41
48-640 E3 Modulevel
®
Displacer Level Transmitter - F
OUNDATION
fieldbus
™
8.3.3 device Status Parameter in the
transducer Block
The following table lists the conditions indicated in the
Device Status parameter. It also shows the affect the condition
has on PV status, Sub-Status and Limit, XD ERROR and
BLOCK ALARM are not affected by these conditions directly.
The first three conditions are Type Mode. If everything is
running normally and there are no Faults or Warnings, then
the device indicates it is “OK” an the local display and in
Device Status viewed from the F
OUNDATION
fieldbus
™
net-
work. If a password is entered through the local display, the
Transducer Block is taken Out of Service if it is not already
and the User Access or Factory Access will be indicated in
Device Status viewed from the F
OUNDATION
fieldbus. This
will indicate to the operator that an attempt is being made
to modify a parameter value. No indication is given on the
Fieldbus network if someone is only viewing parameters on
the local display.
The next set of conditions is device faults. The device will
most likely not be able to measure level correctly if one or
more of these conditions occur. The condition will be indi-
cated in Device Status and will affect PV Status, Sub-Status
and Limit as indicated.
device Status
PV Status
Quality
PV Sub Status
Limit
type
Label
Bit #
Value
Mode
OK
11
0x0800
Good
Non-Specific
Not Limited
Mode
User Access
2
0x0004
Bad
OOS
Not Limited
Mode
Factory Access
14
0x4000
Bad
OOS
Not Limited
Faults
Default Params
12
0x1000
Bad
Configuration Error
Not Limited
Faults
Primary Fault
9
0x0200
Bad
Device Failure
Constant Limited
Faults
Core Drop
8
0x0100
Bad
Sensor Failure
Low Limited
Faults
SecFaultHi
10
0x0400
Bad
Sensor Failure
High Limited
Faults
SecFaultLo
¿
13
0x2000
Bad
Sensor Failure
Low Limited
Warning
Default Cal
5
0x0020
No Effect
No Effect
No Effect
Warning
Hi Temperature
4
0x0010
No Effect
No Effect
No Effect
Warning
Lo Temperature
3
0x0008
No Effect
No Effect
No Effect
Warning
Cal Span
6
0x0040
No Effect
No Effect
No Effect
Warning
Initializing
1
0x0002
Uncertain
Initial Value
Constant Limited
Faults
Fault 1
15
0x8000
No Effect
No Effect
No Effect
Warning
Warning 2
0
0x0001
No Effect
No Effect
No Effect
Warning
Warning 1
7
0x0080
No Effect
No Effect
No Effect
¿
This fault disabled with interface
or density measurement.