57-657 SIL Certified Safety Manual for ECLIPSE Model 706

Coaxial, twin flexible cable, and single element (rod or cable)
are the three basic configurations. As the probe configuration
establishes fundamental performance characteristics, the
probe for use with the ECLIPSE Model 706 transmitter
should be selected as appropriate for the application.

The Model 706 is designed for use in many applications in
process industries. Consult factory for assistance with probe
options.

Careful selection of probe design and materials for a specific
application will minimize media buildup on the probe.

Refer to Installation and Operating Manual 57-606 for
more information.

6.1.2 Environmental

Refer to Installation and Operating Manual 57-606 for
Environmental limitations.

6.1.2.1 Operating

The operating temperature range is -40 to +175 °F (-40 to
+80 °C).

6.1.2.2 Storage

The device should be stored in its original shipping box
and not be subjected to temperatures outside the storage
temperature range of -50 to +185 °F (-46 to +85 °C).

6.2

Installation

Refer to the Model 706 Installation and Operating Manual
57-606 manual for complete installation instructions.

• Contains information on the use, changing and resetting of

the password-protection function.

• Provides menu selection items for configuration of the

transmitter as a level sensing device.

• Offers configuration recommendations.

• Input voltage and loop resistance must be within the safe

operating  area of the device.

6.3

Skill Level of Personnel

Personnel following the procedures of this safety manual
should have technical expertise equal to or greater than that
of a qualified Instrument Technician.

Содержание Eclipse 706-512

Страница 1: ...n the output will be driven to the customer specified out of range signal i e 3 6 mA or 21 mA The Enhanced Model 706 is certified for use in low demand level measurement applications Application The H...

Страница 2: ...ronmental 6 6 1 2 1 Operating 6 6 1 2 2 Storage 6 6 2 Installation 6 6 3 Skill Level of Personnel 6 6 4 Necessary Tools 7 6 5 Configuration Information 7 6 5 1 General 7 6 5 2 Configuration 7 6 5 3 Wr...

Страница 3: ...the liquid level The amplitude of the reflection depends on the dielectric con stant of the product The higher the dielectric constant the larger the reflection 1 3 Determining Safety Integrity Level...

Страница 4: ...Serial Number shown on the name plates 3 0 Level Measuring System The diagram at left shows the structure of a typical measuring system incorporating the ECLIPSE Model 706 transmitter This SIL 2 3 Ce...

Страница 5: ...an Time To Repair MTTR SIL determinations are based on a number of factors including the Mean Time To Repair MTTR The analysis for the ECLIPSE Model 706 is based on a MTTR of 24 hours 5 0 Supplementar...

Страница 6: ...Manual 57 606 for Environmental limitations 6 1 2 1 Operating The operating temperature range is 40 to 175 F 40 to 80 C 6 1 2 2 Storage The device should be stored in its original shipping box and not...

Страница 7: ...nfiguration Ensure the Model 706 transmitter has been properly config ured for the application and probe Special consideration should be given to the following configuration parameters Dielectric Rang...

Страница 8: ...nse Times Continuous internal diagnostics are present within the Enhanced ECLIPSE Model 706 transmitter In the event a Fault is detected a message will appear on the LCD and the output current will be...

Страница 9: ...indicate OK b Choose the menu DIAGNOSTICS EVENT HISTORY Event Log i Any FAULT or WARNING messages must be investigated and understood ii Corrective actions should be taken for FAULT messages continued...

Страница 10: ...curves a Select DIAGNOSTICS ECHO CURVE View Echo Curve i Observe the present Echo Curve identify the characteristic portions of the waveform related to the FIDUCIAL Process level End of Probe and othe...

Страница 11: ...figuration parameters avail able via the Local User Interface during normal operation The end user will enable the User Password to lock out any end user modifiable configuration parameters avail able...

Страница 12: ...will respond to a change from the user s process within the safety function response time The Eclipse Model 706 shall transition to the Faulted Mode from the Normal Mode within the Diagnostic Test Int...

Страница 13: ...13 57 657 SIL Certified Safety Manual for ECLIPSE Model 706 9 0 Appendices 9 1 SIL Certificate...

Страница 14: ...14 57 657 SIL Certified Safety Manual for ECLIPSE Model 706 9 2 FMEDA Report exida Management Summary...

Страница 15: ...itself and its operating conditions The assumption of a constant failure rate is based on the bathtub curve Therefore it is obvious that the PFDavg calculation is only valid for components that have...

Страница 16: ...Mod Guideline on the Implementation of ANSI ISA 84 00 01 2004 Service Policy Owners of MAGNETROL controls may request the return of a control or any part of a control for complete rebuilding or replac...

Отзывы: