40
CUSTOMER CONVENIENCE OUTLETS
The generator is equipped with four convenience outlets. The large outlets
are 240/120VAC twist-lock receptacles rated at 50A each. The smaller
outlets are 120VAC duplex receptacles rated at 20A each with ground
fault circuit interrupt (GFCI) protection. These receptacles are not routed
through the main circuit breaker. Each receptacle has its own circuit
breaker, located directly above the receptacle panel, with the breaker sized
to the maximum rating of the corresponding outlet.
Power to the outlets is available any time
the generator is running,
EVEN IF THE
MAIN CIRCUIT BREAKER IS “OFF/O”.
MAKE SURE THAT ANY EQUIPMENT
CONNECTED TO THE CONVENIENCE
OUTLETS IS TURNED OFF BEFORE
TURNING THE BREAKERS ON.
Make
sure that the voltage selector switch is in
the proper position and that the output
voltage is correct for the equipment that
is connected to the outlets. Improper
voltage may cause equipment damage or
malfunction.
Note:
When the voltage selector switch is in position for 480/277V 3Ø,
voltage at the two GFCI duplex convenience outlets is 139 volts, and the
voltage at the two twist-lock outlets is 240/139 volts. When the voltage
selector switch is in position for 208/120V 3Ø, voltage at the two twist-
lock outlets and the two GFCI duplex convenience outlets is 208/120 volts.
DERATING FOR ALTITUDE
All generator sets are subject to derating for altitude and temperature; this will reduce the available power for operation
of tools and accessories connected to the auxiliary outlets. Typical reductions in performance are 2-4% for every
1000 ft. (305 m) of elevation and 1% per 10ºF (-12ºC) increase in ambient air temperature over 72ºF (22ºC).
REMOTE START TERMINAL BLOCK
The remote start terminal block is located between the two 240/120VAC twist-lock convenience
outlets. It provides a connection for installation of a remote start switch which will allow the generator
to be started by a remote dry-contact closure switch.
Before pressing the “AUTO” button, verify the contacts on any remote switch linked to the generator
are
OPEN
. If the contacts on a remote switch are closed, the generator will crank and start when
"AUTO" is selected. Attach the switch leads to the two unused terminals on the generator’s remote
start block. For additional information on starting the generator, refer to
“Manual Starting Of The
Generator” on page 26
.
Remote
Start
Switch
Terminals