54-610 Thermatel Model TD1/TD2 Flow Level Switch
1.0
Quick Start
Unless ordered with factory calibration, the set point of
the unit must be adjusted for your application.
To calibrate, adjust the alarm set point potentiometer.
Turn the potentiometer clockwise to go out of alarm. Turn
potentiometer counterclockwise to cause the switch to go
into alarm (red LED on). Refer to the Calibration section
on page 8 for detailed procedure.
2.0
Installation
2.1
Unpacking
Unpack the instrument carefully, making sure all compo-
nents have been removed from the packing material.
Inspect all components for damage, and report any con-
cealed damage to the carrier within 24 hours.
Check the contents of the carton, making sure it agrees
with the packing slip and the purchase order. Verify that
the model number imprinted on the nameplate matches
the number on the packing slip and the purchase order.
Report any discrepancies to the factory. Check and record
the serial number for future reference when ordering parts.
Serial Number
2.2
Electrostatic Discharge (ESD)
Handling Procedure
Magnetrol’s electronic instruments are manufactured to the
highest quality standards. These instruments utilize elec-
tronic components which may be damaged by static elec-
tricity present in most work environments. The following
steps are recommended to reduce the risk of component
failure due to electrostatic discharge:
1. Ship and store circuit boards in anti-static bags. If an anti-
static bag is not available, wrap board in aluminum foil.
Do not place boards on foam packing materials.
2. Use a grounding wrist strap when installing and removing
circuit boards. A grounded workstation is also recommended.
3. Handle printed circuit boards only by the edges. Do not
touch components or connector pins.
4. Ensure that all electrical connections are completely made
and none are partial or floating. Ground all equipment to
a good, earth ground.