background image

50-606 Kotron Tip Sensitive RF Level Sensor

4

1.6.2 Vertical Mounting

As medium rises on the probe, unit will signal at a point
determined by the calibration of the unit and the dielectric
constant of the medium. In conductive media, the actua-
tion point will be at the tip of the probe over a wide range
of zero calibrations. Refer to Figure 3.

1.7

Installation Instructions

1. Thread amplifier assembly into mounting bushing

on tank using suitable pipe compound or thread
tape. Assembly may also be bolted to a flange with
a suitable gasket.

2. Tighten securely, being certain that the wrench is applied

ONLY

to the mounting nut. Refer to Figure 3.

1.8

Wiring

All power and control connections are made at the termi-
nal strip within the amplifier enclosure. 16 AWG wire is
recommended for power and control circuit.

Caution:

Observe all local electrical codes and proper wiring
procedures.

1. Make sure the power source is turned off.

2. Unscrew and remove housing cover.

3. Pull power supply and control wires through

conduit connection.

4. Connect power leads to applicable AC or DC terminals as

marked. Refer to Figure 4.

5. Connect control circuit leads to relay terminals. Refer to

Figure 4. Make sure the load to be controlled is within the
relay’s rated capacity.

6. Dress wiring to guard against interference or contact with

cover or circuit board components.

7. Prevent moisture seepage into the housing by installing an

approved seal-drain fitting in the conduit run leading to
the unit.

8. Select operating mode. Refer to Section 1.8.1, 

Operating

Mode Selection

on page 5 for detailed information. Make

sure that the operating mode jumper wire is in the correct
position for your selection. Refer to Figure 4.

Mounting nut
apply wrench here

Tank mounting
bushing

Actuation point in
conductive media

Figure 3

Vertical mounting

Operating 
Mode
Jumper
Wire

Terminal Strip

AC Power
Supply
Connections

Control

Connections

DC Power 
Supply
Connections

Zero
Adjustment

GND AC

AC

RELAY +24v

LL

CM

HL

GND

Figure 4

Terminal connections

Содержание STI Kotron

Страница 1: ...RF Level Sensor Kotron Tip Sensitive RF Level Sensor Instruction Manual and Parts List...

Страница 2: ...nstallations If equipment is used in a manner not specified by the manufacturer protection provided by equipment may be impaired Notice of Copyright and Limitations Copyright 2004 Magnetrol Internatio...

Страница 3: ...Vertical Mounting 4 1 7 Installation Instructions 4 1 8 Wiring 4 1 8 1 Operating Mode Selection 5 1 9 Calibration 6 2 0 Reference Information 8 2 1 Description 8 2 2 Operating Principle 8 2 3 Troubles...

Страница 4: ...mber for future reference when ordering parts 1 2 Electrostatic Discharge ESD Handling Procedure Magnetrol s electronic instruments are manufactured to the highest quality standards These instruments...

Страница 5: ...oint Level Switches should be located for easy access for service calibration and monitoring Switches should not be exposed to ambient temperatures below 40 F 40 C or above 160 F 70 C Special pre caut...

Страница 6: ...Tip Sensitive Point Sensors are shipped assembled to the probe They may be installed in horizontally or vertically 1 6 1 Horizontal Mounting Unit will signal at probe level Refer to Figures 1 and 2 C...

Страница 7: ...source is turned off 2 Unscrew and remove housing cover 3 Pull power supply and control wires through conduit connection 4 Connect power leads to applicable AC or DC terminals as marked Refer to Figur...

Страница 8: ...means tanks material above the set point Loss of power The relay contact will open in all mode selections Relay contact will remain open until power is restored It will then assume a condition in acco...

Страница 9: ...gh level alarm refer to Section 1 8 1 Operating Mode Selection for proper jumper wire connection a With no material on probe turn zero adjustment con trol fully counterclockwise 20 turns Refer to Figu...

Страница 10: ...ectronics 2 2 Operating Principle As the medium covers the sensing probe the amount of capacitance between the probe and tank wall increases This capacitance is measured by the electronics When the ca...

Страница 11: ...Level Sensor 8 2 3 2 Switch Chatter 1 Check for low voltage 2 Check ground system 3 Check for turbulence Relocate probe or isolate from turbulence 2 3 3 Relay Will Not Reset Check probe for buildup or...

Страница 12: ...I Groups C D Class II Groups E F G Class III Type 4X AGENCY MODEL APPROVED APPROVAL CATEGORY APPROVAL CLASSES 2 4 Agency Approvals 2 5 Parts 2 5 1 Replacement Parts No Description Part Number 1 PC Bo...

Страница 13: ...ble SPST 5 amp 120 250 VAC resistive DC 1 Reversible SPST 5 amp 30 VDC resistive Response time 100 milliseconds Repeatability Better than 1 0 Ambient Temperature Electronics 40 to 160 F 40 to 70 C Ope...

Страница 14: ...del Number Voltage 80 8032 302 120 VAC 80 8032 312 240 VAC 80 8032 322 24 VDC 2 6 Specifications 2 6 2 Dimensional Data inches mm 3 4 NPT 3 4 NPT 3 50 89 Min length 4 00 102 14 00 356 std length 375 1...

Страница 15: ...50 606 Kotron Tip Sensitive RF Level Sensor 12 NOTES...

Страница 16: ...of the claim to be covered under the warranty If the trouble is the result of conditions beyond our con trol or is NOT covered by the warranty there will be charges for labor and the parts required t...

Отзывы: