IMPULSE
®
•G+ Mini Technical Manual
November 2020
Page 53
5.1.3.2
Decel to Stop (B03.03 = 00)
Upon removal of the FWD or REV run command, the motor decelerates at a rate determined by the time set in
deceleration time 1 (B05.02) and DC injection braking is applied after the DC injection start frequency, D01.01, has
been reached. If the deceleration time is set too short or the load inertia is large, an overvoltage fault (OV) may
occur during deceleration. In this case, increase the deceleration time or check if the braking resistor is functioning
properly.
Figure 5-2: B03.03 = 00 (Decel to Stop) without DC Injection
Figure 5-3: B03.03 = 00 (Decel to Stop) with DC Injection