Magnetrol Echotel 910 Скачать руководство пользователя страница 2

2

WIRING

ELECTRICAL SPECIFICATIONS: 910

FAILSAFE – ALARM STATUS

JU1

AW2395

T1

J1

J2

K1

P1

LL

HL

TB3

R6

F1

C10

+

NO CM  NC

NO CM NC

L1 L2/N

AC/DC 
POWER

e.g. valve

e.g. lamp

contact
1

contact
2

DPDT
RELAY

L1 L2/N

+

+ TB1 –

TB2

TB3

Sensor plugs
(may be reversed)

240/120 V AC

24 V DC

Shield to green grounding screw

Cable gland

Low level failsafe

High level failsafe

NOTE:
With NO power, NO Contacts are Open.

NC Contacts are Closed.

LOW LEVEL FAILSAFE

HIGH LEVEL FAILSAFE

Description

Specification

Line Voltage (±10%)

240/120 V AC, 50-60 Hz – 24 V DC

Power Consumption

2.5 VA Nominal

Electronics Temperature

-40°C to +70°C (-40°F to +160°F)

Process Pressure/Temperature

55 bar at -40°C to +120°C (800 PSIG at -40°F to +250°F)

Response Time

0.5 s. typical

Repeatability

2 mm (0.078")

Output Relay

Goldflash relay

DPDT, 8.0 A resistive

Hermetically sealed relay

DPDT, 5.0 A resistive

Housing

IP 65, anti-corrosive painted, cast aluminium

Sensor material

316/316 L (1.4401/1.4404)

Failsafe

Field selectable high or low level alarm

Electromagnetic compatibility

Meets CE requirements (EN 61000-6-4 and EN 61000-6-2)

Approvals

ATEX 

II

1/2 G EEx d 

II

C T6 / EEx e 

II

T6

FM/CSA Non incendive and XP