magicpak HWC8 V Series Скачать руководство пользователя страница 3

507388-03

Issue 2110

Page 3 of 19

Installation

General

These instructions must be hung on or near the furnace in 

a conspicuous place.

The MagicPak All-In-One™ HVAC system model HWC8 

V-Series™  units  are  self-contained,  gas-fired  heating 

with electric cooling models. The unit design has been 

certified by Intertek Testing Services for compliance with 

the latest edition of the American National Standard ANSI 

Z21.47 for direct vent central furnaces. The HWC8 models 

are certified to be in compliance with the latest edition of 

A.H.R.I. Standard 210/240. All models are design certified 

for heating operation when fired with natural or propane 

gas.

These installation instructions are intended as a general 

guide only, for use by an experienced, qualified contractor.

Inspection

The unit is shipped in one package, completely assembled 

and wired. The Evaporator drain tubing is in the cooling 

compartment behind the filter access panel.

If any damage is found, proper notation should be made on 

the carrier’s freight bill. Damage claims should be filed with 

the carrier as quickly as possible.

Check  the  rating  plate  to  confirm  heating  and  cooling 

capacities. The unit should be operated only with the type 

of gas and electrical supply noted on the rating plate.

In the State of Massachusetts:

This product must be installed by a licensed Plumber 

or Gas Fitter. When flexible connectors are used, the 

maximum length shall not exceed 36”. When lever-type 

gas shutoffs are used, they shall be T-handle type.

 WARNING

NOTE: 

Remove the chassis hold down shipping bracket 

before installation. These brackets are located on the 

outdoor side of the unit below the louver panels.

Location

The  design  is  certified  for  indoor  installation  only.  The 

interior portions of the unit may be surrounded by a closet 

with minimum clearances to combustible material held 

to 0” sides, 2” top, and 1” front and plenum. Adequate 

clearance must be provided to install gas line union and 

manual shutoff valve as well as providing accessibility for 

field wiring. Do not install directly on carpeting, tile, or other 

combustible material other than wood flooring.

The  grille  side  of  the  unit  may  be  flush  with,  or  extend 

beyond, the face of the exterior wall, but should not be 

recessed more than 2” from the face of the building and 

should not be obstructed with trees, landscape materials, 

or building structure.

There is no minimum clearance required on locating the 

unit to an interior corner of a building.

If the unit is to be enclosed, provisions should be made 

allowing access to the indoor side of the unit for changing 

filters and for inspection. At least 29” of unobstructed space 

should be provided in front of the indoor side, whether 

enclosed or not, to permit removal of the cooling chassis 

should repairs or inspection be required.

If the unit is installed in a residential garage, it must be 

located or protected to avoid physical damage by vehicles. 

Unit must be installed so the burners and ignition source 

are not less than 18” (457 mm) above the floor. This unit 

must be installed so that no electrical components are 

exposed to water.

This appliance should be installed in a location such that 

the vent outlet is located in the following manner:
1.  Distances to windows that open, building openings, or 

public walkways should be consistent with the National 

Fuel Gas Code Z223.1.

2.  For U.S. installations, the vent system shall terminate 

a  minimum  horizontal  clearance  of  4’  from  electric 

meters, regulators, and relief equipment. 

3.  Flue products will not cause degradation to building 

materials.

This furnace design is not listed for installation in mobile 

homes, recreational vehicles, or outdoors.

Use of Furnace as a Construction Heater

Allied Air does not recommended the use of these units 

as a construction heater during any phase of construction. 

Very low return air temperature, harmful vapors and 

operation of the unit with clogged or misplaced filters will 

damage the unit.

Units may be used for heating of buildings or structures 

under construction, if the following conditions are met:

•  The unit must be permanently installed per these 

installation instructions.

•  A room thermostat must control the furnace. The use 

of fixed jumpers that will provide continuous heating is 

not allowed.

•  The return air duct must be provided and sealed to the 

furnace.

Содержание HWC8 V Series

Страница 1: ...ombustible materials near the furnace or warm air ducts The material may ignite by spontaneous combustion creating a fire hazard WARNING These units are not approved for mobile home applications Such...

Страница 2: ...03 Issue 2110 22 27 7 8 29 7 16 13 3 8 43 3 16 16 1 6 1 8 1 Supply Return Low Voltage Supply Line Voltage Box 1 3 4 8 2 3 4 1 1 2 2 7 8 18 1 4 2 2 1 2 Gas Inlet Condensate Drain HWC9 Only Return Supp...

Страница 3: ...tile or other combustible material other than wood flooring The grille side of the unit may be flush with or extend beyond the face of the exterior wall but should not be recessed more than 2 from the...

Страница 4: ...When properly nested the angle on top of the unit should line up with the top flange of the sleeve and should almost touch Fasten the unit to the sleeve with five screws furnished with the sleeve The...

Страница 5: ...could cause an unsafe condition 3 Insofar as is practical close all building doors and windows between the space in which the appliances remaining connected to the common venting system are located an...

Страница 6: ...losing the individual manual shutoff valve during any pressure testing of gas supply piping system at test pressures equal to or less than 1 2 psig or 14 W C If the piping system is to be tested at pr...

Страница 7: ...the unit Refer to the rating plate located on the unit for proper fuse or breaker size Make sure the unit is electrically grounded in accordance with local codes or in the absence of local codes with...

Страница 8: ...in the return duct work or elsewhere the permanent filter can be used or replaced with a disposable filter If a disposable filter is used refer to the information provided in Table 1 when sizing the...

Страница 9: ...e checked to see that none of the wiring is loose or missing Cooling chassis is charged with R410A refrigerant Blower The unit contains a direct drive multispeed blower The proper speeds have been pre...

Страница 10: ...6012P18A 45 75 60 TAP 1 HEAT 208 or 230 630 71 600 N A 570 N A 550 N A TAP 2 HEAT 208 or 230 770 58 740 60 715 62 690 64 TAP 3 HEAT 208 or 230 885 50 855 52 830 54 810 55 TAP 4 COOL 208 or 230 560 540...

Страница 11: ...ustment Screw Under Cap Gas Manifold Pressure Test Tap Model Rise Range F Mid Rise F Indoor Blower Speed Unit Voltage V 0 1 w c 0 2 w c 0 3 w c 0 4 w c SCFM Temp Rise F SCFM Temp Rise F SCFM Temp Rise...

Страница 12: ...ee times Should the burners fail to ignite within the three trials for ignition the ignition control will lock out for 1 hour before beginning another ignition cycle To reset the control turn the ther...

Страница 13: ...osen these screws to remove control board mounting bracket Ignition Control Board Remove these screws to remove Burner Assembly Igniter Combustion Inducer Gas Valve Primary Limit Mounted to Vest panel...

Страница 14: ...Verify proper operation after servicing WARNING Refer to Figure 8 for heating compartment component layout It is recommended that the furnace be inspected annually by a qualified service person Burner...

Страница 15: ...ew and pull the igniter out of the burner assembly 4 For reassembly follow the above steps in reverse order Rollout Switch If for any reason the heat exchanger becomes blocked the temperature sensitiv...

Страница 16: ...from the flue collector box end 6 Brush out the inside of the flue collector box 7 Brush out the inside of the flue tube extension 8 If soot buildup is excessive clean the combustion inducer wheel an...

Страница 17: ...507388 03 Issue 2110 Page 17 of 19 Figure 10 Wiring Diagram HWC 12 18 Wiring Diagrams...

Страница 18: ...Page 18 of 19 507388 03 Issue 2110 Figure 11 Wiring Diagram HWC 24...

Страница 19: ...507388 03 Issue 2110 Page 19 of 19 Figure 12 Wiring Diagram HWC 30...

Отзывы: