Installation

Please note the installation diagram for installation. Firmly connect the fil-
ter with the connection to the threaded socket on the water supply network. 
Use the enclosed nuts and screw connections for this. The arrow stamped 
on the rotary connection (Fig. 1 + 2) must point in the direction of the water 
flow. Thanks to the brass connection that can be rotated 360°, the filter can 
be mounted on both vertical and horizontal lines. The filter must always be 
installed in the hanging position. Ensure that the seal between the flange and 
filter unit is properly seated. 

Note: Tighten the nuts crosswise!

Fig. 2 Domestic water 

station

Fig. 1 backwash filter

Water flow direction

Input

Input

Output

Output

Содержание HWS-1

Страница 1: ...magnetic Drinking water filter Operation manual magnetic einfach besser Backwash filter TWF 1 Domestic water station HWS 1...

Страница 2: ...74547 Unterm nkheim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing partner Michael Bader VAT ID No DE 255 018 730 Commercial register HRA 571362 Reg G...

Страница 3: ...nking water filter Inhalt General information 4 Scope of delivery 4 Intended Use 5 Requirement for the installation site 5 Installation 6 Start up 7 Pressure reducer 7 Maintenance 8 Backwash 8 Technic...

Страница 4: ...installed in the immediate vicinity of heat sources with high radiation temperature Scope of delivery magnetic backwash filter TWF 1 consisting of Backwash filter Connection flange including seal Scre...

Страница 5: ...r VGW or SVGW and technical data must be observed The installation site must ensure that the filter is protected from chemicals dyes solvents va pours and direct sunlight Observe flow direction markin...

Страница 6: ...y connection Fig 1 2 must point in the direction of the water flow Thanks to the brass connection that can be rotated 360 the filter can be mounted on both vertical and horizontal lines The filter mus...

Страница 7: ...ion and after every main tenance To do this use the highest possible operating pressure and visually check the filter for leaks Pressure reducer The pressure reducer is set to 4 bar at the factory Aft...

Страница 8: ...st be carried out if the water pressure in the pipe network decreases due to increasing contamination of the filter element Place a buck et under the filter only for installation without duct connecti...

Страница 9: ...Connection 1 DN 25 1 1 4 DN 32 1 DN 25 1 1 4 DN 32 Flow rate at Dp 0 2 bar m h 4 8 5 4 Flow rate at Dp 0 5 bar m h 3 3 Nominal pressure PN 16 16 16 16 Pressure area 1 6 1 6 Connection nominal size DN...

Страница 10: ...1 1 4 A Total height mm 355 355 B Installation height up to the middle of the connection mm 281 281 C Installation depth up to the middle of the connection mm 167 167 D Installation length with withou...

Страница 11: ...on HWS 1 1 1 1 4 A Total height mm 355 355 B Installation height up to the middle of the connection mm 281 281 C Installation depth up to the middle of the connection mm 167 167 D Installation length...