM
setpoint the starter is switched off and the
speed of the engine can drop under
Start RPM
again. Then the
Underspeed protection becomes active. Protection evaluation
starts 5 sec
27 Vgen <, >
SD
YES
The generator voltage is out of limits given by
Gen <V
and
Gen >V
setpoints.