507388-03
Issue 2110
Page 11 of 19
Start-Up
For Your Safety Read Before Lighting
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury, or loss of life.
WARNING
This furnace is equipped with a direct ignition control.
Do not attempt to manually light the burners.
CAUTION
To Light Main Burners
1.
Turn off electrical power to unit.
2. Turn the thermostat to lowest setting.
3. Move the gas valve ON/OFF switch to the “ON”
4. Turn on electrical power to the unit.
5. Set the room thermostat to the desired temperature.
(If the thermostat “set” temperature is above room
temperature after the pre-purge time expires, main
burners will light.)
To Shut Down Main Burners
1.
Turn off electrical power to unit.
2. Move the ON/OFF switch to the “OFF” position (Figure
Figure 7. Gas Valve
Gas Inlet
ON/OFF
Switch
Gas Inlet
Pressure Test
Tap
Regulator Adjustment
Screw
(Under Cap)
Gas Manifold
Pressure Test
Tap
Model
Rise
Range
(°F)
Mid
Rise
(°F)
Indoor Blower
Speed
Unit Voltage
(V)
0.1“ w.c.
0.2“ w.c.
0.3“ w.c.
0.4“ w.c.
SCFM
Temp
Rise
(°F)
SCFM
Temp
Rise
(°F)
SCFM
Temp
Rise
(°F)
SCFM
Temp
Rise
(°F)
HWC8N4812P30A
30-60
45
TAP 1 (HEAT) *
208 or 230
780
46
755
47
730
49
710
50
TAP 2 (HEAT)
208 or 230
900
40
875
41
855
42
835
43
TAP 3 (COOL) †
208 or 230
530
510
490
465
TAP 4 (COOL)
208 or 230
570
545
530
505
TAP 5 (COOL) †
208 or 230
950
920
900
885
HWC8N6012P30A
45 - 75
60
TAP 1 (HEAT)
208 or 230
780
57
755
59
730
61
710
63
TAP 2 (HEAT) *
208 or 230
900
49
875
51
855
52
835
53
TAP 3 (COOL) †
208 or 230
530
510
490
465
TAP 4 (COOL)
208 or 230
570
545
530
505
TAP 5 (COOL) †
208 or 230
950
920
900
885
N/A: Do not operate unit in heating mode using this blower speed at this external static pressure outside of the proper temperature rise range.
NOTE: HWC**30A models shipped with Low and High stage Cooling taps connected for use of the two-stage system.
* As shipped speed for Heating operation
† As shipped speed for Cooling operation
Table 2.
Supply Airflow Performance (SCFM) as a Function of External Static Pressure