Page 12 of 22
508197-01
Issue 2137
Model
Gas Heating
Indoor
Blower
Speed
0.1 “w.c.
0.2 “w.c.
0.3 “w.c.
0.4 “w.c.
0.5 “w.c.
Rise
Range
(F°)
Mid
Rise
(F°)
SCFM
W
atts
HP
Temp Rise
SCFM
W
atts
HP
Temp Rise
SCFM
W
atts
HP
Temp Rise
SCFM
W
atts
HP
Temp Rise
SCFM
W
atts
HP
Temp Rise
3 T
on
24MGE4-14-361*P
25-55
40
TAP 1
(COOL)
#
704 126 0.17
---
664 131 0.18
---
626 136 0.18
---
592 141 0.19
---
553 147 0.20
---
TAP 2
(COOL)† 1020 307 0.41
---
980 313 0.42
---
940 314 0.42
---
900 318 0.43
---
865 323 0.43
---
TAP 3
(COOL) N/A N/A N/A N/A N/A N/A N/A N/A 965 333 0.45
---
930 338 0.45
---
890 344 0.46
---
TAP 4
(HEAT)* 450 48 0.06
40 385 52 0.07
46 325 55
0.07
55 N/A N/A N/A
N/A N/A N/A N/A N/A
TAP 5
(HEAT)
N/A N/A N/A N/A N/A N/A N/A N/A 550 107 0.14
33 500 112 0.15
36 450 117 0.16
40
36MGE4-14-361*P
30-60
45
TAP 1
(COOL)
#
704 126 0.17
---
664 131 0.18
---
626 136 0.18
---
592 141 0.19
---
553 147 0.20
---
TAP 2
(COOL)† 1020 307 0.41
---
980 313 0.42
---
940 314 0.42
---
900 318 0.43
---
865 323 0.43
---
TAP 3
(COOL) N/A N/A N/A N/A N/A N/A N/A N/A 965 333 0.45
---
930 338 0.45
---
890 344 0.46
---
TAP 4
(HEAT)* 615 82 0.11
44 580 86 0.12
46 540 91
0.12
50 500 96
0.13
54 460 102 0.14
58
TAP 5
(HEAT)
N/A N/A N/A N/A 710 129 0.17
38 685 135 0.18
39 650 140 0.19
41 615 145 0.19
44
48MGE4-14-361*P
35-65
50
TAP 1
(COOL)
#
704 126 0.17
---
664 131 0.18
---
626 136 0.18
---
592 141 0.19
---
553 147 0.20
---
TAP 2
(COOL)† 1020 307 0.41
---
980 313 0.42
---
940 314 0.42
---
900 318 0.43
---
865 323 0.43
---
TAP 3
(COOL) N/A N/A N/A N/A N/A N/A N/A N/A 965 333 0.45
---
930 338 0.45
---
890 344 0.46
---
TAP 4
(HEAT)* 715 135 0.18
50 675 142 0.19
53 640 148 0.20
56 600 155 0.21
60 560 162 0.22
64
TAP 5
(HEAT)
N/A N/A N/A N/A 820 212 0.28
44 785 219 0.29
46 745 227 0.30
48 715 234 0.31
50
3 T
on
60MGE4-14-361*P
40-70
55
TAP 1
(COOL)
#
704 126 0.17
---
664 131 0.18
---
626 136 0.18
---
592 141 0.19
---
553 147 0.20
---
TAP 2
(COOL)† 1020 307 0.41
---
980 313 0.42
---
940 314 0.42
---
900 318 0.43
---
865 323 0.43
---
TAP 3
(COOL) N/A N/A N/A N/A N/A N/A N/A N/A 965 333 0.45
---
930 338 0.45
---
890 344 0.46
---
TAP 4
(HEAT)* 825 175 0.23
54 790 179 0.24
57 755 185 0.25
59 720 191 0.26
62 690 197 0.26
65
TAP 5
(HEAT)
935 240 0.32
48 905 246 0.33
49 870 254 0.34
51 845 260 0.35
53 815 266 0.36
55
N/A: Do not operate unit using this blower speed at this external static pressure.
† As shipped speed for Cooling operation. Blower speed must be field adjusted to speed Tap 3 for higher duct static applications.
* As shipped speed for Heating operation. Blower speed must be field adjusted to speed Tap 5 for higher duct static applications.
# As shipped speed for Low Stage Cooling operation (low duct static).
Table 4. Blower Performance (208V or 230V)
Filter
All return air must be filtered. A washable filter is furnished
with the unit, located in the return air opening.
If a filter is installed at a separate central return
location, then the factory furnished filter must be
removed from the unit.
If an installation is made in which it is more desirable to
mount the filter exterior to the unit, in the return duct work
or elsewhere, the washable filter can be used or replaced
with a disposable filter. If a disposable filter is used in lieu
of a washable filter, use the information provided in Table 5
when sizing the disposable filter.
Table 5. Minimum Required Surface Area for
Disposable Filters
Model Number
Filter Area (in
2
)
15MGE4-12-09*
175
24MGE4-12-09*
15MGE4-12-12*
24MGE4-12-12*
210
36MGE4-12-12*
285
15MGE4-12-18*
24MGE4-12-18*
36MGE4-12-18*
48MGE4-12-18*
325
60MGE4-12-18*
*MGE4-12-24*
385
*MGE4-12-30*
435
*MGE4-14-36*
480