background image

18

57-600 Eclipse

®

Guided Wave Radar Transmitter

2.5.2 Intrinsically Safe

An intrinsically safe (IS) installation potentially has flam-
mable media present. An approved IS barrier must be
installed in the non-hazardous (safe) area. See Agency
Drawing – Intrinsically Safe Installation, Section 3.4.2.

To install Intrinsically Safe wiring:

1. Make sure the IS barrier is properly installed in the safe

area (refer to local plant or facility procedures). Complete
the wiring from the barrier to the ECLIPSE transmitter.

2. Remove the cover to the wiring compartment of the trans-

mitter. Install the conduit plug in the unused opening. Use
PTFE tape/sealant to ensure a liquid-tight connection.

3. Install a conduit fitting and pull the supply wires.
4. Connect shield to an earth ground at power supply.
5. Connect an earth ground wire to the nearest green ground

screw (not shown in illustration).

6. Connect the positive supply wire to the (+) terminal and

the negative supply wire to the (-) terminal.

7. Replace the cover to the wiring compartment of the

transmitter.

2.5.3 Explosion Proof

Explosion Proof (XP) is a method of designing equipment
for installation in hazardous areas. A hazardous location is
an area in which flammable gases or vapors are, or may be,
present in the air in quantities sufficient to produce explo-
sive or ignitable mixtures. The wiring for the transmitter
must be contained in Explosion Proof conduit extending
into the safe area. Due to the specialized design of the
ECLIPSE transmitter, no Explosion Proof conduit fitting
(EY seal) is required within 18" of the transmitter. An
Explosion Proof conduit fitting (EY seal) is required
between the hazardous and safe areas. See Agency
Specifications, Section 3.4.1.

To install Explosion Proof wiring:

1. Install Explosion Proof conduit from the safe area to the

conduit connection of the ECLIPSE transmitter (refer to
local plant or facility procedures).

2. Remove the cover to the wiring compartment of the

transmitter.

3. Connect shield to an earth ground at the power supply.
4. Connect an Earth ground wire to the nearest green ground

screw per local electrical code (not shown in illustration).

5. Connect the positive supply wire to the (+) terminal and

the negative supply wire to the (-) terminal.

6. Replace the cover to the wiring compartment of the

transmitter before applying power.

Current Meter

+

Test

Current Meter

Power Supply

24 VDC

+

(-) negative

(+) positive

G.P./I.S./Explosion Proof Model

Содержание eclipse 705

Страница 1: ...Guided Wave Radar Level Transmitter Enhanced Model 705 Software v3 x Installation and Operating Manual 2014 68 EU...

Страница 2: ...ctrostatic sensitive components This device complies with Part 15 of the FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This devi...

Страница 3: ...rocedure 21 2 6 5 1 Measurement Type Level Only 21 2 6 5 2 Measurement Type Level and Volume 24 2 6 5 3 Measurement Type Interface Level 27 2 6 5 4 Measurement Type Interface and Volume 30 2 6 6 Offse...

Страница 4: ...s a minimum of 6 150 mm below the process connection This may include utilizing a nozzle or spool piece to raise the probe Consult fac tory to ensure proper installation 1 1 Getting Started Before beg...

Страница 5: ...range of the process medium Upper layer dielectric for interface applications _____________ Loop Control Is the output current to be controlled by level or volume _____________ Set 4 0 mA What is the...

Страница 6: ...ly recommended to obtain 45 ft lbs This is a critical connection DO NOT LEAVE HAND TIGHT NOTE Universal connector can be supplied with lock screws for applications with significant vibration Contact f...

Страница 7: ...ired for configuration the default password is 0 from the LCD keypad 7 Lvl Units xxx LvlUnits xxx PrbModel select Probe Ln xxx x LvlOfst xxx x Dielctrc select Set 4mA xxx x Set 20mA xxx x Select the P...

Страница 8: ...erence when ordering parts Model Number Serial Number 2 2 Electrostatic Discharge ESD Handling Procedure Magnetrol electronic instruments are manufactured to the highest quality standards These instru...

Страница 9: ...the process connection size and type Coaxial probe 11 2 38 mm twin rod probe 17 8 47 mm transmitter 11 2 38 mm A torque wrench is highly desirable Flat blade screwdriver Digital multimeter or digital...

Страница 10: ...ure pressure dielectric and viscosity are within the probe specifications for the installation See Specifications Section 3 6 Model 7xD High Temp High Pressure probes should be handled with extra care...

Страница 11: ...be is acceptable 2 4 2 1 To install a rigid twin rod probe Make sure the process connection is at least 2 NPT or a flanged mounting Make sure that there is at least 1 25 mm spacing between the active...

Страница 12: ...0 32 set screws 3 on both securing devices using a 3 32 2 5 mm hex wrench and slide the securing devices off of the probe c Slide the TFE weight off of the probe d Cut and remove the required cable 4...

Страница 13: ...d connections tighten the hex nut of the probe process connection For flanged connections tighten flange bolts Probe can be stabilized by placing into a non metallic cup or bracket at the bottom of th...

Страница 14: ...designed for a 3000 lb 1360 kg pull down force for use in applications such as sand plastic pellets and grains It is offered with a maximum 75 foot 22 meter probe length Model 7x2 Single Rod dielectri...

Страница 15: ...s f Slide the weight back on to the probe g Reinstall the two cable clamps and tighten h Enter the new probe length inches or cm in software 2 4 4 4 To install a Model 7x2 bulk solids flexible single...

Страница 16: ...tter is facing the desired direction use a 11 2 38 mm wrench to tighten the universal connection on the transmitter to 45 ft lbs A torque wrench is highly rec ommended This is a critical connection DO...

Страница 17: ...dive Cl I Div 2 A general purpose installation does not have flammable media present Areas rated non incendive Cl I Div 2 have flammable media present only under abnormal conditions No special electri...

Страница 18: ...uipment for installation in hazardous areas A hazardous location is an area in which flammable gases or vapors are or may be present in the air in quantities sufficient to produce explo sive or ignita...

Страница 19: ...ION fieldbus information 2 6 1 Operating Parameters Some key information is needed to calibrate the ECLIPSE transmitter Complete the configuration information table in Section 1 1 2 2 6 2 Setting Up f...

Страница 20: ...r Enters the configuration mode Accepts a value and moves noted by an exclamation point to the next step of the as the last character in the top configuration program display line 2 6 4 Password Prote...

Страница 21: ...Transmitter Display LoopCtrl Level Transmitter default display showing Status Level Output and Loop values cycles every 5 seconds 2 Level xxx x Transmitter Display Transmitter displays Level Value in...

Страница 22: ...main in alarm until it is manually cleared with the SZ Alarm Reset below 21 20 SZ Height xx x lu Enter distance below BlockDis where SZ Fault will be asserted Enter a distance value that develops a sa...

Страница 23: ...tic parameter 46 Pos Ampl xxx Superuser Password Diagnostic parameter 47 Signal xxx Diagnostic Display Indication of level signal amplitude 48 Compsate select Superuser Password Select from None Manua...

Страница 24: ...x lu Enter desired Level reading when probe is dry Level Offset is the distance from the probe tip to the desired 0 level point 90 to 300 Refer to Section 2 6 6 12 VolUnits select Select the volume un...

Страница 25: ...ingle transmitter installation Poll address does not affect loop current 27 Loop Mode Enable Disable Determines whether the loop is fixed at 4 0 mA or controlled by the PV 28 Trim Lvl xx x lu Enter va...

Страница 26: ...sword Diagnostic factory setting 50 Signal xxx Diagnostic Display Indication of level signal amplitude 51 Compsate select Superuser Parameter Select from None Manual Auto 52 7xKCorr xxx Superuser Para...

Страница 27: ...nter the desired reading when probe is dry Level Offset is the distance from the probe tip to the desired 0 level point 90 to 300 Refer to Section 2 6 6 12 Upr Diel select Enter the dielectric constan...

Страница 28: ...ter installation Poll address does not affect loop current 27 Loop Mode Enable Disable Determines whether the loop is fixed at 4 0 mA or controlled by the PV 28 Trim Lvl xx x lu Enter value to adjust...

Страница 29: ...Calibration parameter 49 Scl Ofst xxx Factory Parameter Calibration parameter 50 Neg Ampl xxx Superuser Password 51 Ifc Ampl Superuser Password 52 Pos Ampl xxx Superuser Password 53 Signal xxx Diagnos...

Страница 30: ...x x lu Enter the desired reading when probe is dry Offset is the distance from the probe tip to the desired 0 level point 90 to 300 Refer to Section 2 6 6 14 VolUnits select Select the volume units Se...

Страница 31: ...l Adr xx Enter HART polling address number 0 63 Select a HART poll address 0 63 Enter 0 for a single transmitter installation Poll address does not affect loop current 31 Loop Mode Enable Disable Dete...

Страница 32: ...ameter 53 Scl Ofst xxx Factory Parameter Calibration parameter 54 Neg Ampl xxx Superuser Parameter 55 Ifc Ampl Superuser Parameter 56 Pos Ampl xxx Superuser Parameter 57 Signal xxx Diagnostic Display...

Страница 33: ...e 4 mA point at 24 inches and the 20 mA point at 60 inches as referenced from the bottom of the tank When the ECLIPSE transmitter is mounted in a chamber bridle it is usually desirable to configure th...

Страница 34: ...ts do not have to be used unused points should be left at 0 2 Strapping table point values can be entered or changed in any order 3 All strapping table points must be monotonic and sequential In other...

Страница 35: ...e terminal block in the electronics housing of the ECLIPSE transmitter HART uses the Bell 202 frequency shift keying technique of high frequency digital signals It operates on the 4 20 mA loop and req...

Страница 36: ...2 Trim Level 23 Date Time Initials 5 Probe Length 1 Probe Model 2 Probe Mount 1 Faults 2 Warnings 1 Loop Test 2 Present Status 3 Status History 4 Level Ticks 5 Fiducial Ticks 6 Fiducial Spread 7 Signa...

Страница 37: ...ith the H1 Foundation Fieldbus protocol operating at 31 25 kbits sec The H1 physical layer is an approved IEC 61158 standard The figure on page 38 shows a typical Fieldbus installation An IEC61158 shi...

Страница 38: ...regardless of manufacturer without a loss of functionality All FOUNDATION fieldbus devices must be tested for interoperability by the Fieldbus Foundation MAGNETROL Model 705FF device registration info...

Страница 39: ...ability The DD provides extended descriptions for each object and provides pertinent information needed by the host system DDs are similar to the drivers that your personal computer PC uses to operate...

Страница 40: ...is a revolutionary new level measurement technology The ECLIPSE electronics are housed in an ergonomic hous ing comprised of two tandem compartments angled at a 45 degree angle for ease of wiring and...

Страница 41: ...rface some of the energy continues down the length of the probe through the upper liquid The pulse is again reflected when it reaches the higher dielectric lower liquid refer to figure at left Since t...

Страница 42: ...ECLIPSE transmitter a waveguide with a characteristic impedance in air is used as a probe When part of the probe is immersed in a material other than air there is lower impedance due to the increase i...

Страница 43: ...enter for the read Universal Commands DDs are not installed in handheld latest DDs Level Reading on Display is stuck at Software believes probe is flooded Check actual level If probe is not flooded fu...

Страница 44: ...electric range 3 Replace with Model 7xR Overfill probe NoSignal No level signal being detected 1 Ensure dielectric setting is correct for measured medium 2 Increase sensitivity 3 Confirm that the prob...

Страница 45: ...Ramp circuit generating improper voltage Consult factory LoopFail Loop current differs from expected value Consult factory No Ramp No End of Ramp signal detected Consult factory DfltParm Internal non...

Страница 46: ...to form a clog or bridge between the elements causes the greatest degrada tion in performance High dielectric media e g water based will show as level at the location of the bridging Stratification I...

Страница 47: ...ELECTRIC RANGE a small amount to aid in reducing echoes in nozzle Increasing the DIELECTRIC setting reduces the gain which may cause instrument to lose level of lower dielectric media consult factory...

Страница 48: ...TANT Measured media inside vessel must be non flammable only If media inside vessel is flammable then the explosion proof version which contains an internal barrier making the probe Intrinsically Safe...

Страница 49: ...49 57 600 Eclipse Guided Wave Radar Transmitter 3 4 2 Agency Specifications Intrinsically Safe Installation...

Страница 50: ...50 57 600 Eclipse Guided Wave Radar Transmitter 3 4 3 Agency Specifications FoundAtIon fieldbus System...

Страница 51: ...Viton Z12 2201 237 Consult Factory for alternative O ring materials Housing cover without glass 004 9225 002 Housing cover with glass GP IS 036 4410 001 XP 036 4410 003 7xB Twin Rod Probe Shortening...

Страница 52: ...0 20 30 40 VDC GENERAL PURPOSE GP INTRINSICALLY SAFE IS EXPLOSION PROOF XP 20 5 mA 24 VDC 630 11 Maximum temperature of O ring not necessarily maximum process temperature Material Code Maximum Tempera...

Страница 53: ...l 7xB probe 1 2 inches 30 mm Specification for top 48 inches of single rod will be application dependent Accuracy may degrade when using manual or automatic compensation 57 600 Eclipse Guided Wave Rad...

Страница 54: ...r 800 F 1500 psig 427 C 103 bar 400 F 5500 psig 200 C 380 bar 7xQ 650 F 2400 psig 340 C 165 bar 7xS 575 F 1275 psig 300 C 88 bar Maximum Process Pressure 1000 psig 70 F 70 bar 20 C 1000 psig 70 F 70 b...

Страница 55: ...375 clearance between rods Two 25 6 mm dia cables 875 22 mm CL to CL 3125 8 mm diameter rod 875 10 mm diameter tube 6 15mm dia rod 1 75 44mm dia tube 6 15 mm diameter rod 1 75 44 mm diameter tube Pro...

Страница 56: ...0 40 60 80 100 120 140 160 100 150 200 250 Ambient Temperature F 300 Process Temperature F Ambient Temperature vs Process Temperature 350 400 180 200 0 100 200 300 400 500 600 700 800 900 1000 1100 12...

Страница 57: ...cess Conn 45 H 10 08 256 4 00 102 D Eclipse with 7xD Probe Threaded Connection Eclipse with 7xD Probe Flanged Connection Eclipse with 7xG Probe max 240 6 1 m 4 12 105 3 28 83 4 00 102 Elect Conn Qty 2...

Страница 58: ...t 10 oz 284 grams 3 00 76 3 00 76 Eclipse with 7x5 Twin Rod Bulk Solids Flexible Probe Flanged or NPT Connection 3 25 83 Probe Insertion Length 0 1875 Cable 316SS Weight 2 0 50 Probe Insertion Length...

Страница 59: ...57 1 25 3 88 99 TFE Weight 1 lb 454 grams 2 0 50 2 24 57 NPT Process Connection 7X1 12 00 305 7X2 3 00 76 0 1875 5 Cable Eclipse with 7x2 Bulk Solids Flexible Probe Flanged or NPT Connection 3 25 83 P...

Страница 60: ...osion Proof FM CSA Non incendive A Integral General Purpose Intrinsically Safe ATEX JIS EEx ia IIC T4 B Remote General Purpose Intrinsically Safe ATEX JIS EEx ia IIC T4 C Integral Explosion Proof ATEX...

Страница 61: ...P 5P 6P and 9P only J 316 316L SST NACE Construction K 316 316L stainless steel probe and process connection ASME B31 1 specifications model 7xS only N Enlarged coaxial probe 316 316L stainless steel...

Страница 62: ...37 11 2 900 1500 ANSI Raised Face Flange 38 11 2 2500 ANSI Raised Face Flange 43 2 150 ANSI Raised Face Flange 44 2 300 ANSI Raised Face Flange 45 2 600 ANSI Raised Face Flange 47 2 900 1500 ANSI Rai...

Страница 63: ...0 DIN 2527 Form E Flange EH DN 80 PN 320 DIN 2527 Form E Flange EJ DN 80 PN 400 DIN 2527 Form E Flange FA DN 100 PN 16 DIN 2527 Form B Flange FB DN 100 PN 25 40 DIN 2527 Form B Flange FD DN 100 PN 64...

Страница 64: ...user from installing an external XP seal adjacent within 18 to the device Fault A defect or failure in a circuit The current mA value unit defaults to 3 6 22 or Hold when a diagnostic condition occurs...

Страница 65: ...he choices are in inches and cm centimeters Waveguide See Probe Window A time slice variable that enhances system resolution Factory setting Intrinsic Safety A design or installation approach that lim...

Страница 66: ...be Mount Measurement Type Level Units Probe Length Level Offset Volume Units opt Strapping Table opt Dielectric Sensitivity Loop Control 4mA point 20mA point Damping Blocking Distance Safety Zone Faul...

Страница 67: ...em Value Value Value TROUBLESHOOTING Working Value Non Working Value FidTicks FidSprd Fid Type Fid Gain Window Conv Fct Scl Ofst Neg Ampl Pos Ampl Signal Compsate DrateFct Targ Ampl Targ Tks Targ Cal...

Страница 68: ...applicability of our warranty No claims for misapplication labor direct or consequen tial damage will be allowed Return Material Procedure So that we may efficiently process any materials that are ret...

Отзывы: