Echotel Model 919 Ultrasonic Level Switch

2.6

Configuration

Configuration for Model 919 relay units is made by selecting either HL (high level), or LL (low level)
via the two-position switch on the PC board. Figure 11 can be used for proper failsafe configuration.

Configuration for the all voltage version is made by selecting either DRY-ON for high level failsafe, or
WET-ON for low level failsafe. Figure 12 can be used for proper failsafe configuration.

NO

CM

NC

Energized

De-energized

Energized

De-energized

"HL"

(High level

failsafe)

"LL"

(Low level

failsafe)

Mode

Level

Relay

Current

NO

CM

NC

NO

CM

NC

NO

CM

NC

Energized

De-energized

Energized

De-energized

between

7 and 500 mA

between

7 and 500 mA

less than 7 mA

less than 7 mA

"DRY-ON"
(High level

failsafe)

"WET-ON"

(Low level

failsafe)

Mode

Level

Load

Current

Figure 11

Failsafe Relay Configuration

Figure 12

Failsafe All voltage Configuration

Содержание STI Echotel 919

Страница 1: ...Installation and Operating Manual Ultrasonic Level Switch Echotel Model 919 Model 919 with sanitary fitting Model 919 with 3 4 NPT...

Страница 2: ...ion is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired...

Страница 3: ...m liquid level measurement in a wide variety of process media and application conditions The transducer uses a pair of piezoelectric crystals that are encapsulated in epoxy at the tip of the transduce...

Страница 4: ...aluminum foil Do not place boards on foam packing materials Use a grounding wrist strap when installing and removing circuit boards A grounded workstation is recommended Handle circuit boards only by...

Страница 5: ...ead tape If flanged bolt unit to mating flange with proper gasket The Valox housing can be rotated up to 330 degrees to align with the conduit Caution Never tighten unit on the tank connection by turn...

Страница 6: ...PROCEDURES 1 Make sure the power is turned off 2 Remove the housing cover 3 Prevent moisture seepage into housing by installing an approved seal drain fitting in the conduit run leading to the unit 4...

Страница 7: ...unit 4 Pull twisted shielded pair wire through the conduit connection 5 Connect the hot lead from the power supply to the middle 24 240 VAC VDC position of the terminal block 6 Connect the return lead...

Страница 8: ...high level failsafe or WET ON for low level failsafe Figure 12 can be used for proper failsafe configuration NO CM NC Energized De energized Energized De energized HL High level failsafe LL Low level...

Страница 9: ...housing 1 2 NPT 2 95 75 Echotel Model 919 Ultrasonic Level Switch 7 3 0 Reference Information 3 1 Troubleshooting 1 No signal with level change a Check wiring to make sure proper input voltage is supp...

Страница 10: ...bar maximum Process Temperature Without heat extension 40 to 250 F 40 to 120 C With heat extension 40 to 300 F 40 to 150 C Housing Material Valox PBT Ingress Protection NEMA 4X IP67 Shock ANSI ISA S71...

Страница 11: ...1 2 NPT conduit connection M Relay version with single PG 13 5 conduit connection R Relay version with single 1 2 NPT conduit connection 0 English actuation length in inches 1 Metric actuation length...

Страница 12: ...e factory inspection finds the cause of the claim to be covered under the warranty If the trouble is the result of conditions beyond our con trol or is NOT covered by the warranty there will be charge...

Отзывы: