Model 705 Menu: Step by Step Procedures
The following table describes the software menu displayed
by the Eclipse F
OUNDATION
fieldbus
™
transmitter for “Level
Only” measurement. Use this table as a step by step guide
to configure the transmitter.
The second column presents the menus shown on the trans-
mitter display. The displays are in the order they would
appear if the arrow keys were used to scroll through the
menu. The numbers on the first column are not shown in
the display. They are only provided as reference.
The fourth column provides the actions to take when con-
figuring the transmitter. Additional information or an expla-
nation of an action is given in the fifth column. (Shaded
sections are factory menu items).
5.1
Measurement Type: Level Only
display
Password
action
Comment
1
*Status*
*Level*
*AI1Lvl*
None
Transmitter Display
MeasType = Lvl Only
2
Level
xxx.x lu
None
Transmitter Display
All MeasType selections
3
AI1 Lvl
xx.x lu
None
Transmitter Display
All MeasType selections
4
PrbModel
(select)
User
Select
the type of probe used
Select from
7xa-x, 7xB-x, 7xd-x, 7xE-x,
7xF-E, 7xF-F, 7xF-x, 7xF-4, 7xF-P, 7xG-
x, 7xJ-x, 7xK-x, 7xL-x, 7xM-x, 7xn-x,
7xP-x, 7xQ-x, 7xR-x, 7xS-x, 7xt-x7x1-x,
7x2-x, 7x5-x, 7x7-x
5
PrbMount
(select)
User
Select
the type of probe
mounting
Select
from NPT, BSP or Flange
6
MeasType
(select)
User
Select
type of measurement
Select
from Lvl Only, Lvl&Vol, Intrface,
Ifc&Vol
7
SnsrUnit
(select)
User
Select
the Sensor units
Select
from cm, inches, feet, meters
8
Probe Ln
xxx.x su
User
Enter
the exact length
of the probe
11.8 to 900 in (30 to 2286 cm)
9
Lvl Ofst
xxx.x plu
User
Enter
desired Level reading when probe
is dry
-90 to 300 in (-228.6 to 762 cm)
10
Senstvty
xxx
Superuser or
user
adjust
gain value upward or downward
to sense liquid surface
(Superuser password required for dual
element probes.)
11
BlockDis
xx.x su
User
Enter
distance below reference point
where level is not sensed
-99.9 to 2286 cm (-39.3 to 900 in)
12
SftyZone
(select)
User
Select
behavior when level is sensed in
safety zone
Off, On, Latch
35