Magnelab Mini AC Current Transducer (CT) Connection Instructions

 

Connecting the CT to the FlexSmart TRMS Module 

 

Configuring the Data Logger for the CT using HOBOware Software 

HOBOware software provides configuration files for the CTs. The table below lists the recommended configuration values for 
each CT that these files contain. For information on loading configuration files, refer to the software documentation.  

 

 

 

HOBO H22 or U30 Series Data Logger

(H22-001 shown)

S-FS-TRMSA / S-FS-TRMSA-D

*

 

FlexSmart TRMS Module

T-MAG-0400-xx

Current Transformer

S1~

S1~

S2~

S2~

S-FS-TRMSA (or S-FS-TRMSA-D)

FlexSmart TRMS Module

Terminal Block

Wiring Diagram for Single CT

Black

White

See below for wire 
capture procedure

From CT

S1~

S1~

S2~

S2

~

S-FS-TRMSA (or S-FS-TRMSA-D)

FlexSmart TRMS Module

Terminal Block

Wiring Diagram for Two CTs

Black

White

From CT

Black

White

From CT

LOAD

LINE

3. Snap CT closed.

1. Open CT.

Source Face

2. Place CT around the 
individual wire carrying the 
phase to be monitored.

*

The S-FS-TRMSA-D has a modular connector for 

connecting to a Smart Sensor port and thus is compatible 
with both H22 and U30 series data loggers. The 
S-FS-TRMSA is compatible with the H22 series only.

S-FS-TRMSA-D

*

Onset Part No: 

Channel Name 

Raw Value 1 (mV) 

Raw Value 2 (mV) 

Scaled Value 1 

Scaled Value 2 

Scaled Units 

T-MAG-0400-05 Current 

333 

T-MAG-0400-20 Current 

333 

20 

T-MAG-0400-50 Current 

333 

50 

T-MAG-0400-75 Current 

333 

75 

HOBO H22, U30, or RX3000 Series Data 

Logger (H22-001 shown) 

*The S-FS-TRMSA-D has a modular connector for connecting 
to a smart sensor port and thus is compatible with H22, U20, 
and RX3000 series loggers. The S-FS-TRMSA is compatible 
with the H22 series only. 