magicpak HWC8 V Series Скачать руководство пользователя страница 7

507388-03

Issue 2110

Page 7 of 19

Electrical Connections

All wiring must be done in accordance with the National 

Electrical Code, ANSI/NFPA No. 70 (latest edition); or local 

codes, where they prevail. Any alteration of internal wiring 

will void certification and warranty.

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

Electrostatic discharge can affect electronic components. 

Take precautions during furnace installation and service 

to protect the furnace’s electronic controls. Precautions 

will help to avoid control exposure to electrostatic 

discharge by putting the furnace, the control and 

the technician at the same electrostatic potential. 

Neutralize  electrostatic  charge  by  touching  hand  and 

all tools on an unpainted unit surface, such as the gas 

valve or vestibule panel, before performing any service 

procedure.

 CAUTION

The rating plate indicates the operating voltage, phase, 

minimum  circuit  ampacity,  maximum  fuse  size,  and 

minimum voltage. Units must never be installed where 

voltage exceeds 10% over the voltage indicated on the 

rating plate.

Units are factory wired for a 230 volt power supply. If power 

supply is 208 volts, it will be necessary to change a wire 

connection on unit transformer from 240 volt terminal to 

208 volt terminal as shown on the wiring diagram.

Failure of the compressor as a result of operation on 

improper voltage voids the compressor replacement 

warranty.

A separate electric line with wire having a temperature rating 

of 60°C should be run directly from the main supply panel 

to the leads in the unit. Refer to the rating plate located on 

the unit for proper fuse or breaker size. Make sure the unit 

is electrically grounded in accordance with local codes or, 

in the absence of local codes, with the National Electrical 

Code, ANSI/NFPA No. 70 (latest edition) for installations 

in the U.S. 

See rating plate for minimum wire ampacity and size wire 

accordingly. 

Exterior Junction Box and Switch

If  local  codes  allow,  a  field  supplied  junction  box  and 

optional switch may be installed on the top panel to provide 

an exterior electrical wiring point and disconnect. A suitable 

junction box cover must be used. If a switch is used it must 

meet or exceed the electrical specifications shown on the 

unit rating plate. The junction box, cover, and (if used) 

switch are standard items that are locally available.

Installing an Exterior Junction Box

1.  Remove the two screws that secure the factory-

supplied cover over the rear half of the internal junction 

box. Keep the front cover in place. See Figure 4.

2.  Position a 4x4 junction box over the opening as shown 

in Figure 5. Make sure the junction box is pulled up 

against the front cover so that there is no gap. Remove 

a knock-out in the box to allow the unit wiring leads 

to extend into the bottom of the box. Pull the leads 

through the knock-out and into the box. Remove a 

knock-out for the main power supply leads.

3.  Secure the junction box to the top panel using screws.
4.  Connect the unit wiring leads to the main power supply 

or the switch as desired. Securely attach the cover to 

the junction box. When complete, the junction box 

should be as shown in Figure 6.

5.  The rear cover that was removed in Step 1 is not used 

and may be discarded.

Rear Cover

Front Cover

(Leave in place)

Figure 4. 

Содержание HWC8 V Series

Страница 1: ...ombustible materials near the furnace or warm air ducts The material may ignite by spontaneous combustion creating a fire hazard WARNING These units are not approved for mobile home applications Such...

Страница 2: ...03 Issue 2110 22 27 7 8 29 7 16 13 3 8 43 3 16 16 1 6 1 8 1 Supply Return Low Voltage Supply Line Voltage Box 1 3 4 8 2 3 4 1 1 2 2 7 8 18 1 4 2 2 1 2 Gas Inlet Condensate Drain HWC9 Only Return Supp...

Страница 3: ...tile or other combustible material other than wood flooring The grille side of the unit may be flush with or extend beyond the face of the exterior wall but should not be recessed more than 2 from the...

Страница 4: ...When properly nested the angle on top of the unit should line up with the top flange of the sleeve and should almost touch Fasten the unit to the sleeve with five screws furnished with the sleeve The...

Страница 5: ...could cause an unsafe condition 3 Insofar as is practical close all building doors and windows between the space in which the appliances remaining connected to the common venting system are located an...

Страница 6: ...losing the individual manual shutoff valve during any pressure testing of gas supply piping system at test pressures equal to or less than 1 2 psig or 14 W C If the piping system is to be tested at pr...

Страница 7: ...the unit Refer to the rating plate located on the unit for proper fuse or breaker size Make sure the unit is electrically grounded in accordance with local codes or in the absence of local codes with...

Страница 8: ...in the return duct work or elsewhere the permanent filter can be used or replaced with a disposable filter If a disposable filter is used refer to the information provided in Table 1 when sizing the...

Страница 9: ...e checked to see that none of the wiring is loose or missing Cooling chassis is charged with R410A refrigerant Blower The unit contains a direct drive multispeed blower The proper speeds have been pre...

Страница 10: ...6012P18A 45 75 60 TAP 1 HEAT 208 or 230 630 71 600 N A 570 N A 550 N A TAP 2 HEAT 208 or 230 770 58 740 60 715 62 690 64 TAP 3 HEAT 208 or 230 885 50 855 52 830 54 810 55 TAP 4 COOL 208 or 230 560 540...

Страница 11: ...ustment Screw Under Cap Gas Manifold Pressure Test Tap Model Rise Range F Mid Rise F Indoor Blower Speed Unit Voltage V 0 1 w c 0 2 w c 0 3 w c 0 4 w c SCFM Temp Rise F SCFM Temp Rise F SCFM Temp Rise...

Страница 12: ...ee times Should the burners fail to ignite within the three trials for ignition the ignition control will lock out for 1 hour before beginning another ignition cycle To reset the control turn the ther...

Страница 13: ...osen these screws to remove control board mounting bracket Ignition Control Board Remove these screws to remove Burner Assembly Igniter Combustion Inducer Gas Valve Primary Limit Mounted to Vest panel...

Страница 14: ...Verify proper operation after servicing WARNING Refer to Figure 8 for heating compartment component layout It is recommended that the furnace be inspected annually by a qualified service person Burner...

Страница 15: ...ew and pull the igniter out of the burner assembly 4 For reassembly follow the above steps in reverse order Rollout Switch If for any reason the heat exchanger becomes blocked the temperature sensitiv...

Страница 16: ...from the flue collector box end 6 Brush out the inside of the flue collector box 7 Brush out the inside of the flue tube extension 8 If soot buildup is excessive clean the combustion inducer wheel an...

Страница 17: ...507388 03 Issue 2110 Page 17 of 19 Figure 10 Wiring Diagram HWC 12 18 Wiring Diagrams...

Страница 18: ...Page 18 of 19 507388 03 Issue 2110 Figure 11 Wiring Diagram HWC 24...

Страница 19: ...507388 03 Issue 2110 Page 19 of 19 Figure 12 Wiring Diagram HWC 30...

Отзывы: