L25-001 REV 2 (05/11)
1. INSTALLATION
Units are to be installed in non-combustible loca tions only to utilize a 0” minimum clearance to
non-combustible construction. Not approved for installations in combustible constructions.
This
installation must conform to local codes.
In the absence of local codes, the installation
must conform with the
National Fuel Gas Code, ANSI Z223.1
;
Natural Gas Installation
Code, CAN/CGA-B149.1;
or
Propane Installation Code, CAN/CGA-B149.2
as applicable.
•
The appliance and its individual shutoff valv e must be disconnected from the gas supply
piping system during any pressure testing of that system at te st pressures in excess of ½
psi (3.45 kPa).
•
The appliance must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure test ing of the gas supply piping system at test
pressures equal to or less than ½ psi (3.45 kPa).
A. Uncrate unit and put into place. The hitch pi ns securing burners must be removed. This will
permit the burners to be readily removed for weekly inspection, cleaning and future service.
B.
FOR INSTALLATION ON LEGS: A set of 6” legs
is packed in the top se ction of the broiler
(unless unit is specifically ordered without). A threaded receptac le is located near each corner
base of the machine. Each leg has a similar ma ting thread. Raise unit sufficiently to allow legs
to be screwed tightly into receptacles. Level the unit by adjusting bottom feet of legs. Unit must
be level to perform properly.FOR INSTALLATION WITH CASTERS: This installation shall be
made with a connector that co mplies with the Standard for
Connectors for Movable Gas
Appliances, ANSI Z21.69
,
or
Connectors for Moveable Gas Appliances, CAN/CGA-6.16
,
and with a quick-disconnect device that complies with the Standard for
Quick-Disconnect
Devices for Use With Gas Fuel, ANSI Z21.41
,
or
Quick-Disconnect Devices for Use With
Gas Fuel, CAN1-6.9.
•
Provide an adequate means of restraint wit hout depending on the gas connector, the quick-
disconnect device or its associated piping to limit the appliance movement.
•
The restraint (i.e. heavy gauge chain or c
able) should be 1000# test load and should be
attached to the building structure by some subs tantial means, such as the use of anchor bolts
into concrete, or lag screws into studs in wooden structures. The opposite end of the restraint
should be affixed solidly to the base of the uni t at the back where it will not become pulled out
or cause damage to the appliance.
If disconnection of this restraint becomes necessary at any time, make sure it is reinstalled after
the unit is placed in its original position and before the unit is placed in operation.
Only two of the four casters supplied have brak
es. Be sure to install the two casters with
brakes
at the front of the unit
.
NOTE:
Front brakes should be locked before unit is placed in
operation.
C. COUNTER MODELS: All counter equipment is to be sealed to
the counter to comply with
applicable sanitation standards. A bead of silicone sealant, approximately ½” wide, is to be
applied to the bottom of the uni t approximately ¼” in from the front, back and side edges. We
CAUTION !