Magic-Pak MHP4-12 Series Скачать руководство пользователя страница 9

508196-01

Issue 2120

Page 9 of 18

Model Number

Filter Area 

(in

2

)

*MHP4-12-09* 

*MHP4-12-12*

265

3MHP4-12-18*
5MHP4-12-18*

310

7MHP4-12-18* 

10MHP4-12-18*

360

*MHP4-12-24*

400

*MHP4-12-30*

515

*MHP4-14-36*

600

Table 5. Minimum Required Surface Area for 

Disposable Filters

Condensate Drain

Provisions must be made to properly drain the primary and 

secondary drain pans of this appliance.

Primary drain and secondary drain connection: 3/4” NPT to 

3/4” PVC fitting (schedule 40 minimum). Both drains must 

be trapped as shown in Figure 7. The drain line should 

pitch gradually downward at least 1” per 10’ of horizontal 

run to an open drain.

Figure 7. Condensate Drain Installation

If local codes require the use of metal condensate lines, 

do not thread metal fittings into the unit drain pans. Thread 

a PVC fitting into the unit drain pans and make the field 

connection to the PVC fitting. 

NOTE: 

These units are designed with a redundant drain 

system  to  handle  condensate  without  the  need  for  an 

emergency drain pan. Should the indoor coil condensate 

drain system fail, all water is contained within the unit and 

the flow is directed into the unit base pan. From there it 

will drain into the condensate riser. If for some reason the 

water cannot drain into the main condensate riser, all water 

is contained in the unit, and the design will allow drainage 

out through the wall sleeve and louver to the outside of the 

building.

Use  thread  sealant  on  the  threaded  fittings.  Install 

threaded fittings by hand only. 

Do not over torque the 

fittings.

Do  not  thread  metal  condensate  fittings  to  unit  drain 

pans.

 CAUTION

Ventilation Air

Units ship with a panel installed that seals the return air 

compartment at the ventilation air intake. Installers can 

choose to remove the factory-installed panel and use 

the  field-provided  ventilation  damper  if  introduction  of 

ventilation air is desired. 

NOTE: 

If  ventilation  air  is  introduced,  the  quantity  of  air 

and conditions of this air must be accounted for in the load 

calculations. 

The  auxiliary  panel  has  nine  knockouts  to  configure 

ventilation air flow to installation requirements. Use Table 

6 and Figure 8 to determine which knockouts to remove 

from the auxiliary panel in order to achieve the desired 

ventilation air flow. Use a flat head screw driver to remove 

the knockouts. Set the factory-installed panel aside for 

possible future changes.

The location of ventilation air capable models must 

conform to the requirements of National Fire Protection 

Association NFPA No. 54 in regards to proximity 

of  forced  air  inlets  to  flue  gas  terminals.  Improper 

installation could result in personal injury or death.

 WARNING

Figure 8. Auxiliary and Factory Panel for Ventilation 

Air

Factory panel

Ventilation

Air Duct

Auxillary panel

with knockouts

1

2

3

4

5

6

7

8

9

Содержание MHP4-12 Series

Страница 1: ...llation These units are not approved for mobile home applications Such use could result in property damage personal injury or death WARNING General These instructions explain the recommended method of installation of the MagicPak All In One HVAC system model MHP4 electric cooling unit and associated electrical wiring These instructions and any instructions packaged with mating components and or ac...

Страница 2: ...e carrier s freight bill Take special care to examine the unit inside the carton if the carton is damaged File a claim with the transportation company If any damage is discovered and reported to the carrier do not install the unit as claim may be denied Check the unit rating plate to confirm specifications are as ordered Limitations The unit should be installed in accordance with all national and ...

Страница 3: ...imension B represents the height of the optional front return air duct opening J Return Air Opening K M Thermostat Wiring Connections Line Voltage Knockouts 7 8 and 1 1 8 Dia Top View 3 4 H 2 1 4 5 Supply Air Opening 1 6 1 16 28 H 6 1 8 Side View D A N Outdoor Fan Discharge Outdoor Coil F G E Rear View Return Air Opening Supply Air Opening Ventilation Air Chase Secondary Condensate Drain Pan 3 4 N...

Страница 4: ...ury or death Accessibility Clearances The front of the unit must be accessible for service A minimum clearance of 30 in front of unit is required for service If the unit is enclosed a door or access panel aligned with the front of the unit is the preferred method of providing access The door or access panel opening must be a minimum of 30 wide centered on the unit and be as tall as the unit Supply...

Страница 5: ...ASLEEVE 5 Orientation of Flange Two Positions Three Positions MHP4 12 09 12 Lower Lower Down MHP4 12 18 Up MHP4 12 24 30 Upper Middle MHP4 14 36 N A Upper Table 2 4 Place the unit into the wall sleeve Lift leading end of unit and walk unit onto the sleeve Once in the wall sleeve lower the unit into position This prevents damage to the base pads Assure that the unit is level and completely seated a...

Страница 6: ...heck unit supply and return air outlets for debris before making ductwork connections It is recommended that supply and return duct connections at the unit be made with flexible joints If flexible ducts are used a 6 sheet metal starter collar is required The supply and return air duct systems should be fabricated per the designed CFM and static requirements of the job see Table 3 Ductwork should n...

Страница 7: ...57 0 21 3 kW TAP 4 AUX HEAT 615 93 0 12 590 97 0 13 555 101 0 14 N A N A N A N A N A N A TAP 5 AUX HEAT 715 127 0 17 685 134 0 18 655 140 0 19 630 146 0 20 600 151 0 20 5 kW TAP 4 AUX HEAT 665 110 0 15 635 114 0 15 605 118 0 16 N A N A N A N A N A N A TAP 5 AUX HEAT 750 148 0 20 725 154 0 21 700 160 0 21 675 166 0 22 650 171 0 23 7 kW TAP 4 AUX HEAT 725 137 0 18 705 144 0 19 675 150 0 20 N A N A N...

Страница 8: ...1260 315 0 42 1230 328 0 44 1200 338 0 45 N A Do not operate unit using this blower speed at this external static pressure As shipped speed for Cooling operation Blower speed must be field adjusted to Speed Tap 3 for higher duct static applications As shipped speed for Heating operation Blower speed must be field adjusted to Speed Tap 5 for higher duct static applications Table 3 Blower Performanc...

Страница 9: ...he unit and the design will allow drainage out through the wall sleeve and louver to the outside of the building Use thread sealant on the threaded fittings Install threaded fittings by hand only Do not over torque the fittings Do not thread metal condensate fittings to unit drain pans CAUTION Ventilation Air Units ship with a panel installed that seals the return air compartment at the ventilatio...

Страница 10: ...sulated wires 18 AWG should be used to connect the thermostat to the unit Electrical Connections The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA No 70 latest edition or CSA C22 2 Part 1 latest edition Any alteration of internal wiring will void certification and warranty Units are factory wired for a...

Страница 11: ...ter the thermostat is satisfied NOTE The 7 2 and 10 kW heats strips offer a W1 and W2 thermostat connection Taking advantage of the two heat strip circuits requires a 3 stage thermostat Y for heat pump W1 for electric heat stage 1 and W2 for electric heat stage 2 If a 2 stage thermostat is used pigtail W1 and W2 wires together when connecting the thermostat wires at the unit Defrost Cycle If the o...

Страница 12: ...ate Drain Foreign material should not be allowed to clog the drain hole Inspect and clear drain opening prior to each heating and cooling season The defrost control is also equipped with a set of pins to aid in the troubleshooting of the defrost system see Figure 11 The following is a brief outline of the testing of the defrost system 1 Defrost sensor must be closed 32 F or below If temperatures a...

Страница 13: ...all sleeve and louver accessories for safe operation Improper installations could result in property damage personal injury or death WARNING Refer to Table 9 for dimension information B 29 1 8 Required Wall Opening C Maximum Wall Thickness Exterior Wall 16 A 16 5 8 29 Wall Sleeve Figure 12 ...

Страница 14: ...AL 7 32 3 4 32 7 8 8 ASLEEVE10 2 ASLEEVEXT4 2 ALVRP 2 ALVRAL 7 32 3 4 32 7 8 10 14 ASLEEVE12 2 ASLEEVEXT4 2 ALVRP 2 ALVRAL 7 32 3 4 32 7 8 12 16 ASLEEVE6 5 ALVRP 3 45 45 1 8 6 ASLEEVE8 5 ALVRP 3 45 45 1 8 8 ASLEEVE10 5 ASLEEVEXT4 3 ALVRP 3 45 45 1 8 10 14 ASLEEVE12 5 ASLEEVEXT4 3 ALVRP 3 45 45 1 8 12 16 ASLEEVE6 5 ALVRAL 3 ALVRALC 3 45 45 1 8 6 ASLEEVE8 5 ALVRAL 3 ALVRALC 3 45 45 1 8 8 ASLEEVE10 5...

Страница 15: ...508196 01 Issue 2120 Page 15 of 18 Wiring Diagrams Figure 13 Wiring Diagram MHP with Single Circuit and Hard Start Enabled 0 75 Ton through 2 5 Ton ...

Страница 16: ...Page 16 of 18 508196 01 Issue 2120 Figure 14 Wiring Diagram MHP with Dual Circuit and Hard Start Enabled 0 75 Ton through 2 5 Ton ...

Страница 17: ...508196 01 Issue 2120 Page 17 of 18 Figure 15 Wiring Diagram MHP with Single Circuit 3 Ton ...

Страница 18: ...Page 18 of 18 508196 01 Issue 2120 Figure 16 Wiring Diagram MHP with Dual Circuit 3 Ton ...

Отзывы: